Troubleshooting
Fixing a TP270 Touch Screen That Ignores Finger Presses
Short answer
When a TP270 6AV6545-0CC10-0AX0 keeps its picture and PLC traffic but takes no finger presses, the fault is in the panel's own flash, not the project: a corrupt calibration table or a damaged OS image. Back up, reset the operating system to factory settings with ProSave over the 6ES7 901-1BF00-0XA0 zero-modem RS232 cable, download the project again and calibrate. If the calibration still will not take, the touch front is worn out and the panel goes for service or replacement.
On this page
- Why the panel, not the project, is at fault
- Tell it apart from the look-alike faults
- Identify the exact variant first
- Back up before the reset
- Reset the operating system to factory settings
- Reload the project and calibrate the touch
- If the presses still do not land: service or replace
- Worked example: timing this panel's full-project serial transfer
- Questions asked
A TP270 (6AV6545-0CC10-0AX0) that keeps its picture and its PLC traffic but takes no finger presses is not throwing a project fault. In almost every case the panel's own flash is the problem: a corrupt touch calibration table or a damaged operating system image, and re-downloading the same project will not shift it. The fix runs in a fixed order. Back up, then use ProSave over the 6ES7 901-1BF00-0XA0 zero-modem RS232 cable to reset the operating system to factory settings, download the project again and calibrate the touch. The memory card backup you already took is your restore source. If the calibration still will not take after a factory image, the touch front itself is worn out and the panel goes for service or replacement.
Why the panel, not the project, is at fault #
The TP270's front is an analog resistive screen: a press closes two coated layers, the controller digitizes an X and a Y count, and a calibration table in the panel's flash translates those counts into pixel positions. The project only draws the buttons; it never touches that chain. So when the picture, the values and the alarms all stay live and no press registers, the fault is behind the glass, in one of three places:
- A corrupt or empty calibration table, typically after an unclean power-down, static discharge during handling or an interrupted transfer. Raw counts then map outside the active area and the panel looks deaf.
- A damaged operating system image after an aborted update or a failing memory module. The panel can boot far enough to draw a screen but not far enough to run its touch service properly.
- A worn front. The conductive coating ages in oily or dusty air, and sharp tools deform the spacer dots, leaving rows or columns that short or open. That is mechanical, and no image fixes it.
Tell it apart from the look-alike faults #
- Picture frozen on one screen, no values updating: that is the freeze fault with the PLC still cycling, covered in Why a TP270 touch screen freezes but the PLC keeps running, and it has different causes.
- Presses register but land offset from the finger: drift. Run the panel's own calibration first; that is a two-minute check. On the newer Comfort generation a calibration that will not save has its own causes, covered in Why a Comfort Panel touch calibration is not saving.
- Picture live, PLC traffic fine, zero response anywhere: the case in this article. Note the trap: the calibration routine itself needs the front to register its targets, so a completely deaf front cannot be fixed by calibrating. That is why the reset comes first.
Identify the exact variant first #
The order number on the rating plate decides everything that follows, because ProSave must be pointed at the right panel type and image. The panel in this case is the 6AV6545-0CC10-0AX0, the TP 270 10-inch touch panel with a 10.4-inch STN color display, 256 colors and 2 MB of configuration memory, configured with ProTool from version V6.0. An SIPLUS HMI TP 270 10 variant (6AG1545-0CC10-4AX0) is built on the same hardware. The family came in more than one display size and each takes its own image, so match the number, not the front label. If ProSave asks for the OS image file, take it from the manufacturer's support portal, matched to this order number, never from a third-party copy.
Back up before the reset #
The reset erases everything in the panel, so the backup is not optional. Keep the external memory card copy you already made as the primary restore source and do not overwrite it. Add a second copy if the serial link cooperates: in ProSave, back the panel up to a file over the same cable, then check the archive has a real file size and a date before moving on. If the front is too dead to drive the panel's own menus, trigger the backup from the PC side, the workaround spelled out in How to back up an HMI with a scratched touchscreen before replacement.
Reset the operating system to factory settings #
Run this with the machine stopped and the PLC in a safe state: the panel is off line for the whole procedure and the operator has no screen meanwhile.
- Power the panel down and connect the 6ES7 901-1BF00-0XA0 zero-modem cable from the PC's serial port, or a USB-to-RS232 adapter, to the panel's RS232 port.
- Start ProSave, select the TP270 10-inch panel type, the serial connection, your COM port, and leave the rate at 38400 bps.
- Open the OS update function and run the reset to factory settings. This is a service channel: ProSave drives the panel from the PC over the cable, so a front that takes no presses is no obstacle.
- If ProSave cannot reach the panel, drop the rate to 19200 bps and retry before suspecting the hardware.
- Wait for the completion message. The panel reboots on the factory image with the project gone, which is exactly why the backup came first.
Reload the project and calibrate the touch #
- The factory image boots with default settings, so open the panel's transfer settings and enable the connection you will use for the download.
- Download the project again from ProTool, or restore the archive from the memory card or the ProSave backup.
- Start the touch calibration on the panel and touch each target exactly as it appears, through the corners, then confirm at the center.
- Prove it before closing the door: press all four corners and several buttons. Every press must act where the finger lands, twice in a row.
If the presses still do not land: service or replace #
After a factory image and a clean calibration attempt, the remaining outcomes are hardware:
- The calibration targets take nothing anywhere: the front is electrically dead, and no software step remains.
- The calibration takes but a strip or one quadrant stays deaf: the conductive layer is worn or the front is deformed, and repeated recalibration will not hold it.
Either way the panel goes for service, and the front replacement quote is the number to weigh. Two replacement routes answer the same question of what fills the hole in the door: the decision is worked through in Is a TP277 a drop-in replacement for a TP270 touch panel, and the other route is a PC-based operator station with the HMI runtime on industrial panel PCs and touchscreen computers instead of a proprietary terminal. Any successor also has to answer to the 61.00 x 41.00 x 18.00 cm envelope and the cut-out already in your door.
Worked example: timing this panel's full-project serial transfer #
The reader's case, with the numbers put to it. Inputs: the 6AV6545-0CC10-0AX0 carries 2 MB of configuration memory (product data sheet, read as 2 × 1024 KB), the transfer rate is 38400 bps with a 19200 bps fallback (the ProSave settings above), and asynchronous serial framing puts 10 bits on the wire per byte (1 start, 8 data, no parity, 1 stop). The rule in words: transfer time equals the bytes moved, times the bits per byte, divided by the bits per second.
Arithmetic:
- Bytes: 2 × 1024 × 1024 = 2,097,152 bytes
- At 38400 bps: 38400 ÷ 10 = 3840 bytes per second; 2,097,152 ÷ 3840 = 546 s ≈ 9 minutes
- At 19200 bps: 19200 ÷ 10 = 1920 bytes per second; 2,097,152 ÷ 1920 = 1092 s ≈ 18 minutes
Result: the wire-time floor for a full-memory restore is about 9 minutes at the default rate and about 18 minutes at the fallback, before ProSave's handshaking and retries stretch it.
Decision: budget 20 minutes for a full project restore at the default rate and 40 minutes at the fallback; a transfer still crawling past those marks gets stopped, the cable reseated and the rate changed. The OS image the reset loads is larger than the project, so give that step correspondingly longer and never interrupt it: an interrupted reset is one of the ways the image gets damaged in the first place.
Questions asked
Can I still order a replacement 6AV6545-0CC10-0AX0?
The 6AV6545-0CC10-0AX0 is listed by its manufacturer as a spare part only, meaning it is out of series production, so a like-for-like swap is not a safe plan for a running line. After a failed calibration the realistic choices are a service exchange for the front or one of the two replacement routes described in this article.
Can I reload the project over MPI or PROFIBUS instead of the serial cable?
Yes. The serial port with the 6ES7 901-1BF00-0XA0 cable is the service channel ProSave uses for the factory reset, but the project download itself can also run through the panel's MPI or PROFIBUS-DP interface, which is usually the faster route back into production. Only the reset insists on the serial link.
ProSave does not find the panel. What do I check?
First the cable: it must be a zero-modem type like the 6ES7 901-1BF00-0XA0, not a straight-through extension cord. Then the PC side: the COM port selected in ProSave must be the one the adapter actually took, because USB-to-RS232 adapters renumber freely. Then step the rate down one notch and retry. A panel that stays silent at the slow rate has a failed port or worse and goes to service.
What exactly does the factory reset erase?
Everything the panel stores: the project, its user and runtime passwords, recipe and logged values, and the interface settings. Only the copies you made survive, so restore the backup before typing anything in by hand, and fall back to the older ProTool project only if the backup itself predates the fault.
The calibration holds for a shift, then presses drift again. Is the reset worth repeating?
No. A calibration that will not hold for more than a few days points at hardware, not at the image: either the conductive coating in the front is wearing through or the panel's 24 V supply is noisy. Run the panel on a clean bench supply for a day; if the drift disappears, fix the supply in the cabinet; if it stays, the front goes to service.