Troubleshooting
Why WinCC says the configured server is not running
Short answer
The 'configured server is not running' message means the project's stored computer name does not match the station opening it. Open the project, set Computer properties to use the local computer name, and clear stale .lck lock files. Never delete the .dcf files: that turns the fault into 'Database context does not exist or is invalid', which only Reset_WinCC.vbs from WinCC\bin recovers.

On this page
- What does the configured server message actually mean?
- How do you remap the server name in Computer properties?
- Should you delete the .dcf files?
- When do you run Reset_WinCC.vbs?
- Which .lck files are safe to delete?
- What computer name rules does WinCC enforce?
- Is your Windows user in the SIMATIC HMI group?
- What if the project still will not open after all of this?
- Questions asked
When WinCC refuses a project with the message that the configured server is not running and tells you to check the computer name of the server, the fault is almost never a stopped server. The project folder carries the computer name of the station it was configured on, and the Project Manager will not start for a station whose name does not match. The fix is to remap the name in Computer properties with the local computer name option, clear any stale .lck lock files, and keep the .dcf files intact, because deleting them turns a simple name mismatch into a database-context failure that only the vendor reset script recovers.
What does the configured server message actually mean? #
The message means the project was last configured for a computer name that does not match the station you are opening it on, so the Project Manager refuses to start until the stored name resolves to this station. In WinCC, the station that owns the project database is called the server even when the project runs standalone, so the message is about that ownership name, not about a multi-server architecture.
The check runs at project open, before activation, before runtime start and before any version conversion. That is why a project created on one computer and copied to another shows it immediately, including a project made with V7.5 and opened with V8.0: the version step is not the trigger, the name is. The practical consequences while the mismatch stands:
- No activation and no runtime start from that station.
- No configuration changes can be saved.
- The message repeats on every open until the name is remapped.
How do you remap the server name in Computer properties? #
Open the project in the Project Manager, open the properties of the computer listed in the project, and when the stored computer name differs from yours select the option to use the local computer name, then close and reopen the project. The project loads even with the mismatch, which is what makes this the clean fix:
- Start the WinCC Project Manager and open the project as it is.
- In the project tree, right-click the computer object and open its properties.
- Compare the computer name shown there with your station's name in the Windows system settings.
- Select the option to use the local computer name.
- Close the project completely and open it again, then activate and start runtime.
Once the name matches, an older project on the new station behaves like any migration: you can run a WinCC 7.0 project on another PC without a new build as long as the installed WinCC version supports opening it.
Should you delete the .dcf files? #
No, deleting the .dcf files from the project folder does not clear the stale name; it removes the database link, and the next open fails with the message that the database context does not exist or is invalid. That failure is worse than the one you started with, because it no longer mentions a name you can remap and it forces the reset script described two sections down.
The .dcf files carry the server-name binding for the project. The supported remap is the local computer name option in Computer properties; the files themselves are not a documented editing surface, so neither delete nor hand-edit them. If someone already deleted them, go straight to the reset procedure and restart.
When do you run Reset_WinCC.vbs? #
Run Reset_WinCC.vbs, located in the WinCC\bin folder of the installation, when the message has changed to the database context error or when SQL Server holds database segments attached under the old computer name, then restart the computer. The script detaches the WinCC SQL database segments and clears the WinCC registration so the Project Manager rebuilds the database context at the next open.
- Close the Project Manager and runtime, and take a full copy of the project folder, because the reset rebuilds the database context and the copy is your way back.
- Open a command prompt with administrator rights and change to the
WinCC\bindirectory of your installation. - Run
Reset_WinCC.vbsand confirm the prompts to detach the databases and clear the registration. - Restart the computer.
- Reopen the project; the Project Manager recreates the database context automatically.
This procedure is for the PC Project Manager. If the invalid-database message appears on an HMI panel at boot rather than here, follow the separate fix for an HMI stuck on invalid database at boot instead, because a panel has no SQL instance to reset.
Which .lck files are safe to delete? #
Files with the .lck extension in the project folder are lock files left behind by a crashed or aborted session, and you can delete them once the Project Manager, runtime and every other WinCC process are fully closed. They block a clean open and are harmless to remove at that point; they are also unrelated to the name mismatch, so deleting them is housekeeping, not the fix.
- Close the Project Manager and runtime.
- Check Task Manager for any remaining WinCC processes and end them.
- Delete every
.lckfile in the project folder. - Reopen the project and continue with the name remap if the message persists.
Leave everything else alone: the .dcf files, the database files and the project package files are all needed for the open.
What computer name rules does WinCC enforce? #
The station's computer name must be at most 15 characters long, plain ASCII, and free of underscores when DNS host names are used, so an over-long or decorated name fails the server check before WinCC even looks at the project. The documented rules for WinCC stations:
- Maximum length of 15 characters, the NetBIOS limit that Windows enforces on the station name.
- Letters and digits, with hyphens allowed; no underscore if DNS host names are used.
- No special or non-ASCII characters such as umlauts.
- The local name must resolve to the station itself, so a name-based check on that station reaches it.
Worked example, counting characters: the name WS-PROD-3 is W, S, hyphen, P, R, O, D, hyphen, 3, which is 9 characters, all ASCII, so it passes. The name WINCCSERVERSTATION01 is 5 letters in WINCC, plus 6 in SERVER, plus 7 in STATION, plus 2 digits, which is 20 characters, so it fails the length rule and must be renamed. After renaming the station, restart it and remap the project's stored name with the local computer name option, because the stored name is now stale again.
Is your Windows user in the SIMATIC HMI group? #
The Windows account you open the project with must be a member of the local SIMATIC HMI group, because that group carries the SQL Server permissions the project database needs, and a missing membership produces connection errors after the name is fixed. Check it before blaming the project:
- Open Computer Management and go to Local Users and Groups.
- Find the SIMATIC HMI group and confirm your account is a member.
- Add the account if it is missing, then log off and on again.
This does not cause the server-name message itself, but it is the next wall you hit, so clear it in the same pass.
What if the project still will not open after all of this? #
If the name remap, the lock files, the group membership and the reset script have all been through and the project still refuses, the project itself is likely damaged, and the remaining documented recovery is a support request with the vendor rather than further manual work on project files. One more trap sits nearby: projects must be renamed only in the SIMATIC Manager or with the Project Duplicator, because a project renamed in Windows Explorer can no longer be opened.
The decision for each case:
- Project copied from another computer: open it, set Computer properties to use the local computer name, close and reopen. Done.
.dcffiles already deleted: back up the folder, runReset_WinCC.vbsfromWinCC\bin, restart, reopen.- Station name over the character limit or containing special characters: rename the station to a compliant ASCII name, restart, then remap.
- Everything tried and still failing: stop editing files and raise the vendor support request, with the full folder backup attached to the case.
Questions asked
Does the step from WinCC V7.5 to V8.0 cause this message?
No. The server-name check runs before any version conversion, so the message would appear on any mismatched station regardless of version. Once the name is remapped the project opens and is converted at first open; keep an untouched copy of the original folder, because the conversion rewrites the project for the newer version.
Does Reset_WinCC.vbs delete project data?
No. The project folder itself is not deleted, and a full folder copy taken beforehand is your way back if the rebuilt context misbehaves.
Can you edit the .dcf file instead of using Computer properties?
Don't. The supported remap is the local computer name option in the project's Computer properties. The .dcf files are not a documented editing surface, and a hand edit carries the same risk as deletion: the database context error that forces the reset script and a restart.
Why does the message say server when only one computer is involved?
In WinCC, the station that owns the project database is called the server even in a single-station setup, with no separate runtime clients. The message is about that ownership name, not about a multi-server architecture, so a standalone project shows it as readily as a distributed one.