Troubleshooting
Why an MTP1200 Unified panel says software was not loaded
Short answer
The message means the panel started without a runnable runtime project: the download never arrived intact, or the panel refused it. Two faults produce it: an Ethernet path that drops frames during the sustained transfer, or a panel image that does not support the device version compiled into the project. A firmware update, a clock correction and deleting the IM files fix neither; swap the cable, prove the link with large-packet pings, then read the installed image against the HMI device version.

On this page
"The software was not loaded" on an MTP1200 Unified Comfort Panel under TIA Portal V20 means the panel started without a runnable runtime project: the download never arrived intact, or the panel refused what arrived. Two faults produce that: an Ethernet path that drops or corrupts frames during the sustained transfer, or a panel image that does not support the device version compiled into the project. A firmware update, a date-and-time correction and deleting the IM files address neither one, which is why they changed nothing. Work in cost order — swap the cable and prove the link with large-packet pings first, since on a second panel with the same message the cable swap alone cleared it — then read the installed image version against the HMI device version and align the two.
Two faults behind one message #
The message is the panel's start-up verdict that no runnable runtime project is present; it names the outcome, not the layer that failed. Siemens' documentation on loading projects into Unified panels anticipates three load errors: incorrect settings for downloading to the HMI device, an incorrect HMI device type in the project, and the HMI device not connected to the configuration PC. On a link that already carries traffic, the fault sits in one of two places.
The first is transport. A project download is a sustained Ethernet transfer, and a marginal cable, a damaged connector, a port negotiating the wrong speed or a switch dropping frames produces retransmissions and aborts until the panel reports an incomplete load. Small operations still succeed on such a link — browsing to the device, a short scan for accessible devices — which is why a bad cable never looks like a dead one.
The second is version pairing. TIA Portal compiles the project for the device version selected in the HMI device properties, compatibility is decided against the WinCC version installed on the engineering PC, and the panel must run an image that supports that device version. When the project targets a device version the installed image does not support, the load is refused. An image update changes only the panel side: if the mismatch runs the other direction, updating without touching the project's device version changes nothing.
The first questions asked for this fault are the installed image version, whether a TIA Portal V20 update is in use, and the device version set for the HMI in the project. Collect those three values before changing anything; they sort the branches on their own.
Sort the symptom to its branch #
| What you observe | Branch it points to | Discriminating check |
|---|---|---|
| Fails at a different progress point on each attempt | Transport | Large-packet ping, cable swap, direct connection |
| Fails at the same point every time | Version pairing | Installed image against the HMI device version |
| Began after a TIA Portal upgrade or downgrade | Version pairing | Device version selected for the HMI, V20 update level |
| Project was built for a different panel type | Project configuration | HMI device type in the project against the panel's type |
| Firmware update completed, message unchanged | Firmware was not the variable | Transport tests first, then the version reads |
| Clock corrected, message unchanged | Clock was not the cause | Leave it correct and move on |
Prove the transfer path first #
- Replace the Ethernet cable with a known-good, factory-terminated patch cord. A link LED proves only that the link is up, not that it is clean.
- Take the plant network out of the path: connect the engineering PC straight to the panel's Ethernet port, not through a shared switch or a wireless bridge, for the whole diagnosis.
- From the PC run a sustained ping,
ping -n 200 <panel IP>, then repeat it with full-size payloads,ping -n 200 -l 1400 <panel IP>. Any missing reply on the large-packet run marks the link. - Confirm the PC and the panel sit in one subnet and that no other adapter captures the route. A NIC with no address in the panel's subnet fails the test before the panel is ever questioned, the pattern where ping fails because the laptop NIC has no subnet IP. A VPN client on the engineering PC is the other common route capturer, worked through in why TIA Portal V20 cannot reach WinCC Unified PC Runtime over VPN.
Match the image to the device version #
- On the panel, read the installed image version from its system information.
- In TIA Portal, open the HMI's device properties and read the device version selected there, and note the V20 update level installed on the PC.
- Apply the rule: the image must support the device version the project compiles for. Which side to move for a given pairing is set out in device version vs panel OS image on Unified Comfort Panels.
- Take new images only from the manufacturer's image-download entry for Unified Comfort Panels, which publishes them per TIA version — V21, V20, V19 and V18 at the time of writing — and load them through the panel's Update OS function under the control panel's system properties.
Worked example: 200 large pings to an MTP1200 under V20 #
Inputs, each with its source:
- Panel and message: MTP1200 Unified Comfort Panel showing "The software was not loaded" (the fault report).
- Engineering side: TIA Portal V20 (the fault report).
- Already tried, no change: firmware update, date-and-time correction, deletion of the IM files (the fault report).
- Test size: 200 packets at 1400 bytes of payload each (the test defined above).
- Pass threshold: 0 missing replies (this article's decision rule).
- Example reading: 196 replies received — a hypothetical run, not a measurement.
Rule in words: the loss percentage is the missing replies divided by the packets sent, times one hundred, and each ping travels as one unfragmented frame because the payload plus the 28 bytes of ICMP and IP headers stays under the 1500-byte Ethernet MTU.
Arithmetic:
- Frame size per ping: 1400 bytes + 28 bytes = 1428 bytes, below the 1500-byte MTU.
- Sustained load of one run: 200 × 1400 bytes = 280,000 bytes, about 273 KiB (280,000 ÷ 1024 = 273.4).
- Loss on the example reading: (200 − 196) ÷ 200 × 100 = 4 ÷ 200 × 100 = 2.0%.
Result: the short ping loses nothing while the large-packet run loses 2.0% of its replies.
Decision: the threshold is 0%. At 2.0% the branch is transport — keep the replacement cable and the direct connection, re-run until every reply returns with stable times, then download. Had the large-packet run come back with nothing missing, the link would pass and the next read would be the installed image version against the HMI device version.
Recover one change at a time #
- Transport branch: keep the replacement cable, scrap the old one, and inspect the RJ45 latch and pin seating at both ends. If a switch port is suspect, move to another port or stay direct until commissioning is finished.
- Version branch: make one move. Either raise the panel image to a level that supports the project's device version, or lower the HMI device version to what the installed image supports — the cases that need an old and a new image side by side are worked in Unified Comfort Panel image updates when two versions are needed. Changing both sides in one attempt leaves the outcome unattributable.
- After any device-version change, recompile the HMI in full, not incrementally, before downloading.
- Run the first download with the machine stopped or the panel on the bench: a load restarts the runtime and the screen is down while it runs. Let the transfer finish without switching adapters on the PC.
Checks that prove the fix #
- Link: the large-packet run returns 0% loss with stable reply times.
- Version pairing: the installed image supports the device version in the HMI properties, with no mismatch warning at compile or at download.
- Load: the transfer runs to completion, the message is gone and the runtime project starts.
- Repeatability: a second download of the same project completes identically with the cable gently flexed at the connector during the transfer.
Questions asked
Does a completed firmware update rule out the Ethernet cable?
No. A finished update proves the panel accepts and installs one transfer, not that the link carries a full project download to its final frame. Keep the large-packet ping and the cable swap in the sequence after a successful update; the message comes from the transfer path or the version pairing, and a new image repairs only the pairing.
Can the project compile without errors and still fail to load?
Yes. Compiling checks the project against the device version selected in TIA Portal, not against the image actually installed on the panel and not against the cable. A clean compile followed by the message points at the version pairing or the transfer path, so read the panel's image version instead of recompiling again.
What does it mean when another project loads over the same connection?
The cable, the PC adapter and the panel's load routine all work, so the transport branch is cleared. Concentrate on the failing project: its device version, the installed image and the V20 update level. Align the two versions, recompile in full and download again before spending more time on the link.
Why does deleting the IM files leave the message unchanged?
The panel raises the message at start-up when it finds no runnable runtime project. Deleting files repairs neither a link that drops frames during the download nor an image that refuses the project's device version, so both causes survive and the message returns at the next start.