Why WinCC Unified Normal alarm rows stay bright white

HMI and touchscreens Published 6 min read By IMDTouch engineering team

Short answer

The WinCC Unified alarm class editor offers background colors for Incoming, Incoming/Outgoing, Incoming/Outgoing/Acknowledged and Incoming/Acknowledged/Outgoing only; the Normal state has a status text but no color property, so cleared rows in a logged alarm view stay bright white, and Alarm State filters were reported ineffective at V20 Update 4. If operators may acknowledge alarms, move the class to acknowledgement; otherwise keep the logged view off the night screen and file the requirement with Siemens support.

On this page
  1. The four states that have a color property
  2. Why the outgoing row shows the Normal text
  3. Why only the logged page turns white
  4. What you can still adjust
  5. Counting the white rows on an MTP1000 logged alarm page
  6. Version status of the missing property
  7. The decision for each alarm class type
  8. Questions asked

Nothing is missing from your project: the WinCC Unified alarm class editor exposes a background color for four states only — Incoming and the three acknowledged combinations — while Normal, the state an alarm takes when it clears without acknowledgement, has no color property at all. Outgoing rows in a logged alarm view therefore stay bright white, reported unchanged from V18 Update 3 through V20 Update 4, filters included. What follows shows why the state model produces those rows, what remains adjustable, and the two decisions that remove the glare without losing the record: move the class to acknowledgement, or keep the logged view off the night screen.

The four states that have a color property #

The reference is the product documentation: in the alarm class editor, the Inspector window carries the class colors under Properties > Colors, where you change the default background color, the text color and the flashing settings. The state lines offered there number four: Incoming, Incoming/Outgoing, Incoming/Outgoing/Acknowledged and Incoming/Acknowledged/Outgoing. Normal has no line at all — it is the state the documentation defines as the condition of an alarm no longer fulfilled, and which reports also call 'removed'. The editor has looked this way from V18 through V20.

Alarm state Background color in the class editor Row at runtime
Incoming Configurable under Properties > Colors Takes the configured color
Incoming/Outgoing Configurable Takes the configured color
Incoming/Outgoing/Acknowledged Configurable Takes the configured color
Incoming/Acknowledged/Outgoing Configurable Takes the configured color
Normal (removed) No property exposed Bright white, not changeable

That table answers the question directly: every state an acknowledged class can take has a color line, and the one state the unacknowledged class uses for outgoing has none.

Why the outgoing row shows the Normal text #

An Alarm class without acknowledgment runs two states: Incoming while the trigger bit is high, Normal once the bit drops. For this class type the outgoing event carries the Normal status text, not the Incoming/Outgoing text — the first sign that Normal is a real state here rather than an absent setting. The documentation keeps the two configurable pieces apart: alarm states reach the operator as status texts, which are configured in the runtime settings, while colors live in the class editor. You can therefore change what the white row says, but not what color it renders.

Why only the logged page turns white #

The reported project runs two alarm pages, and only the logged one turns white. The page for active and pending alarms shows alarms that are still present; its rows sit in the Incoming state, which is colored, so the dark scheme holds. The logged view exists to record state changes, so it keeps every outgoing event — the view doing its job — and that is where the uncolorable Normal rows accumulate. A cleared alarm that lingers in a view meant for active alarms is a different fault with its own cause, covered in why a WinCC Unified alarm row stays after it clears. Do not plan around filters either: at TIA Portal V20 Update 4 with current panel firmware, Alarm State != Normal and Alarm State = Incoming/Outgoing were both reported to leave the rows visible on the logged page.

What you can still adjust #

Three settings remain in your hands; none of them is the Normal row's background.

  • The state colors of the class, under Properties > Colors: set Incoming and the acknowledged-state colors to the dark scheme, so everything that can be dark is dark.
  • The Normal status text, in the runtime settings: word it so an operator reads the row as history, not as a pending alarm.
  • The alarm control's own colors, under Properties > Properties > Miscellaneous > Alarm control in the control's Inspector: these color the control, not individual state rows, so the Normal lines stay white over whatever you choose there.

Counting the white rows on an MTP1000 logged alarm page #

Inputs #

  • Panel and version: one MTP1000 running a WinCC Unified V18 Update 3 project — the reported configuration.
  • Alarm class: Alarm class without acknowledgment, so the class can take 2 states, Incoming and Normal.
  • Background-color properties the editor offers for those states: 1 — there is none for Normal.
  • Alarm pages in the project: 2 — one view for active and pending alarms, one logged view.
  • Rows that one occurred-and-cleared alarm writes to the log: 2 — every state change is logged, one incoming row plus one outgoing row.

Rule #

A logged row renders in a configured color only when its state has a color property; every other row renders the default bright white. A logged alarm view records one row per state change.

Arithmetic #

  • Colorable states the class uses: 1 of 2.
  • Uncolorable states the class uses: 2 - 1 = 1, which is Normal.
  • Rows written per cleared alarm: 1 incoming + 1 outgoing = 2.
  • White rows per cleared alarm: 1.
  • White share of a fully cleared history: 1 / 2 = 0.5, which is 50 %.

Result and decision #

The active/pending page never shows a Normal row, because a cleared alarm has already left it, so that page keeps the dark scheme. The logged page gains one white row per cleared alarm; once alarms have cleared, 50 % of its rows are bright white with no property to change them. From the first cleared alarm onward — one white row, then half of every completed alarm cycle — count the logged view as a bright area: it does not belong on a night-shift main screen. Keep the active/pending view there, open the log from a separate page, or remove the white rows from the design entirely with the class decision below.

Version status of the missing property #

The gap was reported at V18 Update 3 on an MTP1000, reviewed across V18 and V19 with the finding that the Normal color is not implemented, and reported again at V20 Update 4 with current panel firmware, where the filters changed nothing. Treat it as a product limitation, not a project error: in every released version through that update, no class property, runtime setting, control color or filter colors or hides a Normal row, and no documented workaround exists. The property can only arrive in a later TIA Portal version, so file the requirement through official Siemens support with enough detail for the white rows to be reproduced on the reported configuration.

The decision for each alarm class type #

Case A — the alarms may require acknowledgment: configure the class with acknowledgement. A clearing alarm then displays Incoming/Outgoing if it was never acknowledged, or Incoming/Acknowledged/Outgoing if the operator acknowledged before it cleared, and both states carry background-color properties, so every history row takes your dark colors and the white rows leave the design. The price is procedural: each alarm must be acknowledged, and an unacknowledged alarm stays listed until it is.

Case B — the alarms must stay unacknowledged: the Normal rows stay white through TIA Portal V20 Update 4, so fix the exposure, not the color. Put the active/pending view on the operator's main screen, move the logged view to a page that is opened deliberately rather than displayed through the night, and file the requirement with Siemens support so a later version can add the property.

One safety line for both cases: do not cure the glare by hiding the outgoing rows — in a class without acknowledgement they are the only record that an alarm came and went, so relocate the log page rather than empty it.

Questions asked

Why do classic Comfort panels and WinCC Professional not show these white rows?

Their alarm model has no Normal state for this transition: a discrete alarm whose trigger bit drops displays the Incoming/Outgoing status, and that state has a configurable color in both the classic Comfort panels and WinCC Professional. WinCC Unified introduced the Normal state, and the unacknowledged class is the one that lands its outgoing rows in it, without a color property.

My alarm rows show wrong contents, not wrong colors. Is that the same fault?

No. The WinCC Unified readme describes a separate defect: when an alarm text uses a text list whose entries point to a tag, the alarm view contents are not shown correctly in runtime. Check the alarm texts for that construct. It is unrelated to the missing Normal background color, and fixing it will not darken any row.

What should a Siemens support entry for the color requirement include?

The TIA Portal version with its update, the panel firmware version, the alarm class acknowledgement mode, whether the affected control is an active or a logged alarm view, the exact filter that failed, and screenshots of the state colors the class editor offers. Those details let support reproduce the white Normal rows instead of guessing at the configuration.

Can a runtime script recolor the Normal rows?

Not through anything documented. No scripting or control interface exposes a row-color property for alarm states, and none of the reported projects found a setting that does it. Plan the screens on the assumption that the colors in the class editor are the complete set, and spend the scripting effort elsewhere.

Keep reading

  • Troubleshooting

    Why a WinCC Unified alarm row stays after it clears

    A Program_Alarm row that survives its condition has left the incoming state but still waits for acknowledgment, or the alarm control is showing a history or unfiltered list instead of active alarms. Read the SIG tag online, then the row's state and acknowledgment columns. Fix it by acknowledging the outgoing row or filtering the alarm control to the active alarm list, and change the alarm class's acknowledgment requirement only when the process allows it.

    HMI and touchscreens

  • Troubleshooting

    How a Unified runtime script reads the selected alarm row

    WinCC Unified has no alarm-side Loop In. A script reads the selected alarm row either from SelectedRowData, delivered by the alarm display's OnSelectionChanged event and carrying values only for the columns that display shows, or through Alarm.GetSelectedAlarmAttributes(), available from Runtime V19, which takes the name of an alarm display on the current screen and returns the alarm's attributes whatever the column configuration shows.

    HMI and touchscreens

  • Troubleshooting

    Why PanelView 600 Plus Alarms Stay Blank and Configure Mode Crawls

    Blank alarms mean the alarm Trigger Type, whole-word trigger address and message value do not match the PLC bits — with Trigger Type on bit and the trigger on the whole word, the message value is the bit number plus 1. The close-to-five-minute Configure Mode exit is tag errors elsewhere in the application; deleting loaded runtime applications was tried and changed nothing. Re-map the alarms, clear every reported tag error, and both symptoms clear.

    HMI and touchscreens

How to Add an XY Plot to a WinCC Application