Why NetPro rejects a PG/PC with the same IP as your SIMATIC PC

HMI and touchscreens Published 5 min read By IMDTouch engineering team

Short answer

NetPro is rejecting the project because two declared stations claim one Ethernet address. Your engineering computer and the SIMATIC PC station are the same machine, so you do not add a second logical station: assign the engineering access through the existing station's interface, then send the Mobile Panel 177 project over the S7 route from WinCC flexible 2008.

On this page
  1. Why the same address on two declared stations fails
  2. Clearing the conflict for a ProTool runtime PC with a Mobile Panel 177 on PROFIBUS
  3. Fixing the project step by step
  4. Verifying the result
  5. Questions asked

NetPro is not complaining about your hardware; it is complaining about your drawing. The project declares the SIMATIC PC station with its Ethernet interface, and you are trying to add a PG/PC object that claims the same Ethernet address on the same subnet. To NetPro these are two logical machines, so the duplicate-address check refuses the configuration even though one physical computer stands behind both. The fix is to stop declaring a second station: use the existing SIMATIC PC station's interface assignment as your engineering access, set the S7ONLINE access point for that adapter, and send the WinCC flexible 2008 project to the Mobile Panel 177 over the S7 route through the CPU 300.

Why the same address on two declared stations fails #

A PC station in NetPro describes configured communication components and their network connections. A PG/PC object represents engineering access to the configured network. When one physical computer performs both roles, the model still allows only one declaration per physical adapter per subnet. Declaring the adapter twice, once under the PC station and once under a PG/PC object, produces exactly the conflict you are seeing, and it is a configuration error, not a real collision on the cable.

The hardware side enforces this too. SIMATIC NET communication processors run a duplicate-address recognition at startup, so a CP that is given an address already answered on the network reports it at startup. Related reading on routed transfers is in Transfer a WinCC flexible project to an MP277 via S7 routing.

Clearing the conflict for a ProTool runtime PC with a Mobile Panel 177 on PROFIBUS #

This is the case from the bench, worked through with example addresses.

Inputs:

  • SIMATIC PC station, already declared in the project, with its built-in Ethernet interface configured, for example 192.168.0.1 with subnet mask 255.255.255.0.
  • CPU 300 with integrated PROFIBUS and an Ethernet communications processor in the rack, on that same Ethernet subnet.
  • Mobile Panel 177 on the CPU's PROFIBUS segment, with its own bus address.
  • Proposed (rejected) addition: a PG/PC station whose Ethernet interface was entered as the same 192.168.0.1 on the same subnet.

The rule in words: one physical adapter may appear exactly once per subnet in the network configuration. Engineering access to that subnet is declared through the interface assignment of the station that already owns the adapter, not through an additional PG/PC station object.

The arithmetic of the conflict: the PC station's interface is 192.168.0.1 / 255.255.255.0. The proposed PG/PC interface is 192.168.0.1 / 255.255.255.0. Both fall in the subnet 192.168.0.0 / 24, and the host portions are identical, so NetPro's duplicate check matches them exactly and rejects the project. There is no address you can pick for a second declaration that avoids this on the same adapter and subnet; the second declaration itself is the error.

The decision: delete the redundant PG/PC station's Ethernet interface, keep the PC station's interface at its configured address, and declare the engineering access through that station instead. Then route the panel download over the S7 route: Ethernet from the PC to the CPU 300, PROFIBUS from the CPU to the Mobile Panel 177.

Fixing the project step by step #

  1. Save a recoverable copy of the STEP 7 project and note the current runtime communication settings before changing anything, so the working ProTool runtime configuration can be restored.
  2. In NetPro, identify which object represents the running PC station and which PG/PC object was added only for the transfer. Delete the redundant Ethernet interface declaration on the PG/PC object, or the whole added object if nothing else uses it.
  3. Assign engineering access through the surviving station's interface: in the interface properties, assign the Ethernet interface to the TCP/IP protocol parameterization so it sits correctly on the Ethernet subnet.
  4. On the Windows side of the same computer, open the Set PG/PC Interface dialog in the Control Panel and select the S7ONLINE (STEP 7) access point, pointing it at the adapter that connects to the automation network. This is how STEP 7-side tools reach the route without a second declared machine.
  5. Compile the network and hardware configuration and confirm the duplicate-address error and any unresolved connection or subnet errors are gone.
  6. Download the changed configuration to the CPU 300 in a maintenance window, keeping the download scope limited to the routing-related changes so the running runtime connections are untouched.
  7. In WinCC flexible 2008, open the project for the exact Mobile Panel 177 variant and go to Project > Transfer > Transfer settings, select the panel, and choose the transfer route via the CPU. Siemens documents this S7 routing transfer path for operator panels; the CPU and the Ethernet communications processor must both support routing, which the CP 343-1 family does.
  8. Put the panel in its documented transfer state and start the transfer. If the installed panel variant does not support the routed path, use the direct transfer connection documented for that panel rather than reworking NetPro again.

Verifying the result #

Check the path in three stages, because a working Ethernet ping proves only the first leg. First, the compiled network configuration shows no duplicate-address error and the offline drawing matches the station after download. Second, read the module diagnostics and online configuration to confirm the CPU's PROFIBUS side sees the panel at its configured bus address. Third, the transfer itself: the panel accepts the transfer request from WinCC flexible 2008 and the download completes. If stage one passes but the transfer fails, the problem is on the panel's transfer channel settings or the route parameters, not in the Ethernet declaration you just corrected.

If the transfer still fails after the configuration is clean, the direct-download path with a PC adapter is the fallback, covered in Why a PC Adapter cannot download WinCC Flexible to a TP177.

One safety note: any download to the CPU touches the station that your runtime and the panel depend on, so make the configuration change with the line in a safe state and inside a planned window, and keep the saved project copy on hand for rollback.

Questions asked

Can one physical computer be both a SIMATIC PC station and the PG for downloads?

Yes, but not as two separately declared NetPro stations with the same address. Declare the machine once as the PC station with its configured Ethernet interface, and reach the engineering functions through that station's interface assignment, using the S7ONLINE access point for STEP 7-side access. NetPro validates the logical model, so one adapter must appear as one interface, not two.

Why does SIMATIC NET complain about a duplicate IP address even though only one adapter exists?

Communication processors check at startup whether the address they are given is already answered on the network. When a second logical interface is configured with the same address, the startup check reports it as assigned twice. Removing the redundant declaration in NetPro and downloading the corrected configuration clears the report.

Do I need to change the panel or the CPU address to fix this?

No. The fault is in the configuration computer's own representation, not in the panel or controller addresses. Keep the CPU's PROFIBUS address, the Mobile Panel 177 bus address and the Ethernet subnet unchanged, correct only the redundant PG/PC declaration, then run the transfer through the transfer settings in WinCC flexible 2008.

What proves the routed transfer path works before the download?

Three checks: the network configuration compiles with no duplicate-address or unresolved connection errors, the configuration in the routing station matches the offline project after download, and the panel accepts the transfer request when you select it under Project > Transfer > Transfer settings. An Ethernet ping to the controller alone proves only the first leg, not the PROFIBUS leg to the panel.

Keep reading

  • How-to

    Where to save C-more panel IP settings in the project

    The C-more project does store the panel's IP address and subnet mask: enter them under Setup > Touch Panel Network > Ethernet Port and save the project. That entry is a record, not a lock — the panel's System menu can still change the live values — and it is separate from the PLC destinations, so a controller address change still means editing each affected project and re-transferring it to every panel.

    HMI and touchscreens

  • Troubleshooting

    Why WinCC Runtime Professional Shows No Data From PLCSIM

    The runtime window opening with static screens means the runtime process runs but its path to the simulated CPU does not. Point the access point in Set PG/PC Interface at PLCSIM or the matching TCP/IP route, compile the PC station, connect the TIA project to PLCSIM, and put the CPU in RUN before the runtime starts.