Troubleshooting
Why WinCC RT Professional clients change screens slowly
Short answer
When the server changes screens quickly and every client screen runs fine once it is open, the delay is the compiled picture being fetched over the terminal bus, not tag processing. Enable the local picture cache on each client, give the terminal bus its own network adapter with the binding order Siemens' distributed-systems requirements specify, and keep antivirus and indexer scanning out of the project folders.

On this page
When a WinCC RT Professional server changes screens quickly while each client takes seconds, and every tag, button and popup inside the newly opened screen responds normally, the delay is the compiled picture crossing the terminal bus, not tag processing. Two changes fix most installations: the local picture cache on each client, and a terminal bus on its own network adapter. This article gives the ten-minute confirmation test, the changes in the order that pays back first, and the decision for each outcome you can measure.
What the symptom already proves #
The server keeps the compiled pictures in its own project folder and reads them from local disk, which is why its screen changes are quick. A client without a picture cache asks the server for the compiled picture file every time a screen is called, so the whole file crosses the terminal bus on each navigation. Once the picture is open, tag values travel as small cyclic telegrams, which is why everything inside the screen runs at normal speed. Three observations pin the fault to the transfer path:
- The server is quick and the clients are slow: same project, different source of the picture.
- The opened screen responds normally: tag processing and the plant connection are healthy.
- A repeat call is no faster than the first: nothing is kept on the client, so no cache is in use.
The pattern often surfaces after a version upgrade, when the recompiled project runs on stations whose settings were re-created rather than carried over.
Confirm the cause in ten minutes #
Work through this list on one client before changing anything:
- Open the same screen twice with a stopwatch and note both times; the second call is the one the cache changes.
- Connect that client and the server to a standalone switch with nothing else on it and repeat the screen changes. Fast on the isolated switch means the terminal bus path is the cause; still slow means the client itself is.
- While a screen loads, watch the client's network and disk activity: a network burst that lasts as long as the delay is the transfer, while a flat network with a busy disk points at local scanning.
- Check every station against the Siemens setup entry for distributed systems, 108464289, so a misconfigured station is not masking the real cause.
Run the test on a client that is not running production at that moment; a screen change that stalls for seconds delays an operator's response, so schedule it like any controls work. Once the cache works, the second call of the same screen must be clearly faster than the first; if it is not, no cache is active, and that gets fixed before the network.
Enable the picture cache on each client #
The picture cache stores compiled pictures on the client's local disk, so every call after the first is served locally and only the first call after a screen change crosses the bus. Every RT Professional client connects as a uniclient, so the uniclient cache procedure is the one that applies; Siemens support entry 982658 describes it, and the same local-cache mechanism is walked through end to end in configuring the WinCC PDL cache for PCS 7 multi-client systems.
- Enable the picture cache in the client's runtime settings and point the cache directory at a local drive, never a network share.
- Compile and download that client station, then restart its runtime.
- Open each frequently used screen once during commissioning so the cache fills before production relies on it.
- After any screen change or new download, treat the next call as a cold call by design: that first load crosses the bus again.
Proof that it took: stop the runtime and confirm compiled picture files sit in the configured cache directory. An empty directory after the cache should have filled means the setting did not survive the download.
What the cache saves, in numbers #
Illustrative inputs, not a measurement of any particular project:
- Example compiled screen package: 6 MB.
- Client link 100 Mbit/s, shared with PLC traffic; assume about 40 Mbit/s of effective throughput is left for the transfer during a navigation.
- Without the cache: 6 MB × 8 = 48 Mbit, and 48 Mbit ÷ 40 Mbit/s = 1.2 s per navigation before server handling.
- Both clients navigating together split that throughput to about 20 Mbit/s each, so the same call takes 48 ÷ 20 = 2.4 s.
- From the local cache, the same 6 MB read at an illustrative disk rate of 150 MB/s takes 6 ÷ 150 = 0.04 s.
The decision from these inputs: the cache removes the transfer from every repeat call, dropping them from seconds to tens of milliseconds, and a dedicated terminal bus raises the throughput for the first calls that still cross it. Your picture sizes and link rates set your own values; the ratio is what to expect.
Give the terminal bus its own adapter #
Sharing one adapter between the plant bus and the terminal bus puts picture transfers in direct competition with PLC traffic, and it is the configuration this symptom is usually found on. Siemens' Requirements for WinCC in Distributed Systems, entry 22132850, requires the terminal bus network card at the top of the adapter list; if it is not, the terminal bus connection moves to the top. The runtime documentation additionally requires the terminal bus to be configured for the correct network adapter in the SIMATIC Shell, because with several adapters installed it is easy to bind it to the wrong one.
- Add a second network adapter to the server and to each client where the two buses share one today.
- Bind the terminal bus to its own adapter in the SIMATIC Shell and leave the S7 plant connection on the other adapter.
- Move the terminal bus adapter to the top of the Windows adapter binding list.
- Keep the buses on separate subnets and separate switch ports or VLANs; example addressing is 192.168.0.0/24 for the plant bus and 192.168.1.0/24 for the terminal bus.
- Recompile and download the affected stations.
Re-addressing the terminal bus restarts the client-server discovery, and clients can freeze after such a change; why a WinCC server IP change freezes all HMI clients covers that recovery. If a second adapter is impossible, keep the terminal bus binding first in the list and accept that first loads share the wire; the cache still removes every repeat load.
Updates and Windows on the clients #
- Keep the engineering station, the server and every client at the same update level; installations matching this symptom run V17 with Update 5 on all stations, and if you are already there, the update is not the lever. The cache and the bus are.
- Check the client OS build against the compatibility list for your runtime version instead of assuming; the matching case ran Windows 11 Pro 21H2.
- Exclude the WinCC project folder and the cache directory from real-time antivirus scanning and from the search indexer; a scanner that holds picture files during the first load produces the same symptom with the network idle.
Verify and decide #
Measure after each change, then follow the outcome:
- Second call clearly faster and the first call acceptable: done; keep the cache local and the exclusions in place.
- Second call no faster: the cache is not active on that client; check the setting, the local path and the station download.
- Fast on the isolated switch, slow on the plant network: terminal bus congestion or the wrong adapter; dedicate the adapter and fix the binding order.
- Slow even on the isolated switch: a local cause; apply the scanner exclusions and confirm update parity.
- Server slow as well on faceplate-heavy screens: the time goes into the picture itself, and why WinCC Runtime faceplates load slowly on screen activation covers that fault and its fixes.
Questions asked
Why did the same distribution run fast on V13 and turn slow on V17?
A version upgrade recompiles every picture for the new runtime and re-downloads every station, so behaviour that depended on an old default can change without any hardware fault. After a jump like V13 to V17, verify the picture cache on each client and the update level on every station instead of assuming the old behaviour survived. In the installation that matches this symptom, all stations already ran the same update, which left the cache and the terminal bus as the working levers.
Is a slow screen change only a comfort problem?
No. An operator who waits seconds for a screen change also waits seconds to reach the alarm banner or the manual controls on that screen, so persistent navigation delay on a production station is an availability defect, not cosmetics. Screen navigation is not a safety function, and the fix is performance work: the client picture cache, a separate terminal bus and scanner exclusions, proven with the first-call and second-call stopwatch test.
Do I need a gigabit link for the terminal bus?
It helps the first load and does nothing for repeat loads. The 6 MB picture from the worked example needs about half a second on an idle 100 Mbit/s link, 48 Mbit divided by 100 Mbit/s, and a tenth of that on 1 Gbit/s. Enable the cache first, because it removes the transfer from every repeat call entirely, and move the terminal bus to gigabit when the adapters are replaced anyway.
The server is also slow when a screen with many faceplates opens. Is that the same fault?
No. When the server hesitates too, the time goes into instantiating faceplates and running activation scripts inside the picture, not into the transfer, so the client cache cannot help. Reduce what the screen builds when it activates, load faceplates on demand instead of all at once, and keep heavy script work off the activation event. The client-side fixes only pay off when the server itself changes screens quickly.


