Troubleshooting
Why a TP700 Comfort download fails 0132:000002 despite ping
Short answer
Error 0132:000002 with ping and Flash LED working means discovery succeeds but the transfer connection does not. Select the PG/PC interface entry for your adapter that ends in TCPIP rather than ISO, put the TP700 in transfer mode or allow remote transfer, give the PC a unique static address, and confirm no second device answers at 192.168.226.140. Those four checks clear the error in almost every case.
On this page
Error 0132:000002, "Connection failed - The selected online target could not be reached", with ping and Flash LED both working means TIA Portal finds the TP700 Comfort but cannot open the transfer connection. Ping proves an IP device answers at 192.168.226.140. Flash LED proves TIA Portal identifies a panel over the selected path. Neither proves the panel's download receiver is active, and neither proves the interface binding carries the transfer protocol. Fix it in this order: the PG/PC interface entry ending in TCPIP, panel transfer mode, a unique static PC address, then duplicate-address exclusion. In this exact failure pattern the TCPIP entry and transfer mode together clear the error.
What ping and Flash LED actually prove #
The setup behind the error — TIA Portal V13 SP1, an S7-1200 CPU 1214C that already accepts downloads, and a TP700 Comfort at 192.168.226.140 — gives you three observations that people tend to merge. Keep them separate, because each validates a different thing:
| Observation | It proves | It does not prove |
|---|---|---|
| Ping returns with zero packet loss | An IP device answers at 192.168.226.140 | That the device is uniquely the TP700, or that its transfer receiver is active |
| Flash LED flashes the physical panel | TIA Portal can identify the panel over the selected access path | That the panel will accept a transfer |
| The HMI project compiles with zero errors | The project is valid | Anything about connectivity |
The successful PLC download proves a path to the S7-1200, not to the panel. The gap between seeing a device and loading it is a wide one: why an HMI is detected but project download fails walks the same divide on other panels. And if the TP700 sits at its initial start screen rather than in runtime, why an HMI transfer fails in initial start mode despite ping adds the extra step that state requires.
Set the PG/PC interface to TCPIP, not ISO #
The PG/PC interface list holds one entry per adapter and protocol variant, so the Realtek PCIe GbE adapter appears twice: once ending in TCPIP and once ending in ISO. The HMI download opens a TCP/IP connection to the panel's transfer service. With the ISO entry selected, identification such as Flash LED still succeeds while the transfer connection fails — precisely the symptom in front of you. Change this first.
- In TIA Portal, open "Extended download to device".
- Open the PG/PC interface list and select the Realtek PCIe GbE entry that ends in TCPIP, not the one ending in ISO.
- Refresh the accessible devices and select the TP700 at 192.168.226.140.
- Run Flash LED to confirm the same physical panel responds, then start the download.
If the transfer runs, you are finished. If the message returns, leave TCPIP selected and move to the panel.
Put the panel in transfer mode or allow remote transfer #
Transfer mode is the panel state in which the download receiver waits for an engineering station. A panel running the visualization with transfer disabled refuses the request, and it can refuse while still answering ping and Flash LED. SIMATIC HMI devices put this in their transfer settings, which include an option to enable or disable transfer. Two paths work:
- On the panel, open the transfer settings. When the runtime fills the screen and no startup square is visible, how to enter configuration mode on a touch HMI shows the way in.
- Confirm the Ethernet interface is the active one and that it shows 192.168.226.140.
- Enable transfer, and enable remote transfer too if downloads must start while the runtime is loaded.
- For the immediate test, start transfer mode on the panel itself and leave it at the transfer screen while you download from TIA Portal.
Starting transfer mode locally is the better diagnostic, because it removes any doubt about whether the running application accepts remote requests.
Give the PC a unique static address #
The engineering PC needs an address inside the panel's network, held statically for the whole session. Read the subnet mask from the panel's interface settings rather than assuming it. Worked example with an illustrative mask of 255.255.255.0 and a PC address of 192.168.226.10:
- 192.168.226.140 AND 255.255.255.0 = 192.168.226.0 — the panel's network
- 192.168.226.10 AND 255.255.255.0 = 192.168.226.0 — the PC's network
Both stations land in the same network, so no router is involved and a direct cable or a flat switch segment carries the transfer. With that mask, any address from 192.168.226.1 to 192.168.226.254 is valid for the PC, excluding the panel's .140, the PLC's address, and everything else already assigned. If the panel reports a different mask, repeat the AND with it; when the two results differ, the PC cannot reach the panel directly and you fix the address, not the software.
- Open the IPv4 properties of the Realtek PCIe GbE adapter and enter the static address and mask. Leave the default gateway empty for a direct commissioning link.
- Disable the PC's other adapters — wireless, VPN, any second network card — so Windows cannot route the transfer out a different interface.
- Repeat ping and Flash LED and confirm both still work through the Realtek adapter.
Rule out a duplicate at 192.168.226.140 #
A duplicate address produces exactly this mixture of results: one device answers ping, discovery identifies a panel, and the transfer connects intermittently or reaches the wrong Ethernet identity. Flashing the correct panel does not exclude a second claimant to the same address.
- From a command prompt, start a continuous ping:
ping -t 192.168.226.140. - Disconnect the TP700's network cable, or power the panel down. Do this only when the machine state allows losing the operator screen for a minute.
- Replies must stop completely. Any reply that continues with the panel disconnected means another device owns 192.168.226.140: find it, re-address every station uniquely, and retest.
- Reconnect the panel and confirm replies resume cleanly. Intermittent replies after reconnection mean the switch's address tables deserve a look as well.
Step 3 is the decision point: continued answers with the panel off the network is a failed uniqueness test, and no TIA Portal setting will fix it.
If the error still appears #
Two further causes fit this signature. First, host firewall or endpoint-security policy: ping uses ICMP, which many policies pass, while the TCP connection the transfer needs is blocked. Test from a station with an approved rule for the engineering software, or put the PC and the panel alone on a small commissioning switch. A permanently disabled firewall is not a fix.
Second, the project itself: a deactivated Ethernet (PROFINET) interface in the HMI station's hardware configuration is a reported cause of the same message, so verify in the project that the panel interface is enabled and its address matches the physical panel.
Note that 0132:000002 is not HMI-specific. It marks a PG/PC interface connection failure and also shows up on S7-1200 and S7-1500 downloads. When the PLC download already works, as it does here, the code points squarely at the panel transfer path.
Verify the transfer end to end #
- Compile the HMI project and expect zero errors.
- Leave the panel in transfer mode, or confirm remote transfer is enabled in its settings.
- Confirm the PG/PC interface is the Realtek PCIe GbE entry ending in TCPIP.
- Open "Extended download to device", select 192.168.226.140, and run Flash LED one last time.
- Start the download and watch both ends: TIA Portal shows transfer progress and the panel's transfer screen accepts the connection.
- When it finishes, start the runtime and open the edited screen.
Success is unambiguous: the panel shows transfer activity during the load, the edited screen appears after the runtime restarts, and the connection-failed message does not come back.
Questions asked
Why does Flash LED work when the download fails with 0132:000002?
Flash LED is an identification request, and a panel in runtime with transfer disabled still answers it. The download must instead open a TCP/IP connection to the panel's transfer receiver, and that receiver only waits for an engineering station while transfer mode or remote transfer is enabled. Both indicators can therefore be green while the transfer itself never starts. After changing either setting, run Flash LED once more so you know you are still talking to the same panel before retrying.
Does 0132:000002 mean the same thing on PLC downloads?
Yes. The code marks a PG/PC interface connection failure, and it appears on S7-1200 and S7-1500 downloads as well, with causes that sit on the engineering station, including Windows builds that break the interface binding. When the PLC and HMI downloads both fail with it, fix the access path first. When only the HMI fails while the PLC loads, as in this case, the panel's transfer readiness is the difference.
Can security software cause 0132:000002 after the TCPIP interface is selected?
Yes. Ping travels on ICMP, which many policies allow, while the TCP connection the transfer needs is blocked, so the panel keeps answering both ping and Flash LED. Put the PC and the panel alone on an isolated commissioning switch and retry. If the download runs there, add an approved exception for the engineering software through your security policy instead of leaving the firewall off.
How do I confirm which device answers at 192.168.226.140?
Ping the address, then run arp -a and note the MAC address bound to 192.168.226.140. Disconnect the panel and compare: an entry that keeps replying, or a MAC that changes between tests, means two devices share the address. The MAC's vendor prefix usually identifies the second device faster than walking switch ports does.