Why the CP properties cannot be selected after a WinCC upgrade
Short answer
The message means the CP's parameters are owned by another tool: on a PC with SIMATIC NET, the station configuration's Communication Settings, not the Set PG/PC Interface dialog. After an upgrade, restore the missing SIMATIC OAM bin entry in the system Path and start the automation service that will not run before reinstalling anything, because a STEP 7 reinstall did not restore online access in the reported case.

On this page
- What does "The properties of this CP cannot be selected here" mean?
- Do you change the CP in Set PG/PC Interface or in the SIMATIC NET configuration?
- Why does the tool report SRMD_Set(..) - No interface handle?
- Why will the Siemens automation service not start after the upgrade?
- In what order should you run the checks?
- How do you prove online access is really restored?
- Should you reinstall STEP 7 to clear the message?
- Questions asked
The message "The properties of this CP cannot be selected here" is not a dead end: it tells you the CP you selected is parameterized somewhere else, and after an upgrade two further faults can hide behind it. In the reported case, an industrial box PC on Windows XP lost PG/PC Ethernet access when Windows went from SP2 to SP3 and WinCC flexible from 2005 to 2008 in one maintenance step; a Siemens automation service would not start, and removing and reinstalling STEP 7 changed nothing. The repair order is fixed: decide whether the CP belongs to a SIMATIC NET station configuration, verify the Siemens environment variables against the folders on disk, get the service running, then retest online.
What does "The properties of this CP cannot be selected here" mean? #
It means the CP you clicked is parameterized by another tool: where SIMATIC NET manages the interfaces, the CP belongs to the station configuration and its settings live in that configuration's communication settings rather than in the Set PG/PC Interface dialog. The dialog adds that two possibilities exist to change the properties, and the documentation for PG mode on a SIMATIC NET PC names them: you configure a module with the Set PG/PC Interface tool, or you create the configuration with the Communication Settings tool. When the PC carries a SIMATIC NET station configuration, Set PG/PC Interface declines to edit hardware it does not own.
After an upgrade there is a second route to the same message: the machinery behind the dialog is broken. If the environment variables no longer point at folders that exist, or the automation service cannot start, the dialog can neither read nor write the CP properties and reports the same refusal. That is why the checks below run in order rather than beginning with a reinstall.
Do you change the CP in Set PG/PC Interface or in the SIMATIC NET configuration? #
Decide that first, because it picks the tool: with a SIMATIC NET station configuration the CP is set in that configuration's Communication Settings, and only without one is it set directly in Set PG/PC Interface. The reported machine had SIMATIC NET installed alongside STEP 7, so open the station configuration and look for the PC's interface module there before touching anything else.
Decision with a SIMATIC NET configuration: set the CP's parameters in the Communication Settings tool; in Set PG/PC Interface only the assignment of the access point to the configured CP remains. Decision without one: the properties open directly in Set PG/PC Interface, so a refusal on such a station means the tool itself is broken, and the environment and service checks below apply.
For STEP 7 online access the documented selection is: open the Control Panel of the configuration PC, open Set PG/PC interface, and select the entry "S7ONLINE (STEP 7)" in the first tab. If that entry will not save its assignment, treat it as the same environment fault, not as a wrong selection.
Why does the tool report SRMD_Set(..) - No interface handle? #
That error means the tool could not obtain a handle to any interface, and in a documented case on 64-bit Windows 7 the cause was the SIMATIC OAM bin directory missing from the system Path, cleared by restoring the entry. The check lives at Control Panel, System, Advanced system settings, Advanced tab, Environment Variables: compare every Siemens entry with the folders actually present on disk and restore only entries whose folders exist.
| System variable | Value in the resolved 64-bit Windows 7 case |
|---|---|
AutInstLog |
C:\ProgramData\Siemens\Automation\Logfiles\Setup\ |
S7TMP |
C:\Program Files (x86)\Siemens\Step7\S7Tmp |
Simatic_OAM |
C:\Program Files\Common Files\Siemens\Automation\Simatic OAM |
Simatic_OAM_DATA |
C:\ProgramData\Siemens\Automation\Simatic OAM |
SQLANY |
C:\Program Files (x86)\Common Files\Siemens\Sqlany |
Path, Siemens entries in order |
C:\Program Files (x86)\Common Files\Siemens\Sqlany then C:\Program Files (x86)\Siemens\Step7\S7bin, with C:\Program Files\Common Files\Siemens\Automation\Simatic OAM\bin\ last after the standard Windows system folders |
The entries between the Siemens folders are the standard Windows system folders, and the SIMATIC OAM bin entry sits at the end of the reported list. Copy none of these values onto a Windows XP machine: the folder layout differs between the systems, and an entry that points at nothing reproduces the error. The same error text was also reported where a firewall blocked the process; running the tool as administrator and allowing the Siemens programs cleared that variant.
Why will the Siemens automation service not start after the upgrade? #
Because the refusal comes from the environment, not the application files: the service on the reported machine could neither run nor be started from Services, and until it runs no PG/PC configuration will hold, whichever tool you open. A start refusal that survives a reinstall of the application files has a short list of causes, and each lives in the environment: a dependency that is not running, a module the service cannot find, or a permission the log records as denied.
Record the service exactly as Services lists it, open its properties and read the Dependencies tab, then read the matching start-failure entry in Event Viewer. A missing-module entry sends you back to the Path check; an access-denied entry points at permissions or security software. No reinstall comes before this service runs.
In what order should you run the checks? #
Run them in this order: record the state, answer the SIMATIC NET question, verify the environment variables, start the service, then retest, because each result tells you whether the next step is worth doing.
- Record the exact message text, the selected access point and the interface currently assigned in Set PG/PC Interface.
- Open the station configuration and answer whether a SIMATIC NET configuration exists; that decision picks the tool for the CP properties.
- In Environment Variables, compare every Siemens entry with the folders on disk and restore only entries whose folders exist, watching the SIMATIC OAM bin directory in Path.
- In Services, record the failing automation service by its listed name, read its Dependencies tab and the matching entry in Event Viewer, then start it.
- Where the operating system separates user rights, run the tool as administrator and confirm the firewall is not blocking the Siemens programs.
- Retest: open the CP properties, then go online from the engineering software.
How do you prove online access is really restored? #
Three results on the same boot prove it: the service that would not start now runs, the CP properties open without the message, and the engineering software reaches the target controller online. Passing only the first two proves the configuration layer and nothing else, so the online test is the one that counts, and it belongs on a machine in a state where an unexpected write or download cannot move anything: the bench, or the process stopped.
If the interface now works but WinCC flexible still offers no device to transfer to, that is a separate fault with its own fix, described in why WinCC flexible 2008 SP2 lists no device to transfer to an MP277.
Should you reinstall STEP 7 to clear the message? #
No: in the reported case STEP 7 was removed and reinstalled and online access did not come back, which is the useful result, because a reinstall that changes nothing proves the fault sits in the environment and configuration, not in the application files. A second installation onto the same damaged environment reproduces the same failure and costs the downtime twice, so the reinstall is the last step, not the first: correct the environment entries, get the service running, retest, and reinstall only for a fault that survives all three checks.
Before another station takes the same upgrade pair, the compatibility pass described in Checking HMI engineering software before a panel replacement catches the software gaps while the old system still runs.
Questions asked
Why did the failure appear only after the upgrades?
Two changes landed in one maintenance window, Windows XP from SP2 to SP3 and WinCC flexible from 2005 to 2008, so neither can be isolated as the single cause. What the case does establish is the class of fault: the service would not start and a reinstall of STEP 7 changed nothing, which rules the application files out and points at the environment and the configuration route.
Which single Path entry fixed the resolved case?
The SIMATIC OAM bin directory under Common Files, added back as the last entry of Path. The remaining Siemens entries in that list, the Sqlany and S7bin folders, plus the separate S7TMP and Simatic_OAM variables, serve as the reference picture of a correct installation to compare against, not as something to rebuild entry by entry.
What should you do if the service still refuses to start after the Path is corrected?
Open the service's properties and read the Dependencies tab to see which services must run first, then read the start-failure entry in Event Viewer's System log. Fix what the log names before any reinstall.
Will reinstalling STEP 7 again restore online access?
No. STEP 7 was removed and reinstalled on the reported machine and the CP message stayed while the service still would not start, so the fault survives a reinstall of the application files. Correct the environment entries, get the service running and retest; only a fault that remains after all three checks pass justifies another installation.