Why a Unified PC runtime cannot show panel screens in Collaboration

HMI and touchscreens Published 6 min read By IMDTouch engineering team

Short answer

A Unified PC runtime shows panel screens in Collaboration only after two independent checks pass: all participating devices sit at the same level of the TIA Portal project tree, and each panel screen is enabled as visible for collaboration. There is no provider or consumer setting; a screen window in the PC overview must reference the panel-owned screen.

On this page
  1. What Collaboration configures, and what it does not
  2. First check: one common project tree level
  3. Second check: collaboration visibility on each panel screen
  4. Worked example: three panels and one PC runtime
  5. Reading the failure point
  6. Loading the corrected configuration
  7. The decision for each case
  8. Questions asked

A WinCC Unified PC runtime can show panel screens in Collaboration once two independent checks pass. First, the PC runtime and every participating panel must sit at the same level of the TIA Portal project tree; while they do not, Collaboration cannot be configured between them and the panels never appear as providers. Second, each panel screen must be enabled as visible for collaboration; without that property, the panel appears in the selection without its screens. Neither check substitutes for the other. There is also no provider or consumer setting to search for: which device shows whose screens follows from who owns the screen that the screen window references.

What Collaboration configures, and what it does not #

Collaboration lets the runtime of one participating HMI device embed a screen owned by another participating device inside a screen window. The screen window, the ScreenWindow object, is the display element that holds one screen inside another. The device whose screen contains the window does the displaying; the device that owns the referenced screen does the providing. In the overview this article addresses, a runtime screen holding smaller screen windows from several panels, the PC runtime is the consumer and each panel is a provider.

That order is fixed by screen ownership, not by a setting. The runtime settings of the PC runtime include a Collaboration entry, and Siemens documents that Collaboration is always enabled in both directions, even when the collaboration connection is activated for only one collaboration device. A screen window on a panel that shows a runtime screen therefore proves the runtime-to-panel path and nothing about the overview. The panel-to-runtime path needs its own screen window on the PC runtime, referencing a panel-owned screen. A screen stays owned by the device it is configured under, wherever it is displayed: a panel showing a runtime screen is still displaying a runtime-provided screen.

First check: one common project tree level #

All devices in one project is not the same condition as all participants at one level of that project's tree. Collaboration is configured between devices that sit at the same hierarchy level. When a panel sits deeper than the PC runtime, the runtime's provider selection shows no panels at all, which reads exactly like a missing direction setting.

Two placements cause this in practice. The plant hierarchy lives under Project tree > Plant objects, and a panel assigned into a plant view appears there, on a branch below the project root. A PC runtime left directly under the project root is then at a different level from those panels, even though every device is in the same project and reachable over the network.

The project tree is an engineering hierarchy, not a map of the Ethernet network. Changing switch ports or IP addresses does not move a device in the tree, and two entries that look adjacent in the tree view are not at the same level unless they share a parent node. Open the parent of each participant and compare; if the parents differ, the levels differ.

After reorganizing, reopen the Collaboration configuration on the PC runtime side and read the provider selection again. The deciding result is concrete: the intended panels appear as selectable providers. A tidier tree without that result has fixed nothing.

Second check: collaboration visibility on each panel screen #

Participation configures the relationship between devices; screen visibility decides which screens that relationship exposes. Visible for collaboration is a property of each individual screen, set in that screen's properties inside the owning panel's configuration. Open each panel screen the overview needs and enable it there.

If the panel is selectable on the PC runtime but its screen is missing from the screen-window selection, this is the check that failed, and it can fail on a single screen of an otherwise correct project. Enabling it on one screen does not expose the panel's other screens, so walk the list screen by screen.

While you are there, read the owner of the screen you select. The screen window on the PC runtime must reference the panel-owned screen, not a similarly named screen that belongs to the PC runtime. A wrong owner produces a configuration that compiles and then shows the wrong content or nothing at all.

Worked example: three panels and one PC runtime #

Take the reported symptom with example numbers. A TIA Portal project contains one WinCC Unified PC runtime and three MTP panels. The PC runtime sits directly under the project root; the three panels are assigned to a plant-view node inside Plant objects, one branch deeper. Counting levels: the PC runtime sits at the root level and the panels sit one level below, so the participants are at two different levels, Collaboration cannot be configured, and the provider selection on the PC runtime lists no panels.

Reorganize so all four devices share one parent node and sit at the same level. The provider selection now lists all three panels. Each panel owns four process screens the overview needs, so 3 panels × 4 screens = 12 screens to set visible for collaboration. The overview screen on the PC runtime holds one screen window for each panel, so 3 screen windows in total, each referencing one panel-owned screen.

Decision after both checks: the panels are selectable, the 12 screens are selectable, and each window references its intended provider screen. Only then is the configuration ready to load.

Reading the failure point #

Use where the configuration stops to choose the next action:

  • Panel never appears in the PC runtime's provider selection: the device relationship is not configurable. Fix the tree level, move all participants to one common level, then reopen the configuration.
  • Panel appears, screens absent: the relationship is configured but the exposure is not. Enable visible for collaboration on each missing screen in the owning panel's configuration.
  • Screen selectable and referenced, window empty in operation: the engineering configuration succeeded; investigate the runtime. Read the diagnostic or access message before changing any setting, then confirm in order that the provider panel's runtime is running, the corrected configuration was loaded to both devices after the tree change, the PC runtime can reach the panel over the network, and no access restriction blocks the screen.
  • Runtime screen appears on a panel: the reverse direction works. It does not test the overview; configure the PC-side screen windows and test them separately.

Loading the corrected configuration #

Preserve the project before reorganizing devices, make the smallest change that demonstrates the required direction, and verify one panel and one screen end to end before adding the rest. Loading the corrected project to several panels at once has its own sequence; downloading a TIA Portal project to multiple HMI panels covers that procedure. One note that belongs here: do the tree reorganization and the reload during planned downtime, because reloading a runtime takes the operator's screens away until the load completes.

The decision for each case #

  • Panels not selectable on the PC runtime: project-tree level. Place the PC runtime and the panels at one common level; Collaboration becomes configurable between them.
  • Panel selectable, screens missing: collaboration visibility. Enable visible for collaboration on each panel screen the overview needs.
  • Both checks pass and the overview still runs empty: runtime diagnostics. Work through the provider runtime state, the loaded configuration, the network path and the access messages.
  • Runtime screens show on panels but panel screens are not offered on the runtime: that direction is not faulty, it only proves the reverse path. Configure the overview screen windows on the PC runtime.
  • If a remote view of the whole other panel is enough instead of embedded native screens, a VNC viewer object is a different mechanism with its own prerequisites; using a VNC viewer object on an HMI to display other panels covers it.

Questions asked

Can Unified Collaboration connect HMI devices from two separate projects?

Yes. The documentation for preparing Unified Collaboration includes connecting HMI devices from two projects and configuring screen windows from different projects. The same two rules still decide what you can select: the participating devices must sit at one common level in their project trees, and every screen you want to embed must be enabled as visible for collaboration. Configure the collaboration connection between the devices as you would inside a single project, then test one screen window from one provider before adding the rest.

Does the same-level rule apply when a panel only displays screens from the PC runtime?

Yes. The project tree rule applies to every pair of devices you try to configure, in both directions. If a panel cannot select the PC runtime as a provider either, that panel and the runtime are at different levels, exactly as in the panel-to-runtime case. Placing all participants at one common level once resolves every pairing in the project at the same time, which is faster than troubleshooting each direction as if it had its own cause.

Can one overview screen mix screens from several panels?

Yes. A screen can hold several screen windows, and each window references exactly one screen owned by one provider device. Mixing providers on a single overview screen is supported as long as every participating device pair passes the two checks and every referenced screen has collaboration visibility enabled. Test each window on its own: one window staying empty means that one provider or screen reference failed, not necessarily the whole overview.

Where is the setting that exposes a panel screen to Collaboration?

It is the visible-for-collaboration property of the screen itself, set in the properties of that screen inside the owning panel's configuration. It does not live in the PC runtime's settings or in the Collaboration connection entry. You set it screen by screen: open the panel's device configuration, open each screen the overview needs, and enable the property there. If a screen never shows up in the runtime's selection while its panel does, this property on that exact screen is the first thing to recheck.

Keep reading

  • Troubleshooting

    Why WinCC Unified PC Runtime shows a red topology line

    WinCC Unified PC Runtime communicates over IP only and does not take part in LLDP topology discovery, so a red line and an IRT port diagnostic describe an unvalidated drawing, not a broken HMI connection. Delete the PC Runtime port interconnection, keep the IP network, and verify the Runtime PC path separately.

    HMI and touchscreens

  • Troubleshooting

    Why TIA Portal V20 Cannot Reach WinCC Unified PC Runtime Over VPN

    A ping and an open TCP 102 prove only basic reachability. WinCC Unified download uses the HTTPS endpoint on port 443 plus runtime services, certificates and clock agreement, so repair the VM route, the firewall port list and the trust chain before touching the project.

    HMI and touchscreens

  • Troubleshooting

    Why a Unified Comfort Panel web client shows scrollbars

    On V17 Update 7 the panel-integrated web client has no fit-to-window setting, so a screen configured for the panel's native resolution overflows any smaller browser viewport. From V18 Update 1 you set size-fit on the Main screen window. Staying on V17, run the browser fullscreen or fit the layout from a UI.GetClientInfo script.