Why KTP400 Basic panels use Time Shift instead of a timezone
Short answer
A KTP400 Basic panel has no timezone setting; the Control Panel's Date & Time dialog offers a Time Shift field as a signed hour-and-minute value spanning -24:00 to +24:00. Entering +07:00 shifts the panel clock, so a Date/Time field in system-clock mode reads seven hours ahead. Comfort panels get a true timezone setting instead; the procedures are not interchangeable.

On this page
A KTP400 Basic panel has no timezone setting — the option does not exist on that panel family. What it has instead is Time shift: one fixed offset the panel applies to its clock, entered in the Date & Time dialog of the panel's Control Panel. For a Date/Time field set to system-clock mode that must read seven hours ahead of its current display, the entry is +07:00, and the field moves the moment the value is confirmed. The shift belongs to the panel, not to the screen object, so every alarm timestamp and trend axis that reads the HMI clock moves with it. Comfort panels are the family with a true timezone setting, and the two procedures are not interchangeable. What follows is where the entry lives, the arithmetic it performs, and how to keep the S7-1200 from overwriting it.
Why a Basic panel has no timezone setting #
A Basic panel stores one clock and one correction, nothing more. The SIMATIC HMI Basic Panels operating instructions give the whole specification: under "Time shift", enter the offset in ±hh:mm form, with a value range of -24:00 to +24:00. There is no region list and no seasonal table, because the panel keeps no rule set; it keeps a number and adds it to the time it displays. A timezone is a different object — an offset plus the changes a region applies at set times of year. The Basic family can do the first part only, which is exactly what this request needs, and falls short only when the display must follow seasonal changes.
The field is the other half of the story. A Date/Time field whose mode is set to the HMI system clock has no timezone property of its own; it renders the panel clock, shifted or not. The shift therefore belongs to the panel, and it moves every timestamp the panel produces, not just this one field. That is also why no per-object setting can give one screen a different time than the rest of the panel.
Entering the shift on the panel #
- Write down the field's current reading with its date. That baseline is what the corrected display gets checked against.
- Open the panel's Control Panel and touch the "Date & Time" icon. The route into the Control Panel depends on the panel generation, but this dialog holds the clock settings on every Basic panel.
- Enter +07:00 in the "Time shift" field for a display seven hours ahead. The sign leads the value, so a display that must fall behind instead takes -07:00.
- Confirm and leave the dialog, then reopen the screen: the field should read the baseline plus the offset, date included.
Read the entry as a total, not an increment. The field holds the shift applied to the base clock, so a value a previous commissioning left there is replaced, not added to. If the panel already displayed one local offset and the requirement is another, the new entry is the new total.
The same dialog carries the panel's display-format settings. Switching the date and time display to 24-hour format on a second-generation KTP400 Basic is its own short procedure, covered in guide to a 24-hour date and time display on the panel.
Seven hours ahead, with the date rollover #
Take the case with real numbers. Before the change, the field reads 20:00 on 31 May and the Time shift field holds 00:00, so base clock and display agree. The entry is +07:00.
- Hours: 20:00 + 7 h = 27:00. No clock reads 27:00, so the overflow carries out of the hour digits: 27:00 - 24:00 = 03:00.
- Date: the carry consumes one day, so 31 May + 1 day = 1 June.
- Display: the field now reads 03:00 on 1 June — the full calendar value, exactly seven hours ahead of the baseline taken at the same reference instant.
The carry is the part to trust the panel with. Because the shift applies to the whole date-and-time value, month-end and year-end rollovers work the same way; adding to the hour digits by hand, in PLC logic or in a display tag, is where dates silently stop rolling over.
Who may write the panel clock #
A shift survives only if nothing rewrites the clock underneath it. Time synchronization is configured per connection: for a connection integrated in the TIA Portal project, it is set up in the "Devices & Networks" editor, and the endpoints involved must support the time synchronization function. Decide the direction once. With the S7-1200 as master, the connection writes the panel's base clock and the panel displays base clock plus shift; enter the shift once and never correct the panel clock by hand, because the next synchronization erases a manual entry. After one synchronization interval, check the screen: the field should still read seven hours ahead of the PLC's clock.
With the panel as master, the same rule holds with one trap: never push the displayed time into the PLC as its reference. That writes the shift into the PLC's clock as if it were base time, and the panel's next display adds the shift again. One reference, one writer; the shift lives only on the panel. An NTP-fed panel follows the same pattern with the server as reference — the dialog's "Use NTP" switch selects it, and the troubleshooting guide for SNTP clock sync on a Windows CE panel covers what to check when network time does not arrive.
Projects that move the clock as data instead — writing a DATE_AND_TIME tag from PLC logic or a scheduled job rather than using the connection's synchronization — fail in their own way, and the article on fixing an HMI date and time tag that fails over S7 covers that path and its fix.
What a Comfort panel does instead #
Both KTP400 families share the screen and the question, not the answer. A Comfort panel exposes a true timezone setting, regional rules attached, configured on the panel itself; the Basic family exposes only the fixed offset. The procedures are not interchangeable in either direction. Copying the shift recipe onto a Comfort panel leaves a fixed offset where a rule-based timezone belongs, and the display drifts an hour at the next seasonal change. Hunting for a timezone menu on a Basic panel finds nothing, because there is none. Identify the family from the project's device entry or the ordering data before changing anything; the KTP400 name alone appears on both.
The decision #
- Constant offset wanted on a KTP400 Basic, this case: enter the total offset in the "Time shift" field of the Date & Time dialog, let the S7-1200's connection synchronization or the NTP server own the base clock, and verify after one synchronization interval that the display holds the corrected reading.
- Seasonal local time wanted on a KTP400 Basic: the panel cannot hold a rule. Either re-enter the offset each time the region's rule changes, or compute the displayed time as a tag and bind the field to it.
- One field on a different time than the panel: not available in system-clock mode. Compute the tag and switch that field's mode to the tag.
- Same request on a KTP400 Comfort: use the panel's timezone setting; the Basic-panel shift recipe is the wrong tool there.
Questions asked
Does the Time shift value follow daylight saving on its own?
No. The panel stores one fixed offset and applies it all year; a Basic panel holds no seasonal rule. If the destination region changes its clocks seasonally, either enter the new offset in the same dialog when the rule takes effect, or compute the displayed time as a tag the PLC keeps updated. A Comfort panel is the only one of the two families that applies seasonal rules itself, through its timezone setting.
What goes in the field for an offset that is not a whole number of hours?
The ±hh:mm format carries minutes. A five-and-a-half-hour offset is entered as +05:30 and a three-quarter-hour offset as +05:45, inside the same -24:00 to +24:00 span. The value is hours and minutes of clock time, not whole-hour steps, so any offset that fits the span is written directly. Keep the sign in front of the digits so the direction of the shift stays unambiguous.
Why does the corrected time jump back after the panel has run for a while?
Something wrote the base clock after your entry. The usual writer is time synchronization from the S7-1200 over the HMI connection; an NTP server or a scheduled clock write does the same. Leave the base clock to whichever writer is configured, keep the offset in the Time shift field, then watch one synchronization interval: the display should settle at the shifted reading and stay there. If it still moves, hunt for a second clock writer before touching the shift again.
Can one Date/Time field show a different shift than the rest of the panel?
No. The shift belongs to the panel clock, and a field in system-clock mode has no timezone property of its own. Alarm timestamps, trend time axes and every other object that reads that clock show the same shifted local time. To show a second region next to it, compute that region's time as a tag, in the PLC or in the panel project, and switch the field's mode to read the tag instead of the system clock.