IMDTouchKnowledge BaseShop main store

Troubleshooting

Why an APL auxiliary value identifier does not reach WinCC

HMI and touchscreens Published 6 min read By IMDTouch engineering team

Short answer

The identifier is instance data: the OS compile copies it from the CFC block into the WinCC text library, one cell per project language, and the faceplate shows only the cell of the active runtime language. A blank label means the compile never wrote the entry, or that language exists only on the WinCC side. Check the text library cell first, align the languages, then compile the entire OS.

On this page
  1. The text belongs to the block instance, not the block source
  2. How the text travels to the screen
  3. Read the text library before anything else
  4. Align the two language worlds
  5. Diagnostic sequence
  6. Worked example: one identifier in an English-only PCS 7 V8.0 SP2 project
  7. Questions asked

An identifier typed into the Identifier column of a VlvL block in CFC never reaches the screen on its own. The OS compile copies it into the WinCC text library, where it lands in one cell per project language, and the faceplate shows only the cell for the language the runtime is actually running. A blank label therefore has exactly two upstream causes: the compile never wrote the entry, or the entry carries no text in the runtime language's column because that language exists only on the WinCC side. Editing the block source is not the fix. Check the text library first, align the languages second, and compile the entire OS third.

The text belongs to the block instance, not the block source #

The APL valve block VlvL feeds auxiliary values to its faceplate. The first user analog input is declared in the block interface as UserAna1 with the structure AnaValFF, and its attribute list in VlvL.SCL includes S7_xshortcut := 'Value,;', which marks the input as one that carries an operator text — the attribute does not hold the text itself. The label is entered in the object properties of the block instance in CFC, on the I/Os tab, in the Identifier column, and it applies to the standard view of the faceplate. That makes the string instance data and project data: two valves built from the same block type can carry different labels, and the library stays untouched.

So do not patch the block source to chase a label. The standard blocks are not intended for modification, and on most installations the source is not available for editing at all; a hand-patched copy also drifts from the library and is reverted by the next library update while the label problem remains. Nothing in this path affects how the valve moves — out-of-service fail-open behavior of PCS 7 APL VlvL valves is a separate matter with its own write-up.

How the text travels to the screen #

The chain has four links: the Identifier cell on the instance, the OS compile, an entry in the WinCC text library, and the label in the faceplate's standard view. The compile generates the text library entry with its own ID, and the library holds the text in a column for each project language; the runtime language can be any language for which a language column exists. The faceplate never reads CFC, so a label that will not feed through is a text library state, not a CFC state.

The same compile-carries-the-text mechanism is what stands behind getting ALARM_S texts from STEP 7 CFC onto a Comfort Panel, and the compiler's role as the gatekeeper of what WinCC can see is also why WinCC cannot see an S5Time timer setpoint in a PCS 7 block.

Read the text library before anything else #

Open the text library immediately after an OS compile and locate the entry for the identifier. Its state decides the next move:

Text library state Meaning Decision
No entry for the identifier The OS compile never processed the chart, or only a chart-level compile ran; chart-level compiles carry no identifier text Compile the CFC charts, then compile the entire OS
Entry present, text present in the runtime language's column The engineering chain is complete A still-blank label is a runtime matter: check the language the OS starts in and restart the runtime
Entry present, cell empty in the runtime language's column The language was added on the WinCC side only, so the compile writes nothing into that column Align the language lists on both sides, then compile the entire OS again

Align the two language worlds #

SIMATIC Manager inherits the Windows system locale — the setting for non-Unicode programs — while WinCC works in Unicode. Two rules follow. First, the engineering station's system locale must match the project language before you compile; in the reported case that is English (United States) on the system, in SIMATIC Manager and in WinCC alike. Second, a language added only to the WinCC project receives nothing from the OS compile: the column exists, the compile never fills it, and a runtime started in that language shows nothing for the label. Correct the language lists first, then let one entire-OS compile write every column.

Diagnostic sequence #

  1. Open the block instance's object properties in CFC and confirm the string sits in the Identifier column on the I/Os tab of that instance — not of a block-type copy or a different chart.
  2. Compile the CFC charts.
  3. In SIMATIC Manager, compile the OS and select the entire OS rather than a changes-only pass for the first compile after adding or editing the identifier.
  4. Open the WinCC text library, locate the entry, and read the cell in the column of the language the runtime actually uses.
  5. Entry missing: repeat step 3 as an entire-OS compile; a chart-level compile will never create the entry.
  6. Cell empty: correct the language configuration on both sides — system locale, SIMATIC Manager, WinCC — then repeat step 3.
  7. Cell filled: the engineering side is done; restart the runtime and confirm the language the OS starts in.

Worked example: one identifier in an English-only PCS 7 V8.0 SP2 project #

Inputs, each with its source:

  • Block and version: a VlvL instance in a CFC chart on PCS 7 V8.0 SP2 — the reported field case.
  • Identifier text: Positioner feedback, an example string typed into the Identifier cell; the cell is documented, the string is illustrative.
  • Languages: system locale English (United States), SIMATIC Manager English (US), WinCC project and runtime language English (US) — as in the reported case.

Rule in words: one identifier compiles into one text library entry, the entry holds one cell per project language, and the faceplate shows only the cell of the active runtime language.

Arithmetic: one identifier and one language column give 1 × 1 = 1 cell to verify. Add a second language on the WinCC side only and the entry grows to 1 × 2 = 2 cells; the compile fills the one that exists on both sides, and 2 − 1 = 1 cell stays empty for good — that empty cell is the blank label.

Result: in the reported case the settings already matched, and the text appeared only after about six OS compile passes, with nothing else changed.

Decision: read the cell after every entire-OS compile. Filled — stop; anything still blank on screen is a runtime-language or restart matter. Empty after the first pass — repeat the cycle compile CFC, compile entire OS, check the cell, and treat about six passes as the outer bound observed in the field. Still empty beyond that — stop recompiling, correct the language configuration on both sides, and compile once more. Editing the block source never enters the sequence; the cell, never the compile count, tells you the chain has closed.

Questions asked

Can the identifier text be in a language other than English?

Yes. The OS compile transfers the text in any language, but the Windows setting for non-Unicode programs on the engineering station must be able to represent its characters. If it cannot, the string reaches the text library as question marks or garbled symbols, and the faceplate displays exactly that. Set the system locale to the text's language before compiling, or keep the identifiers in the project language.

Is a changes-only OS compile enough after editing one identifier?

Once the entry exists, yes: a changes-only pass merges new and changed parameters, and an edited identifier is such a change. Use the whole-OS compile after a language change or a library update instead, because only it rebuilds the text library entries; a chart-level compile carries no identifier text at all.

The whole auxiliary value row is missing, not just the label. Is it the same fault?

No. The block sends the faceplate a visibility signal for each auxiliary value, and the faceplate hides the row when that signal is absent, whatever the text library contains. A missing row therefore points at the block side, the value or its visibility signal, while a visible row with a blank label points at the text library. Check the row before blaming the compile.

Why does the fault show as a blank label instead of an error?

Because WinCC treats an empty text library cell as a fallback case, not a fault: it uses the static text configured for that object, and for an auxiliary value label that static text is empty. The runtime displays nothing and reports nothing, which is why this failure never announces itself. Diagnose it in the text library, where the empty cell is visible, not on the screen.

Keep reading

  • Troubleshooting

    Why PLCSIM V15 tags do not reach the HMI simulation

    Full access alone does not open the PLC. Point the S7ONLINE access point at the PLCSIM TCP/IP interface, tick Permit access with PUT/GET communication from remote partner under Protection & Security, recompile and download, and the HMI simulation reads PLCSIM V15 tags; a 10-toggle bench check proves the path.

    HMI and touchscreens

  • Troubleshooting

    Why WinCC PerformanceMonitor shows blank point values

    WinCC PerformanceMonitor shows a blank point when no qualifying value reaches the point, not when the display is wrong. Read the source tag's value and quality code in plain runtime, confirm the configured input reference, check that the example project matches the installed WinCC release, then check the evaluation interval, trigger conditions and data volume. No display setting fixes an input that never qualified.

    HMI and touchscreens

  • Troubleshooting

    WinCC Runtime Faceplates: Slow Loading on Screen Activation

    Screen activation time equals parse time plus serialized per-instance binding on the UI thread plus the S7 read jobs the screen's tag set needs. Repeat-open speed, core pinning and a bisection of faceplate instances split the delay; inconsistent multi-minute loads point to request packing, optimized DB access, acquisition cycles or stale tag addresses.