IMDTouchKnowledge BaseShop main store

Troubleshooting

What WinCC Runtime Advanced needs on an S7-1200 HMI PC

HMI and touchscreens Published 9 min read

Short answer

A PC that only operates an S7-1200 needs one software package: WinCC Runtime Advanced, installed from the dedicated runtime setup, plus a compiled project and a working Ethernet path. SIMATIC NET is not required for this HMI connection; it enters only when the same PC also runs a Siemens software controller. The example station runs V13 SP1 Update 9.

On this page
  1. What software does a PC need to be an HMI for an S7-1200?
  2. Do I need SIMATIC NET for WinCC Runtime Advanced with an S7-1200?
  3. Which installer goes on the HMI PC, and does TIA Portal need to be there?
  4. What license does WinCC Runtime Advanced need on the PC?
  5. What project file does WinCC Runtime Advanced load?
  6. How do I configure the S7-1200 connection in the project?
  7. What IP addresses do the HMI PC and the S7-1200 need?
  8. Does the S7-1200 need PUT/GET enabled for this HMI connection?
  9. What do I check when the screen opens but the values stay static?
  10. Questions asked

A PC that only operates the machine needs exactly one Siemens software package to talk to an S7-1200: WinCC Runtime Advanced. Install it from the dedicated runtime setup, transfer the compiled project, put the PC and the CPU on one reachable Ethernet path, and the operator station is done — SIMATIC NET is not on that list. The sections below follow one commissioning from an empty disk to live values: the example project is built in WinCC Advanced V13 SP1 Update 9, the target PC runs WinCC Runtime Advanced V13 SP1 Update 9, and the CPU sits on the machine network. When the software is right but the screens still show nothing, the last section is the ordered fault hunt.

What software does a PC need to be an HMI for an S7-1200? #

One package is enough: WinCC Runtime Advanced from the dedicated SIMATIC WinCC Runtime Advanced setup, which carries the S7-1200 driver, loads the compiled project through the WinCC Runtime Loader and exchanges tags with the CPU over Ethernet, with no TIA Portal and no SIMATIC NET on the machine.

The complete install list for the operator role has three items, and nothing else is missing:

  • WinCC Runtime Advanced, from the dedicated runtime setup, at the version level the project expects
  • the compiled .fwc project file, delivered by the WinCC Runtime Loader
  • a runtime license key held on this PC

Screens, HMI tags and the connection definition are not installed separately — they travel inside the compiled project. The engineering side that builds those things runs TIA Portal with WinCC Advanced on a different PC, and nothing from that engineering install belongs on the operator PC.

Do I need SIMATIC NET for WinCC Runtime Advanced with an S7-1200? #

No — for an HMI-only PC talking to an S7-1200, WinCC Runtime Advanced alone carries the communication stack the configured connection needs, SIMATIC NET adds nothing and fixes nothing, and it becomes relevant only when the same PC also runs a Siemens software controller.

Much of the confusion comes from reading installation notes for the wrong runtime family: the installation documentation for WinCC Unified lists SIMATIC NET among its product-specific special characteristics, and that requirement does not carry over to Runtime Advanced on an S7-1200 station. Installing SIMATIC NET on an HMI-only PC does not repair a wrong address, wake a disabled adapter or mend a broken tag map, because the HMI connection never calls those components.

The answer changes exactly once: when the same PC is also meant to host a Siemens software controller, SIMATIC NET joins the install list and the network design has to change with it, for the reasons set out in why a software controller needs a separate Ethernet operator path. For every other S7-1200 operator station the decision stands: runtime only.

Which installer goes on the HMI PC, and does TIA Portal need to be there? #

Use the dedicated SIMATIC WinCC Runtime Advanced setup rather than the engineering DVD that carries WinCC Advanced or TIA Portal, because the runtime installer stands on its own and does not require TIA Portal anywhere on the operator machine.

Running the engineering DVD on an operator PC drags in screen-editing components the station never uses and blurs which machine is allowed to change a running project. Keep the engineering station as the only place TIA Portal lives, and the operator PC as the place where compiled projects are loaded.

After installation, open the installed-products information on the runtime PC and read the level back. The example station shows WinCC Runtime Advanced V13 SP1 Update 9, and SIMATIC NET need not appear anywhere on that list. Pair the runtime to the project rather than to habit: the example engineering station compiled the project in WinCC Advanced V13 SP1 Update 9, so the runtime sits at the same service pack and update level, and a runtime reads projects from its own or an earlier engineering version.

What license does WinCC Runtime Advanced need on the PC? #

Every runtime PC carries its own license key, a USB dongle or a software key installed on that machine, sized to the project's tag count; the licensing documentation names the base tier as WinCC Runtime with 128 tags, and a project with more tags needs the tier above it.

The key is checked where the runtime runs, so the operator PC is the machine that has to hold it — a dongle that lives in the engineering cabinet licenses nothing at the machine. Size the tier by counting the controller-backed tags the compiled project uses and taking the tier above that number, and treat a missing or mismatched key as a before-the-network check: the runtime does not bring the project up without the license it is sized for.

What project file does WinCC Runtime Advanced load? #

The runtime does not open the engineering project — the WinCC Runtime Loader loads the compiled .fwc file that WinCC Advanced produces when the HMI station is compiled, so a change made in the project never reaches the screen until it is compiled and transferred again.

That split is the mechanism behind why an HMI edit needs a new runtime download: the engineering project on the office PC and the file the operator PC loads are two different artifacts, and only the second one runs. Transfer goes over the same Ethernet path, from the engineering PC to the loader on the runtime PC. Keep transfer problems separate from controller problems: if the compiled file will not load, the cause is version, transfer path or license, and the CPU has not been asked for a value yet.

How do I configure the S7-1200 connection in the project? #

In the engineering project, open the Connections editor of the HMI device, create the connection with the SIMATIC S7 1200 channel, select the PC network interface that faces the machine and enter the CPU's IP address, because the runtime will use exactly that connection definition from the compiled project.

Bind the connection to the interface the machine network actually uses. On a PC with several adapters, the project can point at a specific one, and a docking-station or wireless adapter can quietly take the traffic somewhere else; commission on a single wired path where practical. Check firmware compatibility between the HMI device entry and the CPU while the engineering tool is open, since it validates the HMI device against the CPU's firmware. Then map at least one HMI tag to a real PLC variable and put it on the start screen — a screen object bound to an internal HMI tag updates locally and proves nothing about the CPU. Every fix in this section ends the same way: recompile, transfer, restart the runtime.

What IP addresses do the HMI PC and the S7-1200 need? #

Give the PC and the CPU addresses in the same subnet and the runtime reaches the controller directly with no gateway — for example a PC at 192.168.0.10 and an S7-1200 at 192.168.0.1, both with mask 255.255.255.0, sit in one network.

Worked example, with illustrative addresses. The commissioning PC gets 192.168.0.10 with mask 255.255.255.0; the S7-1200 keeps 192.168.0.1 with the same mask. Whether two stations are direct neighbours is decided by ANDing each address with the mask:

  • 192.168.0.10 AND 255.255.255.0 gives 192.168.0.0
  • 192.168.0.1 AND 255.255.255.0 gives 192.168.0.0

Both network addresses come out as 192.168.0.0, so the PC and the CPU sit in one subnet and the traffic never needs a default gateway. If the CPU had instead been left configured at 192.168.1.1, its network address would compute to 192.168.1.0 — a different network from the PC's 192.168.0.0 — and every packet would set off toward a gateway that does not exist on an isolated machine net, which reads exactly like a dead PLC.

Keep every address unique, including the PC's: a station that borrows the CPU's address, or any duplicate on the net, produces intermittent reachability that moves as devices power up. Compare the full address and mask rather than the last octet — the mask, not the last number, decides the network. Close the check with a ping from the HMI PC to the CPU's address: a reply proves the IP path, and it proves nothing about the runtime channel or the tags. The addresses above are an illustration; apply the same subnet logic to whatever plan the machine network actually carries.

Does the S7-1200 need PUT/GET enabled for this HMI connection? #

Not for the connection configured in the Connections editor — the S7-1200 HMI link that WinCC Runtime Advanced uses does not require PUT/GET to be enabled on the CPU, so a protection setting left closed does not block the operator screens.

The CPU's permission for PUT/GET communication from remote partners governs access that is not configured through an HMI connection, which is where the setting's reputation comes from. Enabling it is therefore not a fix, and its absence is not a fault: when the screens show no values, this is the wrong trail. Leave the CPU protection as the project design intends it and spend the commissioning hour on the connection data, the addressing and the tag mapping instead.

What do I check when the screen opens but the values stay static? #

Work down one path only — license and start state, then link, then addressing, then connection data, then the tag itself — because in practice the fault sits in the compiled project's connection definition or in a screen object bound to an internal HMI tag instead of a controller-backed tag.

  1. Read the runtime state first: the project must have started to its configured start screen with its license key present. A runtime that never started explains a completely static screen faster than any network test.
  2. Check the wired adapter's link state and the switch port on the machine network. A link light proves the cable and the port, not a conversation.
  3. Ping the CPU's address from the HMI PC — the example station pings 192.168.0.1 — and read a reply as proof of the IP path only.
  4. Change a value in the CPU from an approved commissioning tool and watch the controller-backed test tag on screen. Then write one value back from the HMI on a non-hazardous condition with the machine's interlocks respected — that is the one safety rule in this procedure.
  5. If the object follows an internal tag but ignores the PLC tag, the connection or the mapping is the fault. Correct it in the project, recompile and transfer again, because the compiled file is what the runtime loads.
  6. If the transfer to the runtime PC itself stalls, stop tuning the PLC: the PC sees the station but the download stops, which is a failure mode of its own, set out in why an HMI is detected but project download fails.

The decision, case by case. An HMI-only operator PC: install WinCC Runtime Advanced from the runtime setup with its license key, and nothing else. A PC that will also host a Siemens software controller: add SIMATIC NET and separate the network paths before commissioning. A runtime that refuses the compiled project: align the engineering and runtime versions, recompile and transfer. Static values on a loaded screen: work the six checks in order and expect the fix to end in a recompile and a fresh transfer, not in new software.

Questions asked

Can two operator PCs share one WinCC Runtime Advanced license?

No. Moving one key between two running stations leaves one of them unlicensed, and that runtime can refuse to bring its project up until the key is back on its own PC, so plan one dongle or software key per runtime installation from the start.

Why does the runtime refuse to load the project my engineering station compiled?

A runtime reads projects from its own or an earlier engineering version, so a compile from a newer engineering level will not load. Read the installed product version on both machines; either update the runtime to match or rebuild the project at the runtime's level, then compile and transfer again. The example pair, engineering and runtime both at V13 SP1 Update 9, loads without a version rejection.

Can one PC do the engineering and the operator work at the same time?

It is possible, but keep them separate. The operator PC needs only the runtime and the compiled project, the PLC program lives entirely in the S7-1200, and the screen edits belong on the engineering station. Engineering software on a machine that runs production invites edits to live screens and adds components the runtime never uses.

The ping test passes, so why do the screens still show no live values?

A ping reply proves the IP path and nothing else. Check that the screen object is bound to a controller-backed tag rather than an internal HMI tag, then confirm the connection data in the project and recompile, because the compiled file the runtime loads still carries the CPU's address from when it was last built.

Keep reading

  • How-to

    Selecting a WinCC Unified PC Target in TIA Portal

    An IPC can host WinCC Unified as a PC-based HMI. If the SIMATIC HMI application list shows only WinCC RT Advanced, your TIA Portal installation is missing the Unified PC engineering option: add a PC station, add the SIMATIC WinCC Unified PC application, then match the runtime version and license on the target computer. The hardware is not the deciding check.

    HMI and touchscreens

  • Troubleshooting

    What WinCC V11 needs to run a PC as an HMI

    WinCC V11 Professional in TIA Portal configures and downloads HMI projects; it does not make the PC a runtime station by itself. To run the PC as an HMI you install WinCC Runtime Advanced for panel-class projects or WinCC RT Professional for SCADA, each on its own runtime license. When the Advanced setup stops at the Sebu_winccv11 check, the image carries classic SIMATIC packages the V11 SP2 compatibility list does not clear, so clean the machine and reinstall.

    HMI and touchscreens

  • Comparison

    Choosing Free Modbus HMI Software for a Windows Panel PC

    For a Windows panel PC that must show Modbus TCP data and alarms, Ignition Maker Edition and VTScada Lite are the only candidates with a free tier and a specific Modbus TCP claim on record. Maker Edition is documented free for non-commercial use only, so production machines bench-test VTScada Lite first or fall back to code-based AdvancedHMI.

    HMI and touchscreens

Does an HMI need setup to recognize a MicroSD extended memory card