Why a ProSave Backup Cannot Migrate a Panel PC ProTool Project

HMI and touchscreens Published 6 min read

Short answer

No. ProSave backs up and restores panel targets only, and no PC or Panel PC appears in its device list, so a Panel PC 677B backup is not something ProSave produces or that any migration tool can import. The ProTool to TIA Portal route needs the editable ProTool configuration project and runs through WinCC flexible 2008 SP3 or SP5; with runtime only, reinstall ProTool runtime on a compatible 32-bit Windows PC or virtual machine.

On this page
  1. What ProSave backups can and cannot do
  2. Why a backup is not a project
  3. Find the file that can migrate
  4. The migration route, once you have the project
  5. Worked example: three inventories, three decisions
  6. Runtime-only fallback for the Panel PC 677B
  7. The decision
  8. Questions asked

A ProSave backup cannot be migrated, on a Panel PC 677B or on any other target. ProSave backs up and restores operator panels, and PC-based platforms do not appear in its device list, so your panel PC running ProTool never produces a ProSave backup in the first place. Even on a supported panel, the backup is a restore image, not editable engineering source, and no migration tool imports it. Migration from ProTool to TIA Portal needs the editable ProTool configuration project and runs in two conversions through WinCC flexible 2008 SP3 or SP5. If only the runtime application survives, the practical route is to reinstall ProTool runtime on a PC with a compatible Windows version instead of migrating.

What ProSave backups can and cannot do #

ProSave has two jobs: back up the project and system image of a supported operator panel to a file, and restore that file to a device of the same family. Its device selection is panels only — text displays, MP-series panels, Comfort panels. A ProTool Service Pack that expanded ProSave added targets such as the Mobile Panel 170 and an MP 370 Touch, still all panels. A PC or the Panel PC is not on the list: its ProTool runtime keeps the application as files on the unit's own storage, and a full copy of that unit is made with the platform's own imaging tools, not with ProSave.

So if a file on the panel PC is called a ProSave backup, one of two things is true: it was created on a real panel elsewhere in the plant, or it is an ordinary copied folder wearing the wrong name. Establish which before planning anything around it.

Why a backup is not a project #

Three artifacts get confused here, and they solve different problems:

  • A configuration project is the editable engineering source, created and edited in the ProTool configuration software. It holds screens, tags, alarm texts, recipes and controller connections in editable form.
  • A runtime application is the compiled output that ProTool runtime executes. Compilation is one-way: the runtime file contains no editable objects to import.
  • A backup is a restore image of what one device held. Restoring it reproduces the same application on a similar device; it creates no editable source.

Because migration translates engineering source, a backup gives the migration tool nothing to read. The rule holds across panel families too: as why an uploaded HMI copy is not an editable project explains, a restored or uploaded copy is not engineering source. On some panel types a ProSave upload can return an editable archive under specific settings, as covered in how to enable an editable project from a TP270 ProSave upload — but a PC-based target has no such route at all.

Find the file that can migrate #

Search in this order:

  1. The panel PC itself. Note where the runtime start-up entry points; the runtime location tells you the install layout, and project folders or an engineering installation may sit alongside it on the same unit.
  2. The engineering workstation that last edited the project. Configuration projects live where they were saved, not on the panel.
  3. Machine-builder handover documents and maintenance archives. Original project media is often in the commissioning folder.
  4. Network shares and old backups — USB sticks, CDs, copies of the project directory taken before earlier upgrades.

Then validate. Open each candidate in the ProTool configuration software on a copy, and compare screens, tag names, alarm texts and controller connections against the running machine. Record the installed runtime version and the communication components while you are at it; you need both for the next step. A project that opens cleanly can still be an older revision, so check it against the screens the operators actually use.

The migration route, once you have the project #

The documented route from ProTool to TIA Portal is two conversions, and both are mandatory:

  1. Convert the ProTool configuration project to WinCC flexible 2008, Service Pack 3 or Service Pack 5.
  2. Migrate the WinCC flexible project to your TIA Portal version.

Siemens' WinCC migration guide states that a ProTool project reaches TIA Portal only through WinCC flexible 2008 SP3 or SP5; there is no direct converter. The second step is covered in how to migrate a WinCC flexible project to TIA Portal, and the overall move from a ProTool project onto a new panel in how to migrate a ProTool HMI project to a new touch panel.

Work on a copy and keep the original untouched. Every conversion reports items it changed or dropped; classify each one rather than clearing messages to get a clean build. Before operators rely on the converted screens, prove writes, alarms and controller changes against the real machine on a bench — a screen that displays the wrong setpoint or suppresses an alarm is a safety problem, not a cosmetic one.

Worked example: three inventories, three decisions #

What the inventory finds Migration possible? Decision
An editable ProTool configuration project Yes, 2 conversions Convert to WinCC flexible 2008 SP5, then to TIA Portal, then compile for the new target
A ProSave backup plus a runtime folder, no project No Restore the backup only to a panel of the same family; no migration route exists
Runtime application only, no project, no backup No Reinstall the ProTool runtime on a compatible PC or a 32-bit virtual machine; continuity, not migration

The arithmetic for the first row: two mandatory conversions plus one compile before commissioning tests, three tool steps in total. The second and third rows give zero migration inputs, because a restore image and a compiled runtime carry no editable objects — the count of supported migration routes stays at zero no matter which TIA Portal version you own.

Runtime-only fallback for the Panel PC 677B #

If only the runtime application survives, you are not migrating; you are keeping an old application alive. The ProTool generation is a 32-bit Windows product — documented installations include 32-bit Windows 7 desktops — so a 64-bit-only replacement PC cannot run it. Check the release notes of your exact ProTool version for the supported Windows editions, then either install the runtime and the application files on a PC with such an edition, or set up a 32-bit virtual machine and run the runtime inside it. Verify the communication drivers, the licence and the connection to the controller inside the virtual machine before cutover; a runtime that runs but cannot reach the PLC stops the machine as surely as a dead panel. When the fallback means putting a new computer at the machine, industrial panel PCs are the hardware class built for that duty.

The decision #

  • Have the editable ProTool project: migrate, in two conversions through WinCC flexible 2008 SP3 or SP5, then compile for the new target.
  • Have only a backup or only the runtime: there is nothing to migrate. Restore the backup to a similar panel, or reinstall the ProTool runtime on a compatible 32-bit Windows PC or virtual machine.
  • Have a file called a ProSave backup on the panel PC: identify where it really came from, because nothing inside it can be converted to a TIA Portal project.

Questions asked

Can I restore a ProSave backup to a different device?

No. ProSave restores a backup to a device of the same family as the one it came from, and its device list contains panel targets only, with no PC or Panel PC entry. A restore also reproduces the same application; it never returns an editable project, so even a successful restore gives a migration tool nothing to import.

Which file migrates a ProTool project to TIA Portal?

The editable ProTool configuration project, the one created with the ProTool configuration software. The documented route is two conversions: first to WinCC flexible 2008 with Service Pack 3 or Service Pack 5, then from WinCC flexible to your TIA Portal version. A compiled runtime file and a ProSave backup cannot be imported at any step.

What if only the runtime application survives on the Panel PC?

Treat it as continuity, not migration. Install the ProTool runtime and the application files on a PC running a compatible 32-bit Windows edition, or inside a 32-bit virtual machine, then verify the communication drivers, the licence and the controller connection before cutover. Without an editable project, moving to a current panel means rebuilding the screens from documented machine behavior.

Keep reading

  • How-to

    Replacing an MP277 Touch Panel with a Panel PC

    A Panel PC 677 can replace an MP277, but as a migration, not a swap: retarget a copy of the project with WinCC flexible Advanced (a Powerpack upgrades an existing Standard license), then buy a PC Runtime license sized to the project's PowerTag count. The engineering license on the development PC does not authorize Runtime on the Panel PC.

    HMI and touchscreens

  • Selection guide

    How to Prove a PC-Based HMI Before Replacing Panel Terminals

    Use an isolated bench controller to compare candidate PC-based HMI runtimes. Test the read path, one write to a spare test tag, touch response, communication loss and automatic recovery. Check the deployed license on the target PC.

    HMI and touchscreens

  • How-to

    How to Migrate a ProTool HMI Project to a New Touch Panel

    A discontinued ProTool-era panel is replaceable without a rewrite only when the editable project file exists: migrate it under WinCC flexible 2008 with Service Pack 2, Advanced edition for ProTool Pro projects, then review every conversion message and adapt tags and screens for the chosen target. Without the .ptp file, budget the job as a rebuild.

    HMI and touchscreens

Importing a ProTool .lib library into WinCC Flexible