Explainer
Why SIMATIC Logon logout uses the panel Administrator timer
Short answer
When SIMATIC Logon authenticates the users of a Comfort panel, the automatic logout is not taken from the server: every user inherits the automatic logoff time of the local Administrator user in the panel project's Users and roles editor, in whole minutes from 1 to 60. Keep that value at least one minute away from the SIMATIC Logon server time, because equal values are reported to stop the panel logout, and leave the server's forwarding option cleared.

On this page
- Where does the automatic logout time come from with SIMATIC Logon?
- Why does changing the SIMATIC Logon server time not log the panel off?
- How do you set the logoff time on the panel's Administrator user?
- Why must the panel time be different from the server time?
- What resets the logout timer while the operator works?
- Is the logout configured the same way on WinCC Unified?
- How do you test the setting before the machine is handed over?
- Questions asked
When a Comfort panel checks its operators against the domain through SIMATIC Logon, the automatic logout still comes from the panel, not from the server: every domain-authenticated user is logged off on the automatic logoff time of the local Administrator user, in whole minutes from 1 to 60. The server's own logoff time, set once for everyone in Configure SIMATIC Logon, ends the sessions on that server, and it reaches a panel only when the option that forwards it is enabled. This article shows where the timer lives, how to set it, why the panel value has to differ from the server value, and the check that proves the logout before the machine is handed over.
Where does the automatic logout time come from with SIMATIC Logon? #
Every user who logs on through SIMATIC Logon inherits the automatic logoff time of the local Administrator user in the panel project's Users and roles editor, whatever the SIMATIC Logon server is set to; the logon method changes nothing about which timer applies. SIMATIC Logon is the central user administration for Panels, Comfort Panels and the PC runtimes: it answers each logon from the domain and maps the authenticated account to a local group with the matching runtime authorizations. The panel project keeps its own user administration underneath, and that local administration is where the logout time lives. The documentation for the panel user administration requires the logoff time for the SIMATIC Logon user to be enabled on the "Automatic logoff" tab, and running panels show which entry that tab belongs to: the standard user "Administrator". Changing the time on any other local user changes nothing for a domain logon.
Why does changing the SIMATIC Logon server time not log the panel off? #
The server's logoff time is set once, for all users, in the Configure SIMATIC Logon tool on the server computer, and it ends only the sessions on that server unless the option that forwards it to the panels is enabled. The tool is opened on the server with Start > SIMATIC > SIMATIC Logon > Configure SIMATIC Logon. A Comfort panel enforces the user administration compiled into its own project, so a value changed at the server reaches the PC stations and leaves the panels untouched — which is why editing the server time appears to do nothing at the line.
The bridge between the two sides is the option "Use SIMATIC Logon Automatic logoff" in the same tool. Enabled, it makes the panels follow the SIMATIC Logon time; cleared, each panel's Administrator time governs. Leave it cleared when the panels need their own logout time, and enable it only when every station is to share the server's value.
How do you set the logoff time on the panel's Administrator user? #
Open the Users and roles editor of the panel project, select the Administrator user, and on its "Automatic logoff" tab enable the setting and enter the logout time in whole minutes from 1 to 60. In order:
- Open the panel project in TIA Portal and go to its Users and roles editor.
- Select the "Administrator" user, the standard user that every panel project contains and that cannot be deleted.
- Switch on automatic logoff for that user and enter the minutes.
- Compile the project and transfer it to the panel. The panel image has to match the project version; matching an HMI panel image to its TIA Portal project version walks through that check.
- Write the chosen value into the commissioning record next to the SIMATIC Logon server time, together with the separation rule in the next section.
Common plant choices are a few minutes at an operator station and a longer time where a supervisor reviews screens for extended stretches; those are examples, not limits, because the timer accepts any whole minute in its documented range.
Why must the panel time be different from the server time? #
When the panel's Administrator time equals the SIMATIC Logon server time, running systems report that the panel logout stops firing, so keep the two values at least one minute apart. It is not specified in the documentation, only reported: with the values equal, the automatic logout does not come while the panel is online with the server, and it returns as soon as the values differ. Treat it as a hard configuration rule anyway — a one-minute offset costs nothing, and the reported failure disappears.
Worked example with hypothetical inputs: the SIMATIC Logon server runs a 10-minute logoff time for the PC stations, and the plant rule says a panel must log its operator off after 5 minutes without input.
- Panel setting: Administrator automatic logoff = 5 minutes.
- Separation check: 10 - 5 = 5 minutes of gap, comfortably above the 1-minute minimum, so the panel timer stays in charge.
- Wrong setting for comparison: an Administrator time of 10 minutes "to match the server" gives a gap of 10 - 10 = 0 minutes — the reported skip, and no logout at all.
- Timeline to observe: logon at 10:00, last touch at 10:03, logoff at 10:03 + 5 min = 10:08.
Either direction clears the server value — 9 minutes or less, or 11 minutes or more — but the plant rule picks 5. If the logout still refuses to fire with these settings, work through resolving a SIMATIC Logon automatic logoff configuration error, which collects this failure pattern with its fixes.
What resets the logout timer while the operator works? #
The timer counts time without operator input at the panel: touches, screen changes and value entries restart it, while tags updated from the controller do not, so an operator who only watches can still be logged off. That is the behavior the plant rule wants — the timer guards an unattended station, and a running screen nobody is touching is an unattended station. The operator logs back on with one touch and loses nothing but the logon step.
The PC runtimes offer a choice the Comfort panel does not: their user administration has a "Type of automatic logoff" field that takes "Absolute" or "Inactive" for a user or a group. "Inactive" is the idle time described above; "Absolute" logs the user off after the set time even while they work, which is the setting for a session that must never outlive a fixed window. On the Comfort panel, the SIMATIC Logon time works as the idle time.
Is the logout configured the same way on WinCC Unified? #
No: WinCC Unified uses a "Runtime timeout" that the engineering system configures for the whole runtime, entered in seconds rather than minutes, and the user is logged off when the inactivity lasts that long. There is no per-user logoff time to hunt for. A Comfort value carried over has to be converted, for example 10 minutes × 60 seconds per minute = 600 seconds. No per-user SIMATIC Logon timer sits beside the runtime timeout, so the equal-value failure does not apply here. The logon side is configured separately; login methods on a Unified Comfort Panel by user management covers that half.
How do you test the setting before the machine is handed over? #
Run the check on the bench: log on with a domain account, note the time of the last touch, and confirm the logon screen returns at that time plus the configured minutes — last touch at 14:20 with a 4-minute setting means 14:25. Switch on the logging of the logon and logoff events first, so the record carries both timestamps and the check does not depend on someone watching the screen. Repeat the test once after a restart of the panel to confirm the setting survived the transfer.
One boundary to keep straight: the automatic logout ends access, it does not stop the machine, and nothing in the safety circuit may depend on who is logged on. Close out by writing the panel value and the server value, with the test date, into the commissioning record — that is the paper an auditor asks for when a session ended too early or too late.
Questions asked
Can different domain users get different logout times on the same Comfort panel?
No. With SIMATIC Logon every authenticated user runs on the single time stored for the Administrator user, so per-user logout times exist only for users local to the panel project. Different logout times per station are still possible, because each panel project carries its own Administrator entry — set the faster station to its own value there.
Does the automatic logout still work when the panel cannot reach the SIMATIC Logon server?
Yes. The time is stored in the panel project and enforced by the panel runtime, so the countdown does not wait for the server; the server answers the logon, the panel performs the logoff. Disconnect the panel from the server on the bench and repeat the timeout test to confirm it on your own hardware.
Is the operator warned before the automatic logoff fires?
On the server side, yes: the Configure SIMATIC Logon tool takes, on its Automatic logoff tab, a wait time, the time that passes before the logoff notification is displayed. WinCC Unified also offers a warning with its own warning time ahead of the Runtime timeout. On a Comfort panel, verify any warning behavior on the running panel before you rely on it.
Where is a change of the logoff time recorded?
In the Audit Trail: any user change of the logoff time is logged there, so the value in force on a panel can be reconstructed after the fact. That is the record to quote when an auditor asks why a session ended at a particular minute.