Why a WinCC screen with many objects updates slowly

HMI and touchscreens Published 7 min read By IMDTouch engineering team

Short answer

There is no fixed object limit behind a slow WinCC screen. Update time scales with the number and type of dynamics on the picture, the work inside each VB action, and how many actions share one trigger. Read the Dynamics page totals, compare a fast picture in the same project, then consolidate repeated scripts and spread trigger load.

On this page
  1. What the 1 to 8 seconds is telling you
  2. Read the dynamics count, not the object count
  3. The load budget for a 600-object picture that takes 1 to 8 seconds
  4. Combine the repeated VB actions
  5. Spread the actions across triggers
  6. Verify each change
  7. Questions asked

There is no object limit to set or raise on a WinCC screen: a picture does not cross a line where it turns slow. What grows with size is work — the number and type of dynamics on the picture, the work inside each VB action, and how many actions come due on the same trigger. The pictures in this case carry more than 600 objects whose properties run through VB script, they take 1 to 8 seconds to update, other pictures in the same project stay fast, and a client shows the same delay. That combination points at picture design, not a platform ceiling. Read the dynamics totals first, work the load budget for your own picture, then consolidate the repeated scripts and spread the trigger load.

What the 1 to 8 seconds is telling you #

Picture update time here means the interval from calling the picture to seeing its objects sit in their intended runtime state. Split the symptom before changing anything: a picture that is slow to open carries concentrated initialization work, while objects that keep lagging after the picture has been open point at recurring dynamics and triggers. The two halves have different fixes, so decide which one you have.

  • Only the scripted 600-object pictures are slow. The shared design pattern is the suspect, not an object count.
  • The delay moves between 1 and 8 seconds. The workload or the trigger coincidence differs between update events, so look for actions that become eligible together.
  • Fast pictures exist in the same project. Compare picture implementation rather than project-wide settings, and keep one fast picture as the control case.
  • The client shows the same delay as the server. The same picture, dynamics and scripts run on both sides, so transport and client hardware drop down the list.

The opening half of the delay is the same effect that explains why WinCC Runtime faceplates load slowly on screen activation: work that must all happen as the screen comes up. One object type reading its tags slowly is the separate case behind why a WinCC VBScript table screen takes 20 seconds to open, where the cost sits inside a single object rather than across picture-wide dynamics.

Read the dynamics count, not the object count #

Open the inventory before editing anything. In WinCC Explorer, select Graphics Designer, right-click the PDL to analyse, choose Properties, and open the Dynamics page: it lists the total number of dynamics in that picture and the number of each dynamic type. Repeat the same inspection on one fast picture from the same project and compare the two by dynamic type, not by object totals.

Then classify the work the slow picture carries:

  • Map which object properties are controlled by VB actions, and mark every place where the same condition or value read repeats across many objects.
  • Group every action by its trigger type. The Triggers chapter of the WinCC documentation defines a cyclic trigger as an interval together with a starting point, so every action on that trigger becomes eligible together at each interval.
  • List tag-triggered actions separately, especially any attached to changing analog values.

A static rectangle and an object with several scripted properties both count as one object, and they cost very different runtime work. That is why the Performance Data chapter of the WinCC documentation ties cost to the complexity of the objects and the functionality inside the scripts rather than to counts of either.

The load budget for a 600-object picture that takes 1 to 8 seconds #

Run this arithmetic on your own picture; the numbers below are this case's.

The inputs, each with its source:

  • 600 objects carrying properties driven through VB script — the count in this case.
  • 1 to 8 seconds to update — the measured spread in this case.
  • The dynamics total for the real picture comes off the Dynamics page. The arithmetic below takes the worst case, that every one of the 600 objects carries exactly one scripted dynamic, so the picture holds 600 dynamics.

The rule in words: the average budget per dynamic equals the measured update time divided by the number of dynamics — the share of the update window one dynamic may consume if all of them are to finish inside it.

The arithmetic: at the slow end, 8 s ÷ 600 dynamics = 0.0133 s, about 13 ms per dynamic. At the fast end, 1 s ÷ 600 dynamics = 0.0017 s, about 1.7 ms per dynamic.

The result: each scripted dynamic in this picture holds between roughly 1.7 and 13 ms of window, and that slice must carry its tag reads, its condition checks and its property writes together. It is an average share, not a schedule; its use is as the comparison value for the decision below.

The decision: time one small action from this picture on its own. If a single action needs longer than its share — more than about 13 ms against the slow end here — then hundreds of copies cannot finish inside the observed window at any trigger setting, and consolidating the repeated scripts is the fix. If one action fits well inside its share, the remaining suspect is how many actions become eligible on the same trigger, which the trigger section below takes up.

Combine the repeated VB actions #

The general point in WinCC's scripting guidance is that a lot of small scripts usually run better combined into a smaller number of bigger ones. Merge by function, not by size:

  • One grouped action owns a coherent set of related properties, so the shared condition is calculated once instead of once per object.
  • The action writes a property only when its required state changes; reassigning an unchanged value spends runtime without moving the display.
  • The original decision logic survives the merge, and the list of properties each grouped action owns is recorded where the next engineer can find it.

Run this work where a dropped indication cannot matter — on a bench runtime, or with the machine in a state that does not depend on the affected display — because a merged script that hides a fault indication is a safety problem, not a tuning problem.

Watch the far end of the scale too: when one action is heavy enough to take whole seconds, a few of them per cycle stall a picture on their own, which is the pattern behind why HMI reset actions take seven seconds to finish. Time a single action before multiplying it.

Spread the actions across triggers #

When many scripts fall due in the same cycle, execution backs up and the picture waits on the queue. Put unrelated action groups on different triggers so only the ones that truly share an event run together, and keep simultaneous execution only where the process display needs the values to change as one event.

Treat the interval as a budget: the number of action starts each second equals the number of actions on a cyclic trigger divided by its interval in seconds, so shortening the interval multiplies the load in exact proportion. Choose the interval from what the operator must see — a status color that may run a second behind tolerates a slower trigger, while a fast-moving value needs a faster one.

Tag triggers belong where a tag transition is the event the display must react to, such as a step completing or a fault arriving. Keep them off rapidly changing analog tags, where every small change requests script execution the operator never sees and the trigger itself becomes the load. Scripted dynamics are not the only multiplier: plain tag bindings add traffic of their own, which is the case behind why HMI pages lag with many PLC variable bindings.

Verify each change #

  1. Record the baseline before editing: representative update times and the Dynamics page totals, captured under the same runtime state you will retest in.
  2. Change one script or trigger group at a time and retest before the next change, so the group that controls the delay shows itself.
  3. Re-open the Dynamics page after each merge. The total and the per-type counts should fall by the consolidation made; the object count need not move at all.
  4. Check every state the merged conditions select: visibility, color and appearance properties must still match the process states the separate scripts produced.
  5. Confirm that recurring updates stay responsive after the picture has been open a while, on the server and on the client where the delay was seen.
  6. Finish against the fast control picture: the reworked picture should now update in a similar time under the same conditions.

Questions asked

Is there a maximum object count for a WinCC picture published anywhere?

No. The Performance Data chapter of the WinCC documentation explains runtime cost through the complexity of the objects and the functionality inside the scripts, and it publishes no ceiling expressed in objects. Any fixed ceiling is a house convention: useful for keeping designs consistent, but proven only by the update-time arithmetic on your own pictures, never by a specification.

How many objects can one picture afford?

Whatever your runtime proves it can update inside the time the operation needs. The check is the load budget: take the dynamics total from the Dynamics page, divide the required update time by it, and compare that share against the measured cost of one of your scripted actions. A house rule of a few hundred objects keeps designs consistent, but it is a convention to confirm, never a specification.

What if only one client is slow on the same picture?

Then the diagnostic flips. When the server and every client show the same delay, the picture design travels with the picture, so the picture is the suspect. When one client alone lags on a picture that updates quickly everywhere else, leave the picture alone and check that client: its runtime installation, its graphics performance and its connection to the server, in that order.

How do I time one VB action by itself?

Write a timestamp at the first line of the action and another at the last line into two internal tags, show both on a test screen or in the tag list, and read the difference across several runs. If your WinCC version offers script or diagnostics tracing in runtime, use that instead. Compare the result with the budget the picture's own arithmetic gives each dynamic.

Can a merged script change what operators see?

Yes, if the merge drops a branch. A combined action must compute the shared condition once and then apply each property exactly as the separate actions did, for every state those conditions select. Test visibility, color and appearance dynamics across all the states the process reaches, and keep the list of properties each grouped action owns where the next engineer can find it.

Keep reading

  • Explainer

    Does One Shared Script Speed Up WinCC Screen Animations

    No for screen changes: opening a picture loads graphics, dynamic bindings and initial tag values, and consolidating animation scripts into one does not reduce that. Yes for steady-state runtime, but only when the grouped animations share one frame rate and phase, the trigger is scoped to the picture, and the shared counter has exactly one writer. Expect the visible running cycle to be three times the trigger interval.

    HMI and touchscreens

  • Troubleshooting

    Why a TP177A Runs Slowly After a WinCC Flexible 2008 Transfer

    A TP177A that slows down only after a WinCC flexible 2008 transfer has one of three causes: the panel image never got the OS update the 2008 build demands at first transfer, the engineering station lacks the latest 2008 service pack and its cumulative update, or the MPI or PROFIBUS segment runs at a rate and length the 2008 polling exposes. Run the OS update, install the newest pack, then set the highest baud rate the cable length and every node allow.

    HMI and touchscreens

  • Troubleshooting

    Why WinCC RT Professional clients change screens slowly

    When the server changes screens quickly and every client screen runs fine once it is open, the delay is the compiled picture being fetched over the terminal bus, not tag processing. Enable the local picture cache on each client, give the terminal bus its own network adapter with the binding order Siemens' distributed-systems requirements specify, and keep antivirus and indexer scanning out of the project folders.

    HMI and touchscreens

Why Gas Dispenser Screens Show the Wrong Prompt or Overlapping Text