Why the KTP700 Basic popup keypad cannot be modified

HMI and touchscreens Published 6 min read

Short answer

The popup keypad on a KTP700 Basic is drawn by the panel runtime and has no editable object in TIA Portal, so no setting or engineering license changes it. Custom keypads are screens of script-driven buttons, and Basic panels run no scripts, so they are documented only for WinCC Advanced panels and PC Runtime. Keep the built-in keypad and size your own fields, or move the configured target.

On this page
  1. Why the KTP700 Basic keypad is fixed
  2. What a higher license changes
  3. Why scripts decide it
  4. Worked example: deciding for the setpoint screen on the KTP700 Basic
  5. What to do instead
  6. The decision, case by case
  7. Questions asked

No, the popup keypad on a KTP700 Basic cannot be modified. TIA Portal V13 exposes no object, property or setting for it, and a higher engineering license does not change it, because the keypad is drawn by the panel's own runtime, not by anything in your project. The documented route to a different keypad — a screen of buttons whose events call scripts — exists for WinCC Advanced panels and WinCC Advanced PC Runtime, and Basic panels do not run scripts. The lever is the configured target device, not the engineering product: a project that names WinCC Professional still behaves as a Basic panel for as long as its device configuration names the KTP700 Basic. This article explains why the keypad is fixed, what a license changes and does not, works the decision for a setpoint screen, and gives the call for each case.

Why the KTP700 Basic keypad is fixed #

Basic panels have no popup screen layer in the way Comfort panels do. When the operator touches an IO field on the KTP700 Basic, the runtime draws its built-in keypad over the current screen. That keypad is not a project object: nothing in the TIA Portal toolbox, properties list or runtime settings selects it, resizes it or rearranges its keys, so there is nothing to edit.

The engineering product named in the project does not enter into it. A station configured for a KTP700 Basic compiles and runs as a Basic panel project whether the engineering station holds WinCC Basic or WinCC Professional; WinCC Professional is the engineering product for PC Runtime stations, and it does not attach new behavior to a Basic panel target.

The complaint itself is fair. On a 7 in widescreen panel, the built-in keys are small for frequent setpoint entry, and operators feel it on every edit. Small touch targets are a known pain across compact panels — popup calendar buttons that are too small for touch panels are the same class of problem on other devices.

What a higher license changes #

Nothing about this keypad. The engineering license decides what your PC can open, edit, simulate and compile; it does not change what the panel runtime draws at the machine. The keypad's layout, key size and key count are behavior of the Basic panel family, so moving the license tier up from WinCC Basic engineering through WinCC Professional or beyond leaves the keypad exactly as it was.

Check the one input that actually moves the answer: which HMI device the project's device configuration names. If that entry is the KTP700 Basic, the keypad is fixed on any license. If the project instead targets a Comfort panel or a PC Runtime station, the question reopens, because those targets run the scripts a custom keyboard needs.

Why scripts decide it #

The documented custom keyboards are screen builds. A keyboard is a project screen of button objects; each key's press event calls a script, and the script places that key's character into the input field. Siemens documents the approach for WinCC Advanced panels and WinCC Advanced PC Runtime in support entry 106226404, and an earlier on-screen keyboard for WinCC flexible PC Runtime stations in support entry 52257864. Every key on either keyboard lives or dies by a script event firing.

Basic panels do not execute project scripts. With no script engine on the target, a keyboard built this way cannot place a single character on a KTP700 Basic, which is why both documented designs stop at the Advanced and PC Runtime targets. Scripting support differs across panel families in both directions — even Comfort panels, which do run scripts, take VB scripts only, as covered in why a Comfort panel shows only VB scripts, not C scripts — so the target sets what a keypad can be, not the toolbox.

Worked example: deciding for the setpoint screen on the KTP700 Basic #

The inputs, and where each comes from:

  • Configured HMI device: KTP700 Basic, a 7 in widescreen panel — the entry in your project's device configuration, the case from the question.
  • Engineering station: TIA Portal V13, with WinCC Professional named in the project description.
  • Script events the configured target executes: 0 — the Basic panel family runs no project scripts.
  • Script calls one custom key needs per press: 1 — in both documented keyboard designs, each key places its character through a script event.

The rule in words: a custom key works when its press event can fire, so the working keys equal the script events the target runs minus the script calls the key needs. If that difference is negative, the press completes nothing.

The arithmetic: 0 events available − 1 call needed per press = 1 call short on every press. One call short means no character lands in the field, so the working-key count is 0 of every key drawn.

The result: on the KTP700 Basic, a script-built keypad has 0 working keys, and the built-in keypad — which the runtime draws without scripts — remains the only entry method.

The decision, with its threshold: a target qualifies for a custom keypad when it executes project scripts. Basic panels expose no script events, so with the KTP700 Basic configured, keep the built-in keypad and design your fields around it. When the configured device is a WinCC Advanced panel or a WinCC Advanced PC Runtime station, the script-event count is no longer 0 and the script keypad is a design option.

What to do instead #

  • Accept it on the KTP700 Basic. The IO field is your object: make setpoint fields large, position them so the built-in keypad does not cover them, and put a critical entry on its own screen. Key and shortcut operation is documented for Basic panels, so the panel's own keys carry frequent edits without touching the screen.
  • Change the target when bigger keys are a requirement, not a wish. Reconfigure the station to a WinCC Advanced panel or a WinCC Advanced PC Runtime station and build the keypad as a screen of script-driven buttons, following the documented designs. A PC Runtime station needs a touchscreen computer mounted at the machine, and that is the role industrial panel PCs are built for.
  • Spend no license upgrade on this. On the existing KTP700 Basic it buys nothing.

One safety note belongs with setpoint entry on a temperature loop: clamp the setpoint in the PLC, not on the panel, so that whatever keypad carries the number, the controller still enforces the limits on a mistyped entry.

The decision, case by case #

  • Project configured for the KTP700 Basic: the keypad cannot be modified. Keep it, size your IO fields around it, and use the panel keys for frequent entry.
  • Larger keys are a hard requirement from the operators: change the configured device to a WinCC Advanced panel or a WinCC Advanced PC Runtime station, then build the script-driven keypad.
  • A higher engineering license is proposed for the existing KTP700 Basic: it does not change the keypad; decline it for this purpose.
  • The project actually targets a Comfort panel or a PC Runtime station: a custom keypad is feasible, built with VB script events on key buttons.

Questions asked

Will a higher TIA Portal license let me modify the KTP700 Basic keypad?

No. The license changes what the engineering station can open, edit and compile, not what the panel runtime draws. The keypad is fixed behavior of the Basic panel family, and a Basic target executes no project scripts, which is the only mechanism a custom keypad uses. Upgrading the engineering product leaves the keypad untouched; only changing the configured target device does.

Do Comfort panels have the same fixed keypad?

No. The Basic range has no popup screens the way Comfort panels do, and Comfort targets execute VB script events, which is enough to build larger custom input screens of your own. The catch is language choice: Comfort panels run VB scripts only, not C scripts, so a keyboard design for a Comfort target is written in VB. Check the exact target's scripting support before promising bigger keys.

Is there a documented custom keyboard for a PC runtime?

Yes. Both are screens of buttons driven by script events. Neither runs on a Basic panel, because a Basic panel executes none of the script events those keys depend on.

What can I still change on the KTP700 Basic setpoint screen?

Your own objects. The IO field is a project object: its size, its font and its position on the screen are yours to set, so make setpoint fields large and keep them clear of the area the built-in keypad covers. Key and shortcut operation is documented for Basic panels too, so frequent edits can go through the panel's physical keys instead of the small on-screen ones.

Will a firmware update change the Basic panel keypad?

Treat the keypad as fixed for the life of the target. No documented Basic panel setting or project object exposes its layout, and no released change promises a different layout or key size for the Basic range. If key size is a hard requirement from the operators, that requirement belongs in the device selection step, when the target platform is chosen, not in the panel project afterwards.

Keep reading

  • Explainer

    Why WinCC Professional cannot program a Unified Comfort Panel

    A Unified Comfort Panel is programmed only with WinCC Unified Engineering; WinCC Professional builds applications for a different set of targets and cannot download to this panel. Multitouch is a panel capability, not a compatibility path. Before V19 the two engineering packages could not share one PC; from V19 parallel installation is documented.

    HMI and touchscreens

  • How-to

    Enable object access on a KTP700 Basic Panel with Visibility

    On a KTP700 Basic Panel you cannot use VBScript or the Control enable animation, so you gate operator access with an Animations > Display > Visibility animation instead. The on-screen keyboard layout is fixed on smaller panels and only resizes on larger Comfort Panels.

    HMI and touchscreens

  • Troubleshooting

    Why HmiDigitalClock Is Missing on a Unified Basic Panel

    The Style list on a Clock object only offers HmiClock because the MTP1000's configured module version is V18.0.0.3, and the digital style was introduced with Unified runtime V19.0.0.0. Update the module version in Devices & Networks, or build the clock as an output-only I/O field driven by JavaScript until you can update.

    HMI and touchscreens

Why Vijeo Designer Basic Router Fields Stay Greyed Out