Troubleshooting
Why WinCC PerformanceMonitor shows blank point values
Short answer
WinCC PerformanceMonitor shows a blank point when no qualifying value reaches the point, not when the display is wrong. Read the source tag's value and quality code in plain runtime, confirm the configured input reference, check that the example project matches the installed WinCC release, then check the evaluation interval, trigger conditions and data volume. No display setting fixes an input that never qualified.

On this page
- Why does a configured PerformanceMonitor point stay blank after setup?
- How do you verify the source tag's value and quality code first?
- Does the configured input reference resolve to the tag you checked?
- Will a V7.2 GettingStarted example project produce data on WinCC 7.4?
- Does the evaluation interval contain any qualifying records?
- How much data does one evaluation hour pull through runtime?
- How do you prove the fix with a single point?
- Questions asked
A blank point in WinCC PerformanceMonitor means no qualifying value reached the point; the runtime control and the display settings are almost never the fault. Work the data path in order and stop at the first failed step: verify the source tag's value and quality in plain WinCC runtime, confirm the configured input reference resolves to that same tag, check that the example project and the installed option match your WinCC release, then check the evaluation interval, trigger conditions and data volume. Each step proves the input to the next, so a fix applied downstream of a failed step cannot work.
Why does a configured PerformanceMonitor point stay blank after setup? #
A PerformanceMonitor point stays blank because no qualifying value has reached it: either the source tag never delivered a usable value and quality, the configured input reference does not resolve, the runtime release does not match, or the selected evaluation interval contains no data. The blank proves only that the runtime control received nothing to show; it says nothing yet about where the chain broke. A configured point is not a live one — populating the configuration in the PerformanceMonitor Configuration Studio, opened from WinCC Explorer in the documented V7.2 procedure, proves only that you edited the project, not that runtime acquired or calculated a usable value. Check these five checkpoints in order and stop at the first one that fails:
- The source tag's value and quality code in plain WinCC runtime
- The configured input reference, confirmed against the tag you just verified
- The project's release identity and the installed option build
- The evaluation interval and any enable or trigger condition
- The calculation operands and the data volume inside the interval
When a step passes, everything downstream inherits a proven input. When a step fails, no display change, color, format or control setting repairs it — the sections below take the checkpoints in order.
How do you verify the source tag's value and quality code first? #
Open the tag in plain WinCC runtime first: a usable reading is a valid number with quality code 0x80 (good) or 0x4C (initial value), per the WinCC V7.4 communication documentation; anything else means the communication path, not PerformanceMonitor, is the fault. Read the tag on an ordinary screen or tag table in the same runtime project, because a number on a display can be a retained value from an earlier successful acquisition while the connection is already down. Confirm three behaviors:
- The value matches the controller or data source after the configured scaling; a mismatch points at addressing, conversion or a wrongly selected tag.
- One real process change arrives in WinCC. If the process is genuinely steady, watch a different, safely observable input instead.
- The quality stays at 0x80 through the change, not just at startup.
The same driver-versus-tag-versus-screen split that decides a stuck HMI value decides this step, and the page Is It the Driver, the Tag or the Screen? Diagnosing HMI Values walks that diagnosis in detail.
One safety rule: never force a production tag just to make a monitor point populate — forcing changes machine behavior and hides the real acquisition fault. Use existing process activity or an approved bench test signal.
Decision: blank point with bad quality or a frozen value means repair the communication path first; PerformanceMonitor is not yet in play.
Does the configured input reference resolve to the tag you checked? #
A point cannot calculate anything from an unresolved reference even when a similarly named tag works elsewhere in the project, so compare the tag the point actually selects against the tag you verified in runtime, by name, connection and address rather than by its description text. Reopen the point's input selection in the configuration and compare field by field; a description can survive a rename that the reference did not. Two traps produce a blank even when a good value exists somewhere in the project:
- A renamed, moved or deleted tag leaves the reference unresolved. Runtime diagnostics list unresolved objects; keep that text with its timestamp as evidence.
- A state input and a quantity input are not interchangeable. A running/stopped state carries a valid numeric value that is still the wrong operand for a quantity calculation. Check what the calculation expects, and check a ratio's denominator too, because division by zero yields no numeric result.
Where the question is whether a typed reference matches the object the system actually exposes, the page When OPC UA tag browsing fails and manual NodeIds work shows how a reference that looks correct can still select nothing.
Decision: every reference resolves and each value fits its role means move on to the release check; an unresolved object means reselect the input and prove the new selection against the tag you verified.
Will a V7.2 GettingStarted example project produce data on WinCC 7.4? #
The V7.2 GettingStartedPerformanceMonitorV72_complete project carries its release in its name and is not a proven WinCC 7.4 setup: the name documents where it came from, not that it converts and runs with data in a later release, so treat it as an untested input until checked. Read the installed version information for WinCC and the PerformanceMonitor option, open the project with conversion messages visible, and investigate every reported issue instead of reopening the same project repeatedly — with a backup taken first. Then check the example's dependencies: the V7.4 Getting Started documentation notes that the Quick_Start project needs no automation system because its values move through an internal tag, so an example can depend on demonstration tags that do not exist in your project. Restore missing dependencies through the documented example setup, or replace them with tags you have verified yourself. Obtain example projects and matching documentation only through the manufacturer or its authorized distribution channels.
Decision: a converted example that still shows nothing after its dependencies are restored is reporting on its own inputs, not on your runtime — swap in a verified source tag for the single-point test at the end.
Does the evaluation interval contain any qualifying records? #
A historical evaluation and a live tag reading are different measurements: the selected interval must overlap real acquisition activity, any enable or trigger condition must be active during it, and every calculation operand needs usable records inside that window, or the point has nothing to display. Read the selected start and end times first: an interval that ends before runtime started, or that ends at the current moment before the configured period has closed, cannot contain a finished result. Then check the enable or trigger condition — if it stays inactive during the test, diagnose its own source and logic; do not substitute a constant to force a display. Compare diagnostic timestamps against the runtime clock, because a clock offset can place your test records outside the interval you selected and make a healthy acquisition look empty.
Decision: no qualifying records inside the interval means the blank is correct behavior. Reselect an interval that contains known acquisition activity, or wait for the configured period to close, before judging the point.
How much data does one evaluation hour pull through runtime? #
Load scales with the number of inputs and the interval: the WinCC/PerformanceMonitor documentation's own example works out to 108,000 values calculated and displayed for three pieces of equipment over a one-hour evaluation, which is 36,000 per equipment, or 10 values per second. The arithmetic behind the documented figure: 108,000 ÷ 3 = 36,000 values for each piece of equipment in the hour, and 36,000 ÷ 3,600 s = 10 values per second per input. Your own load multiplies out the same way — number of inputs × values per second × interval in seconds. This does not fix a blank point, but it decides how long a valid result takes to appear and whether runtime can render the result completely: when the product outruns the acquisition and display cadence, shorten the evaluation interval or reduce the inputs rather than reading the lag as a fault.
Decision: size the interval to the data volume runtime can actually carry, and treat a point fed by an interval that has not yet closed as blank by design, not broken.
How do you prove the fix with a single point? #
Reduce the test to one known-good input driving one point, with the project backed up first: if that single point fills, the data path and configuration logic are proven and the fault was confined to the other point's input, condition or interval selection. Work it like this:
- Back up the project, then record every input reference, enable condition, evaluation interval and the diagnostic text with its timestamps.
- Apply the one correction the failed checkpoint called for: communication quality, reference selection, release mismatch or interval.
- Configure one fresh point driven by one input you verified above, ideally an internal tag so no controller is involved.
- Run runtime through one complete evaluation cycle — the configured interval, not a guessed wait time — and read the point.
- If the single point fills, restore the remaining points one at a time so any second failure isolates itself.
Decision: a filled single point proves the data path and the configuration logic. Any point that stays blank after that carries its own failed input, condition or interval, and the five checkpoints name which one — license status, display settings and the runtime control have nothing left to do with it.
Questions asked
Does WinCC PerformanceMonitor need its own license on top of base WinCC?
Yes, PerformanceMonitor is a WinCC option with its own license, separate from the base runtime license. A freshly resolved license is worth re-checking at the currently active runtime, but once the option starts without a licensing message and points still stay blank, the fault has moved downstream to the data path: tag quality, input reference, project release or evaluation interval.
Can you test PerformanceMonitor without a PLC connected?
Yes. The WinCC V7.4 Getting Started documentation states the Quick_Start project needs no automation system because its values are transported within WinCC by an internal tag. An internal tag gives you a known-good source for proving the PerformanceMonitor configuration, evaluation interval and display before you involve real controller communication.
Why does a point stay blank right after runtime starts?
Most evaluations need a closed interval of qualifying records before any result exists. A point fed by an hourly evaluation has nothing to show until the first full hour of good data has been acquired, even when the source tag reads correctly on a normal screen. Wait for the configured interval to complete, then judge the point.
What should you capture before changing a PerformanceMonitor configuration?
Back up the project, then record the input references, the enable or trigger conditions, the selected evaluation interval and the runtime diagnostics text with timestamps. If an edit makes things worse, that record returns you to the exact prior state and shows which step in the data path actually failed.