Which runtime languages WinCC V7.5 supports and which need the dongle
Short answer
WinCC V7.5 supports any runtime language the PC's operating system supports, so English and Russian need only OS language support and suitable fonts. Simplified Chinese, Traditional Chinese, Korean and Japanese additionally require the ASIA hardware dongle included with the WinCC Asia versions. You create runtime languages in the WinCC Text Library, following the multilingual-project procedure in Working with WinCC, sections 14.1 and 14.2.4, which also applies in V7.5 SP2.

On this page
- Which languages can WinCC V7.5 run as runtime languages?
- Which languages need the ASIA hardware dongle?
- Where do you create a runtime language in the project?
- Which manual procedure applies to your service pack?
- How much translation work does each extra language add?
- Why do some labels stay unchanged after a language switch?
- Why do characters appear as boxes on the runtime PC?
- How do you get the Asian-language entitlement if the project needs it?
- Questions asked
WinCC V7.5 runs English and Russian as runtime languages with nothing beyond operating-system language support and suitable fonts on the runtime PC. Simplified Chinese, Traditional Chinese, Korean and Japanese additionally require the ASIA hardware dongle, which is part of the delivery scope of the WinCC Asia versions. You create every runtime language in the WinCC Text Library, following the multilingual-project procedure in Working with WinCC, sections 14.1 and 14.2.4, and the same procedure applies in V7.5 SP2. Below is the entitlement decision for each language group, the Text Library steps, and the faults you meet at runtime.
Which languages can WinCC V7.5 run as runtime languages? #
Any language the runtime PC's operating system supports can be configured as a runtime language, so English and Russian need no entitlement beyond the normal WinCC runtime license, only operating-system language support and fonts that cover their characters. That is the documented rule: nearly every OS-supported language can be projected, and the Asian group is the single exception that adds hardware.
A runtime language is the language used to present configured operator text while the application runs. It is separate from the engineering interface language, so an English engineering environment can produce a Russian runtime without any additional entitlement. Commissioning a multilingual project therefore comes down to three separate checks: operating-system language support on the deployed PC, the applicable WinCC language entitlement, and the project's translated text. For the mechanics of switching an existing PCS7 operator station between the two Cyrillic-free and Cyrillic languages, see configuring PCS7 WinCC multi-language runtime switching between English and Russian.
Which languages need the ASIA hardware dongle? #
Simplified Chinese, Traditional Chinese, Korean and Japanese require the ASIA hardware dongle for both configuration and runtime operation, and that dongle ships with the WinCC Asia versions, whose documented language set is those four plus English (Siemens support entry 15093581). The requirement is triggered once by any Asian language in your project list; a second or third Asian language adds translation work, not a second entitlement check.
Two things do not substitute for it. Changing a Windows language setting on the runtime PC changes what the operating system can display, not what the WinCC license permits. Translating project strings into Chinese, Korean or Japanese does not remove the hardware requirement either. The TIA Portal documentation states the same principle for its WinCC Runtime: when runtime is used in an Asian language, a dongle is used additionally for the validation of the required license.
Where do you create a runtime language in the project? #
In the WinCC Text Library: open it, check whether the runtime language you need is already set, and if it is missing, enter it in the data area of the "Languages" tab, as the V7.5 procedure in entry 109760739 describes. Inside the Text Library, the editor-language entries created in the project are listed in table form, and each language entry carries an ID.
Two properties of that step decide what happens next. First, adding a language establishes a place for its translations; it does not translate the application automatically, so every text unit gains an empty field per new language. Second, the Text Library edits the project data directly, so take a recoverable backup copy of the project before changing its language configuration.
Which manual procedure applies to your service pack? #
For V7.5 SP1 use Working with WinCC, section 14.1, Structure of Multilingual Projects, and section 14.2.4, How to Create a Multilingual Project (entry 109773058); V7.5 SP2 carries the same two topics in its own edition of the manual, entry 109792641. The procedure is unchanged between the two service packs, so the decision does not depend on which of them is installed.
The manual's starting point shapes the whole project: configure a single-language project in your preferred language first, then add the other languages. All selected languages are equal — the first one keeps no master status, and every language column is filled the same way.
How much translation work does each extra language add? #
Each configured language adds one translation field per text unit, so the translation load scales as languages multiplied by text units, minus the source column you write only once. Worked example, with illustrative numbers:
- Text units in the project (screen labels, alarm texts, operator messages): 1,200.
- Languages configured: English (source), Russian, Simplified Chinese, Korean, Japanese = 5.
- Total translation fields: 5 x 1,200 = 6,000.
- Translations to write beyond the source language: (5 - 1) x 1,200 = 4,800, which is 1,200 per target language.
The same list settles the entitlement question: three of the five languages are in the Asian group, so this project runs only on a PC with the ASIA dongle, while the identical project with English and Russian alone runs on the ordinary runtime license.
Why do some labels stay unchanged after a language switch? #
Language switching replaces only texts that take part in the project's translation mechanism, so a fixed label, a caption burned into a bitmap, or a string supplied by the PLC keeps its original wording in every language. Before treating an unchanged label as a failed language switch, classify its text source: multilingual project text, fixed project text, or a dynamic value from the control application. Only the first group responds to the language switch; the others need their own supported mechanism or a translation inside the PLC program.
Layout is the second trap. Translation changes text length, and fonts differ in character width and height between languages, so correctly rendered text can still be unusable when a button clips its caption or an alarm column hides the actionable part of a message. Inspect screens, navigation controls and alarm presentation in each language, not just the source language.
Why do characters appear as boxes on the runtime PC? #
Because the runtime PC lacks either operating-system language support or a font covering those characters, a fault that appears on the deployed machine even when the engineering station rendered the same text correctly. Language selection alone never proves that every character will render; rendering depends on the installed fonts and their coverage of the characters the application actually uses.
Check the deployed runtime PC, not only the development machine. Display representative text containing each target language's distinctive characters — Cyrillic for Russian, Hangul for Korean, CJK ideographs for Chinese and Japanese — and confirm readable characters without replacement boxes, missing glyphs or substitutions. A related font-coverage failure on a machine display is covered in troubleshooting missing Russian fonts on a machine display.
How do you get the Asian-language entitlement if the project needs it? #
Buy the WinCC Asia version, or move an existing installation to it through the standard upgrade path, and confirm the dongle is recognized on every PC that configures or runs the Asian languages before commissioning continues. The reasons that favor the upgrade route for an existing Runtime Professional installation are set out in why WinCC Runtime Professional Asia uses the standard upgrade path.
The decision for each case:
- English or Russian only: ordinary WinCC runtime license, plus OS language support and fonts on the runtime PC. Create the languages in the Text Library's "Languages" tab and follow sections 14.1 and 14.2.4.
- Any of Simplified Chinese, Traditional Chinese, Korean or Japanese: WinCC Asia version with its ASIA hardware dongle, present and recognized on both the engineering and runtime PCs; the same Text Library procedure then applies.
- Characters rendering as boxes with the license in order: a font or OS-support problem on the runtime PC, fixed by installing the missing font or language pack, not by changing the project.
- Labels ignoring the language switch: a text-source problem — fixed text or a PLC-supplied string — fixed through that source's own mechanism, not through the language configuration.
Questions asked
Does WinCC Unified use the same Text Library procedure?
No. In WinCC Unified you double-click "Runtime settings" in the project tree, open "Language & Font", and enable there the languages that should be available on the device; the V7.5 Text Library does not exist in that engineering model. The dongle principle still applies to WinCC Runtime in the TIA world, where an additional dongle validates the license when runtime runs in an Asian language.
Does the engineering PC need the ASIA dongle as well as the runtime PC?
Yes. The requirement covers configuration as well as runtime operation, so every PC that edits Asian-language texts or runs the project in an Asian language must have the dongle present and recognized. Checking only the runtime station leaves the engineering station unable to configure those languages, and the fault then appears as blocked language configuration rather than a license message at startup.
Can you start with a single-language project and add languages later?
Yes. The manual's approach is to configure a single-language project in your preferred language first and add the other languages afterwards; all selected languages are equal, so the first language keeps no master status. Adding a language creates empty translation fields rather than translations, so budget the translation work before operators see half-translated screens.