Why WinCC flexible MPI transfer closes its waiting window

HMI and touchscreens Published 6 min read By IMDTouch engineering team

Short answer

The waiting window closes because the Loader's MPI transfer channel cannot open the CP5611; a channel that initializes, as Ethernet does here, keeps the window open. Runtime SP3 is the released service pack for 64-bit Windows 7, so the project, the installation and the user groups are cleared. The fault is the adapter's 64-bit communication driver or the access point that should bind MPI to the CP5611.

On this page
  1. What the closing window establishes
  2. The released combination, component by component
  3. Check the CP5611 driver first
  4. Then verify the access point assignment
  5. The decision for each reading
  6. If the window still closes
  7. Questions asked

The waiting window that opens and immediately closes means the Loader's MPI transfer channel failed to open the CP5611, so the transfer service dropped its waiting state. The Ethernet channel holding that same window open proves the Loader itself is healthy and pins the fault to the MPI path: the adapter's 64-bit communication driver, or the access point that should bind MPI to that adapter. With WinCC flexible 2008 Runtime SP3 on Windows 7 64-bit you are on the released service pack, so the project, the installation and the user groups are cleared as causes. Run the checks below in order; each ends with a reading and a decision.

What the closing window establishes #

The Loader is started from Start > SIMATIC > WinCC flexible 200x Runtime, and its Settings button is where the transfer channel is chosen. Project transfer loads the compiled application into the runtime station; process-data exchange with the S7-300 begins only after that application starts. These are separate functions, so a working MPI runtime connection would not prove a working transfer path, and a dead transfer channel says nothing yet about the project.

When you select a channel, the transfer service binds to it and then waits for the engineering station. A channel that initializes keeps the window open; a channel that will not initialize is abandoned, and the window goes with it. The reported observations therefore read as follows:

Observation What it establishes Next check
MPI window closes immediately The MPI channel would not initialize Driver first, then the access point
Ethernet window stays open The Loader holds a waiting state correctly; the fault is channel-specific Use it as the comparison, nothing more
No error message, no event-log entry The channel was dropped before any fault was raised Device Manager and the communication diagnostics

The driver check comes first for one reason: no access point can be mapped to an adapter the system has not loaded.

The released combination, component by component #

WinCC flexible 2008 Runtime in SP3 is the documented release for 64-bit Windows 7, and the reported station already runs it, so the application layer is cleared. Releases are granted per component, not per generation: WinAC MP 2008 for WinCC flexible 2008, for example, is released for Windows XP only and does not run on Windows 7. Apply the same rule to the CP5611: it needs a communication package whose compatibility list includes Windows 7 64-bit for that exact card. The account's membership in the SIMATIC NET groups proves the package was installed at some point; it says nothing about whether the installed driver revision is 64-bit capable.

Check the CP5611 driver first #

  1. Open Device Manager and locate the CP5611. Record the device status, the driver provider and the driver version. A card in an error state, or one Windows cannot load a driver for, is the cause; stop here.
  2. If the card shows no usable driver, install the 64-bit driver released for Windows 7 64-bit with the installed communication package, sourced from Siemens or its distributors, not from an arbitrary download.
  3. Run the bus diagnostics supplied with the installed communication software against the CP5611. The reading is binary: the adapter opens and lists reachable nodes, or it cannot be opened.
  4. If the adapter opens but the S7-300 is missing from the node list, the fault has moved off the driver: confirm the MPI transmission rate and station addresses match the network. For example, on a bus running 187.5 kbit/s with the CPU at address 2, the CP5611 needs the same rate and its own free address. This is the failure class behind why a station search over MPI comes back blank.

Then verify the access point assignment #

In Control Panel, Set PG/PC Interface maps each named access point to a physical interface. Having every entry set to MPI is not the check that matters: an MPI label on every entry does not say which interface each access point is actually bound to. What must be true is narrower: the access point the transfer uses is assigned to the CP5611's MPI parameterization, the entry that carries the adapter's name.

  1. Open Set PG/PC Interface and write down the current access point and its interface assignment before changing anything.
  2. Assign the access point used for transfer to the CP5611 MPI entry, with network parameters that match the bus.
  3. Restart the Loader, select MPI as the transfer channel and click Transfer. Expected reading: the waiting window stays open.

If the CP5611 is missing from the interface list altogether, no mapping can help: that is the driver failing to register, the same failure as an adapter that does not show in the PG/PC interface on Windows 7 64-bit, and the fix is the driver installation in step 2 above.

The decision for each reading #

  • The card sits in an error state or has no driver: install the released 64-bit driver. If the compatibility list offers no 64-bit driver for the CP5611 on this system, the card is a dead end on this station; move the MPI channel to a PC Adapter USB A2, as covered in using a PC Adapter USB A2 as the runtime MPI channel.
  • The adapter opens and the diagnostics list nodes: the mapping was the fault. Correct it as above; the window will hold and the transfer will run.
  • The adapter opens and the PLC is missing: fix rate, address and bus termination first, then return to the mapping step.
  • Whatever the readings, the transfer itself does not need MPI. Set the transfer channel to Ethernet and move the project today; MPI only has to work for the runtime connection to the S7-300.

The reported station, walked end to end: Windows 7 Enterprise 64-bit with Runtime SP3 is a released combination, so that box is closed. The Ethernet window holds, so the Loader is healthy. That leaves exactly two suspects inside the MPI path, and the Device Manager reading picks between them: an error-state card means the driver line; a healthy card that the diagnostics open means the mapping line. Either way, the transfer goes over Ethernet while the MPI channel is repaired.

If the window still closes #

Capture the failure on paper before it goes to vendor support: the OS edition and architecture, the runtime service pack, the adapter model, the driver version, the access point assignment and both diagnostic readings. Two extra controlled tests belong in the record: the Loader run once from an elevated prompt, and once with every other communication client closed, since another application can hold the adapter. Note that entering transfer mode takes the runtime off its normal screen, so run these tests only when the visualization may be interrupted. A support case opened with that record begins at the failure instead of at the questionnaire.

Questions asked

Which service pack does WinCC flexible 2008 need on 32-bit Windows 7?

SP2 or SP3. On 64-bit Windows 7 the requirement is SP3 only. A version older than those packs is not a released combination for Windows 7, so a 32-bit station still on SP1, for example, has to be updated before the transfer channel is even considered.

Why is there no error message or event-log entry?

Because nothing crashed in the Windows sense. The transfer service tried the MPI channel, could not initialize it, and abandoned the waiting state, and a handled exit raises no event. The silence is itself a signature of a failed channel binding, which is why the diagnostics, not the event log, have to produce the evidence.

Do the user groups need changing?

No. The account already belongs to the groups the installer creates for the HMI and the communication software, and a permissions fault announces itself with a message rather than a silently closing window. Adding memberships will not change this behavior; whether the Loader's process can open the adapter depends on the driver loading, not on more groups.

Can the CP5611 be swapped for a USB adapter on this station?

Yes, when no released 64-bit driver exists for the card. A PC Adapter USB A2 takes over the MPI channel for the runtime connection, attaches without a PCI slot, and appears as its own entry in the interface list, so the transfer access point is remapped to it. Keep the network's transmission rate and give the adapter its own free station address.

Keep reading

  • Troubleshooting

    Why WinCC flexible Runtime Cannot Control an S7-1200

    WinCC flexible Runtime on the PC is a separate HMI station, not a view into the MP277, so a working panel proves nothing about the PC path. Ping the S7-1200 from the Runtime PC, confirm the project connection uses the S7Online access point, then map that access point in Set PG/PC Interface to the adapter that reaches the real PLC, or to the simulation path when PLCSIM is the destination.

    HMI and touchscreens

  • Troubleshooting

    Why WinCC Flexible transfer to a TP177B PN/DP fails instantly

    The error appears instantly and identically with or without the panel and cable attached, so WinCC Flexible 2008 stops while opening the local interface, before any message reaches the TP177B. Use the PC Adapter USB 6ES7 972-0CB20-0XA0 instead of the serial cable through a converter, assign its entry in Set PG/PC Interface, activate the matching data channel on the TP177B 6AV6 642-0BA01-1AX1, and start the transfer again.

    HMI and touchscreens

  • Troubleshooting

    Why WinCC Runtime Professional Shows No Data From PLCSIM

    The runtime window opening with static screens means the runtime process runs but its path to the simulated CPU does not. Point the access point in Set PG/PC Interface at PLCSIM or the matching TCP/IP route, compile the PC station, connect the TIA project to PLCSIM, and put the CPU in RUN before the runtime starts.

    HMI and touchscreens

Why the 840D sl HMI package will not install on Windows 7 x64