Explainer
Why a WinCC operator still reaches Windows during runtime
Short answer
No single WinCC setting keeps an operator on the runtime screen. Four independent layers do it together: the documented WinCC V6 key-combination disablements, taskbar auto-hide, WinCC Autostart, and a User Administrator split where Operator lacks the System change right and Administrator holds it. The maintenance route stays open — log in as Administrator in runtime, deactivate the project, and the desktop is back.
On this page
- Why one layer alone never holds
- Layer 1: disable the documented key combinations
- Layer 2: auto-hide hides the taskbar; it does not lock it
- Layer 3: WinCC Autostart holds project paths, not user rights
- Layer 4: the System change right in User Administrator
- Native WinCC and PCS7 projects take different fixes
- The bench test that proves the lockdown
- Questions asked
Keeping a WinCC operator off the Windows desktop is not one setting. The ways out of runtime are independent: keyboard combinations, the taskbar itself, a reboot that lands on the desktop, and the project's own deactivate-runtime control. Close one and the others stay open. The combination that holds on a WinCC 6.0 machine stacks four layers: disable the four key combinations the WinCC V6 documentation lists, auto-hide the taskbar, configure WinCC Autostart, and split User Administrator so Operator lacks the System change right while Administrator holds it. The operator then stays on the runtime screen; maintenance logs in as Administrator inside runtime, deactivates the project, and the desktop comes back. This is access control, not a machine safety function — the emergency stop and every function that protects a person stay in the PLC and the electrical safety circuit.
Why one layer alone never holds #
Four routes lead from runtime to the operating system, and each needs its own closure. The system security screen, task switching, the Start interface and window cycling are keyboard routes. The taskbar is a pointer route: hiding it changes what the operator sees, not what the bar can do. Ending the project reveals the desktop, so an application right has to gate that control. And a reboot without a startup configuration lands the machine on the desktop before anyone logs into anything.
Two failure shapes tell you which layer failed. If runtime stays open while another interface appears over it, an input route or the taskbar is still reachable. If runtime stops and the desktop appears, the deactivate control was operable or the reboot route was never closed. Name the shape before changing a setting.
Take every observation under the operator's own logins: the operator's Windows account and the operator's WinCC user. A maintenance session with broad Windows rights does not represent the operator's effective access, and a verdict taken from that seat is worthless.
Layer 1: disable the documented key combinations #
The manufacturer documents this for WinCC V6 in the FAQ titled "How do you lock typical Windows key combinations in WinCC V6?": Ctrl+Alt+Del, Alt+Tab, Ctrl+Esc and Alt+Esc can be disabled in the properties dialog for each computer in WinCC Explorer. Pull that procedure from the manufacturer's support documentation or your distributor before touching the machine; the switches and their exact wording belong to that procedure, not to memory.
Apply it to the runtime computer, start the project, and press all four combinations under the Operator login. Expected result: none of them reaches an operating-system interface. Press the plain Windows key in the same pass and record what it does, because keyboards and shells vary between machines.
Scope matters. The disablement belongs to WinCC runtime on that computer; it is not a Windows policy, and it guards nothing once runtime is closed. Outside runtime, the Windows account's own rights are what protect the desktop.
Layer 2: auto-hide hides the taskbar; it does not lock it #
Set the taskbar to auto-hide. The expected visual result is a screen that stays clean while runtime fills it, with the bar retracted out of the way.
Auto-hide is a visibility change, nothing more. The bar keeps every function it had, so judge this layer by what the operator can invoke, not by how the screen looks. Move the pointer to the activation edge during runtime with the Operator login. If the bar rises and its controls respond, the pointer route is open on that machine and the lockdown is not finished — more hiding will not close it.
In the four-layer combination the other layers carry the closure: the keyboard routes are already disabled and the System change right is withheld, so a raised bar has nothing to hand the operator. The pointer route and its verification are walked through in configuring WinCC runtime taskbar lockdown for HMI security.
Layer 3: WinCC Autostart holds project paths, not user rights #
Point WinCC Autostart at this project. After a reboot the machine starts the project in runtime by itself and never sits on the desktop waiting for someone to launch anything. With the layer 4 split in place, the rebooted client comes back into runtime as Operator.
The trap to skip: opening Autostart to look for user rights finds only project paths. Rights live in the User Administrator editor; startup behavior lives here. Hunting Autostart for an authorization that is not a startup setting wastes the afternoon.
Shutdown behavior has its own failure mode: if a stopped project leaves runtime hanging when the machine powers down, that is covered in why WinCC runtime stays open after project deactivation on shutdown.
Layer 4: the System change right in User Administrator #
Open the User Administrator editor from WinCC Explorer and create two WinCC users; Operator and Administrator are the working example names. The right that decides this question is named System change — not System rights, a near-miss name that sends the search to the wrong place. Set it for each user: grant it to Administrator, withhold it from Operator.
The effect is direct. With System change disabled for a user, that user cannot make system changes such as deactivating runtime: the deactivate control reads as dead under Operator and live under Administrator. That asymmetry is the maintenance route — log in as Administrator inside runtime, deactivate the project, and the desktop is available again.
Keep the two administrations apart in your head. A WinCC user called Administrator gains nothing in Windows; application rights and operating-system rights are separate layers, and the HMI login alone never changes Windows input handling — that is what layer 1 is for.
Two traps sit on this layer. System change was seen under WinCC 6.2 but not under WinCC 6.0, so if the installed editor does not list it, stop searching and gate your own deactivate-runtime control with a project-level authorization instead, as the next section sets out. The daily handling of these accounts — expiry, renames, password changes between shifts — is its own procedure, covered in managing WinCC runtime user accounts and password changes.
Native WinCC and PCS7 projects take different fixes #
Before applying any screen-level instruction, establish where the project came from. A project created in the PCS7 process-control toolchain carries a standard screen set; a native WinCC project built by hand carries none. A recipe written for one will not map onto the other, and that mismatch explains most of the confusion when documented steps appear to be missing.
The marks are concrete. @screen.pdl in the project marks the standard screen arrangement, and @buttons12.pdl marks the predefined control screen that ships with it. In a project that has them, the predefined control buttons gate on level 3 (Process controlling) — a project-specific assignment from that toolchain, not a native-WinCC permission. Read the authorization on the actual control before changing anyone's rights.
A hand-built native project has nothing inherited to enable: no @screen.pdl, no @buttons12.pdl. Program the deactivate-runtime control yourself and gate it with a project-level authorization that only maintenance holds; the layer 4 split then decides who can operate it.
Timing matters too. Keep the lockdown off the seat that programs: during commissioning the engineering environment stays open, and the four layers go onto the runtime client at handover, when the plant stops needing the development tools. Where the process-control toolchain and plain WinCC diverge, the working relationship is set out in how WinCC and STEP 7 work together in a PLC project.
The bench test that proves the lockdown #
Worked example, labeled as such: a machine running WinCC 6.0 with a hand-built project, tested at the bench before handover. Configure all four layers first — the combination disablements on the runtime computer, taskbar auto-hide, WinCC Autostart on this project, and the Operator/Administrator split in User Administrator — then run this sequence.
- Reboot. Expected: Autostart brings the project up in runtime by itself; no desktop appears.
- Log in as Operator, using the operator's own Windows account and WinCC user.
- Press Ctrl+Alt+Del, Alt+Tab, Ctrl+Esc and Alt+Esc, then the plain Windows key. Expected: no operating-system interface appears.
- Move the pointer to the screen edge. Expected: the bar stays down or rises dead. A bar that rises live fails the lockdown.
- Try the deactivate-runtime control. Expected: nothing happens under Operator.
- Log in as Administrator inside runtime and deactivate the project. Expected: the desktop returns under that session's Windows rights.
- Reboot once more. Expected: runtime again, straight back into the project.
| Route the operator can try | Layer that closes it | Bench verdict that proves it closed |
|---|---|---|
| Ctrl+Alt+Del, Alt+Tab, Ctrl+Esc, Alt+Esc | combination disablements on the runtime computer | every combination does nothing under Operator |
| Pointer to the screen edge raises the bar | auto-hide over a fullscreen runtime | the bar stays down or rises dead under Operator |
| Deactivate runtime from inside the project | System change withheld from Operator | the control is dead under Operator, live under Administrator |
| Reboot to reach the desktop | WinCC Autostart on this project | the machine returns straight into runtime |
Four passing verdicts close the lockdown and the machine can be handed over. A failing verdict names its layer: a combination that still works points at the disablements, a live bar at auto-hide, a desktop after reboot at Autostart, a working deactivate control under Operator at the System change split. Fix that layer and repeat the sequence from the first step. Where any verdict fails, the lockdown is not partially achieved; it is not achieved, and the machine stays with engineering.
Questions asked
Is keeping the operator off Windows a safety function?
No. The four layers control access to the operating system while WinCC runtime runs. Emergency stop, guard interlocking and every function that protects a person stay in the PLC program and the machine's electrical safety circuit, designed and verified to their own requirements regardless of what the HMI allows or blocks.
The documented list covers four combinations. Does the plain Windows key stay blocked?
The Windows key opens the same Start interface as Ctrl+Esc, which is why Ctrl+ESC is in the documented list. Keyboards and shells still vary between machines, so the bench test presses the plain key with the Operator logged in. If a Start interface appears, that route is open and the lockdown is not finished.
What changes in later WinCC releases?
In WinCC V7 the user administration is itself guarded: only users holding the authorization named "User administration" can use its button and accept the configured screen changes. Keep the maintenance account under change control, because whoever holds that authorization decides who holds every other one.
How does maintenance get back to Windows?
Log in inside runtime as the Administrator user, deactivate the project, and the desktop is available under that session's Windows rights. That session is the moment the machine is exposed, so keep it short and note the visit. With WinCC Autostart configured, a reboot brings runtime straight back, so no desktop session is left sitting at the machine.