Troubleshooting
Why a TP900 Comfort Panel prints nothing on a PostScript USB printer
Short answer
When both a report and a screen print produce no page, the fault is in the shared path, not the report layout: printer readiness, the USB1 transport, or the exact printer model's real PostScript support. Print the printer's own configuration page, confirm the cable sits in its device socket and in the panel's USB1, keep the PostScript driver entry, and test a screen print before the report.

On this page
When both a report print and a screen print leave the printer silent on a TP900 Comfort, the report layout is not the suspect. Both jobs leave the panel through the same printer entry, the same port and the same driver, so the fault sits in that shared path: the printer is not ready, the job never crosses USB1, or the exact printer model does not interpret the PostScript data the panel generates. Installing a driver and selecting PostScript, USB1, landscape and draft changes what the panel sends and where it sends it; it cannot add PostScript to the printer. Work through the checks below in order, changing one variable per test.
One shared path behind both failures #
- A screen print comes from the
PrintScreensystem function and renders the current screen; a report is a configured document that runtime outputs through its print function. Different content, same printer entry, port and driver. - Both failing at once clears the report layout and leaves three suspects: the printer itself, the USB transport, and the printer's page-description language for its exact variant.
- Before you change anything, split "no sign of life" into observations: does the printer's display change, does a job appear in the printer's own status list, does the panel show a message? "No page although data arrived" and "no data arrived" lead to different fixes.
- If the print control is greyed out rather than silently failing, the cause is the viewer's print option, not the printer path; that is the case in Comfort Panel viewer print option disabled: the viewer, not the driver.
Prove the printer without the panel #
- Print the configuration page from the printer's own controls. If no complete page comes out, the trouble is paper, cover or consumable, and it belongs to printer service, not the HMI.
- Read two facts off that page: the exact model designation and the enabled page-description languages. HP LaserJet Pro 400 is a family name, and variants differ in which languages are fitted or enabled, so the label and the configuration page decide, not the family name.
- Decision: a configuration page that lists no PostScript means no panel setting will ever produce output. Leave that printer for the office and put a listed printer at the panel.
Verify the USB transport and the port #
- Connect the panel's USB host port straight to the printer's USB device socket, the square connector the printer receives jobs on. A front walk-up port meant for storage media does not accept a host job, and using it produces exactly this silence.
- Confirm the cable sits in the socket the panel's printer settings name as
USB1; a cable in USB2 or through a hub invalidates the port selection. For the test, one cable and no hub. - Respect the passive cable limit: the USB 2.0 specification allows 5 m per segment.
- Worked example: a 3 m cable extended by a 5 m extension gives 3 m + 5 m = 8 m, which is 8 m − 5 m = 3 m over the limit; such a link can enumerate yet stall on a print job. Replace it with one short cable — 2 m is right for a bench test.
Set the panel side once, then leave it #
- In the panel's Control Panel, under
Printers, select thePostScript V1.4entry with portUSB1, matching the documented printer selection for Comfort Panels. - Leave landscape and draft as they are while you isolate the fault.
- Restart the panel after saving the printer entry so runtime starts with the new configuration — with the machine in a safe state, because the operator loses the screen until runtime is back.
- Remember what the driver is: it generates PostScript on the panel, and interpretation happens in the printer. The same rule explains why a Comfort Panel will not print to a Brother label printer on USB: the transport can be healthy while the language is not.
Test a screen print, then the report #
- Trigger the screen print from a plain runtime screen and watch both devices; it exercises the whole shared path with no report configuration involved.
- Match what you observe to the next move:
| Observation | Meaning | Next move |
|---|---|---|
| No page, printer receives nothing | The job never left the port: cable, socket or USB1 selection |
One short cable in the device socket, confirm the port, retest |
| Printer receives data, then no page or a PostScript error | Transport works; this exact model is not interpreting the job | Enable the language per the printer's documentation, or fit a listed printer |
| Screen page prints, report stays silent | The shared path is good; the report's setup or runtime trigger is at fault | Check the report output and trigger in the project |
| Page prints, layout wrong | Everything downstream works | Adjust orientation and paper size in the printer entry |
- Only after the screen print succeeds, run the intended report. A report that still fails alone is a project-side check, not a printer fault.
The decision for each result #
- The printer's own page fails: service the printer; the panel was never involved.
- The page prints but lists no PostScript: this printer cannot serve the panel at any setting. Use a printer named on the released-printers compatibility list for the installed panel software.
- PostScript is listed yet the printer receives nothing: it is transport — single cable, device socket,
USB1confirmed. Still silent: test a second listed printer to split a dead panel port from a dead printer interface. - Data arrives but no page: the variant is not interpreting the job. Enable its PostScript mode as its documentation describes, or replace the printer with a listed one.
- Screen print works, report does not: stop touching the printer and fix the report trigger and output in the project.
Questions asked
The same printer prints fine from an office PC. Does that prove it works with the panel?
No. The PC sends whatever its own driver generated, often PCL or its own PostScript flavor, over its own connection. The panel sends only the PostScript its driver produces over USB. PC output proves the printer mechanics and consumables, never the panel-to-printer path.
Can the landscape and draft settings cause the silence?
No. Orientation and print quality change how an interpretable job is laid out on paper; they cannot stop data leaving the panel. Leave both untouched while you isolate the fault, so each test differs from the last by exactly one variable.
Does it matter that the project was built with TIA Portal V13 SP1?
Not for this fault. The engineering tool version does not identify the image installed on the panel. Read the image version in the panel's Control Panel and match it when you consult the released-printers compatibility list, because printer support follows the panel image.
Can the report go to a network printer instead?
No. Comfort Panels output to USB printers only; network printers are not supported. If the printer must stand away from the operator panel, keep the USB run within the passive cable limit of the USB 2.0 specification and select a printer named on the compatibility list.
Where do I find which printers are released for Comfort Panels?
Siemens publishes the compatibility list in its support entry titled Commissioning of released printers on the SIMATIC HMI operator panel, as a download under the available compatibility lists. Match the exact printer designation, not the family name, against the list for the installed panel software.