Explainer
Why WinCC joins SINUMERIK Operate instead of replacing it
Short answer
WinCC Runtime Advanced does not replace SINUMERIK Operate on a PCU-based 840D sl. It is integrated into Operate and opened from a configured softkey, so the standard screens stay available while you build the machine-specific screens in WinCC. The option required is 6FC5800-0AP61-0YB0 once per NCU; the SIMATIC-panel option in the proposal belongs to a different architecture.

On this page
- What the integration does on the PCU
- Why Operate screens do not convert into WinCC screens
- The order numbers and the one to strike
- Correcting the license list for a batch of five grinding machines
- Keep the skeleton and cut the visible surface
- Pair the versions on the engineering seat
- The decision for the machine
- Questions asked
On a SINUMERIK 840D sl with a PCU50.5, Windows 7 and an OP015, WinCC Runtime Advanced does not replace SINUMERIK Operate. It is integrated into Operate and opened from a softkey you configure, so the standard Operate screens stay available next to your own WinCC screens, and access to the Operate side can be restricted. The option that pays for this on the control is 6FC5800-0AP61-0YB0, SINUMERIK Integrate Run MyHMI /WinCC, required once per NCU. The Run MyHMI /SIMATIC OP option, 6FC5800-0AP03-0YB0, belongs to designs where a SIMATIC panel is the operator device, so it does not fit a PCU-based grinding machine. That settles the architecture: keep Operate's basic structure, reduce what production can reach, and build the grinding screens in WinCC.
What the integration does on the PCU #
WinCC Runtime Advanced runs as an application integrated into SINUMERIK Operate on the PCU. A configured Operate softkey opens your WinCC user interface, the complete Operate screen set remains usable in addition to the WinCC screens, and access to Operate can be restricted. The Create MyHMI /WinCC manual documents the integration in chapter 11 and the access restriction in chapter 8.5; work from the revision that matches your installed software, because a chapter reference from another release can describe a different mechanism.
Through this integration the WinCC screens can use the data, alarms and PI services of the SINUMERIK 840D sl, which is what the delivery release for Create MyHMI /WinCC V15 Update 1 lists together with the per-NCU option. On the engineering side, Create MyHMI /WinCC is required as a supplement to SIMATIC WinCC Advanced whenever the user interface being created accesses NCU data, so the two packages are a pair, not alternatives.
Why Operate screens do not convert into WinCC screens #
The standard areas such as Machine and Commissioning are Operate application pages with control-specific behavior, navigation and access rules built in. No documented import turns them into WinCC pictures, and the integration does not change that: it adds your screens alongside them, it does not dissolve them. A button on a WinCC screen therefore does one of three things — it opens one of your own screens, it calls a function the integration documents, or it hands the operator back to Operate, where the trace or axis-diagnosis page is drawn by Operate as before.
The flexible-based machine screens do not port control for control either. From Create MyHMI /WinCC V13 on, the File viewer and File editor controls known from WinCC flexible are no longer available; selecting and editing part programs is handled as Siemens support entry 99414532 describes. Plan the grinding screens as new WinCC work that reuses your parameter list and validation rules, not as a translation of the old HMI PRO sl or EasyScreen pictures.
The order numbers and the one to strike #
The bill of materials for this design has four candidate lines, and one of them must go.
| Order number | Item | How it counts |
|---|---|---|
| 6AV2102-0AA03-0AA5 | SIMATIC WinCC Advanced V13 engineering software | Once per engineering workstation, under its license terms |
| 6FC5861-3YC43-0YA0 | SINUMERIK Integrate Create MyHMI /WinCC V13 | The same workstation, once; the supplement that opens NCU data to the project |
| 6FC5800-0AP03-0YB0 | SINUMERIK Integrate Run MyHMI /SIMATIC OP | For a SIMATIC panel as the operator device; strike it on a PCU-based machine |
| 6FC5800-0AP61-0YB0 | SINUMERIK Integrate Run MyHMI /WinCC | Once per NCU, on every machine |
An engineering license authorizes development on the workstation; it is not the machine's runtime entitlement. That entitlement is the per-NCU option, and it repeats with every control, which is why the question of what is needed again for each machine has exactly one answer on this design. The delivery releases do not say whether a separate WinCC Runtime Advanced runtime license is also needed on the PCU; get that single line confirmed in writing by Siemens or an authorized distributor before you release the batch order.
Correcting the license list for a batch of five grinding machines #
Take five machines as the example batch, each with one 840D sl NCU and the PCU50.5 with Windows 7 and OP015 described above, developed on one engineering workstation. The inputs: five machines with one NCU each is the batch being ordered; the two engineering packages come from the one-time workstation purchase; the rule that the runtime option is required once per NCU comes from the documented requirement for this integration.
The rule in words: engineering packages are counted per workstation and bought once, while the Run MyHMI /WinCC option is counted per NCU, so machines multiplied by NCUs per machine.
The arithmetic:
- NCUs in the batch: 5 machines × 1 NCU per machine = 5 NCUs.
- Runtime options: 5 NCUs × 1 option per NCU = 5 × 6FC5800-0AP61-0YB0.
- Engineering: 1 workstation × (1 × 6AV2102-0AA03-0AA5 + 1 × 6FC5861-3YC43-0YA0) = 2 packages, once.
- SIMATIC-panel options on a PCU design: 5 machines × 0 = 0, so the proposed 6FC5800-0AP03-0YB0 line is struck.
The result is an order of two engineering packages once and five per-NCU options. The decision: every NCU carries exactly one /WinCC option however the batch is split, and no SIMATIC-panel option belongs on a PCU-based machine; if the batch later doubles to ten machines, only the per-NCU line doubles, to ten.
Keep the skeleton and cut the visible surface #
Resolve navigation before drawing any screen. The workable division for a grinding machine:
- List production tasks and service tasks separately: grinding-parameter entry and machine operation on one side, diagnostics, trace, axis diagnosis and commissioning on the other.
- Assign each task to an application: the machine-specific workflow to WinCC, everything with control behavior to Operate.
- Define the entry softkey in Operate, including where it sits and which WinCC screen it opens.
- Define the return and service paths, so neither application is a dead end and authorized users still reach the retained diagnostics.
- Apply the access restriction from chapter 8.5 so production navigation shrinks while the maintenance route survives.
Hiding softkeys is the visible half of the last step, not the whole of it: removing a key changes navigation, while the access restriction decides who may reach a function. The mechanics for Operate 4.5 are collected in hiding HMI softkeys on the 840D sl. Keep the standard main groups the operator already knows and add the grinding softkeys inside the groups where they belong, instead of inventing a second structure to learn.
Pair the versions on the engineering seat #
Create MyHMI /WinCC is released in step with its WinCC counterpart — V13 with WinCC Advanced V13 — and later deliveries such as V15 Update 1, V17 and V20 continue the family, so the manual chapters you use are the ones of the installed revision. Match the SINUMERIK-side engineering package to the control's software version the same way which HMI programming package an 840D sl needs by software version sorts the options.
The flexible-based route is closing at both ends. The 840D sl HMI package with WinCC flexible 2008 will not install on a 64-bit Windows 7 engineering PC, as why the 840D sl HMI package will not install on Windows 7 x64 shows, and the PCU 50.5 generation runs SINUMERIK Operate rather than the flexible-based HMI. New grinding screens therefore belong on the WinCC path described here, with HMI PRO sl and EasyScreen kept only where a machine runs Operate in the NCU without a PCU.
The decision for the machine #
Keep the basic Operate structure and hide what production never uses. Build the grinding-parameter screens and their validation in WinCC, open them from one configured Operate softkey, and return to Operate for everything the control already does, from trace to commissioning. Buy the engineering pair once per workstation and one Run MyHMI /WinCC option per NCU, and strike the SIMATIC-panel option from the proposal. WinCC joins Operate on the PCU; it does not replace it — and for a grinding machine that is the point, because the functions you would otherwise reinvent stay part of the control software while your special screens stay yours.
Questions asked
Can the standard Operate screens be imported into the WinCC project?
No import does that. The standard screens remain Operate application pages and stay available next to your WinCC screens; a WinCC button can hand the operator back to Operate, but the page is still drawn by Operate. Rebuilding pages such as trace or axis diagnosis as WinCC objects would mean reimplementing control behavior the documentation does not offer as components, which is why the integration keeps them where they are.
Can the WinCC screens show alarms from the NCU?
Yes. The integration gives the WinCC screens access to the NCU's data, alarms and PI services. From Create MyHMI /WinCC V17 the configuration manual also covers taking user alarm files directly from an NCU and importing them into TIA Portal, so alarm configuration does not have to be entered twice.
Does this work on machines that run Operate in the NCU without a PCU?
No. WinCC Runtime Advanced runs on the PCU, so the integration described here belongs to PCU-based designs such as a PCU50.5 with an OP015. A machine with Operate in the NCU and no PCU keeps its machine screens in HMI PRO sl or EasyScreen, which is one reason builders standardize on HMI PRO sl for such series.
Is hiding softkeys enough to keep operators out of commissioning?
Hiding a softkey removes it from navigation; it does not by itself decide who may call a function. The access restriction described in chapter 8.5 of the Create MyHMI /WinCC manual is the mechanism that matches visible functions to user responsibilities. Do both: hide what production never needs and restrict what only service may reach, then verify the service path with a login you would actually issue.
Is one engineering seat enough for the whole batch?
Count engineering licenses by the workstation or concurrent-use arrangement in their license terms, not by the number of machines built. In the worked batch, one pair of packages on a single workstation covers all five machines, because the item that repeats is the NCU option. A second developer on a separate workstation needs their own pair unless the terms allow otherwise.