Troubleshooting
Why WinCC WebNavigator screens show exclamation marks daily
Short answer
Yellow exclamation marks on WebNavigator screens mean the tag-connected picture objects have no valid values; the mark does not say which component dropped them. When WinCC Runtime still shows the same values, isolate the web path: run a client on the server, then test whether recovery follows logging in to the server session rather than the publishing run.

On this page
Yellow exclamation marks on a WinCC WebNavigator screen mean the tags connected to those picture objects have no valid values at that moment, nothing more. In the reported case every screen on the shop floor opened marked each morning while WinCC Runtime on the server kept showing the same values, so the loss sits in the web path between Runtime and the browser clients, not in the tags. The strongest lead is the recovery behavior: starting Web Publisher seemed to fix the screens before publishing finished, which points at whatever happens when someone touches the server console, not at regenerated content. Prove Runtime, prove the server locally, then test the login action alone, in that order.
What the exclamation marks do and do not say #
A yellow exclamation mark on a tag-connected picture object, such as an I/O field, means the tag behind that object has no valid value at the moment the screen is drawn. That is the whole message. It does not tell you whether the value was lost in WinCC Runtime, in the WebNavigator server, in the web bridge, on the network or in the client session, and reading more into it is what sends this fault down the wrong path.
The marks are a different signal from the #### hash marks WinCC puts in a field when a value exists but does not fit its output format; that distinction is worked through in why a simulated HMI shows hash marks, not PLC values. Marks mean no value reached the object. Hash marks mean a value arrived and cannot be displayed.
The reported system behaved exactly as a web-path failure should: the pictures opened normally because the client browser draws them from cached graphics, while the tag updates never arrived, so every dynamic object sat marked. Runtime on the server kept showing the same values, which clears the tags and the process data path. The marks first appeared after an update to PCS 7 8.1, occasionally on a couple of screens, then daily on every screen, a timeline that says the update changed something, but nothing in the evidence names which component, so the isolation tests still have to find it.
One operational note: while screens are marked, treat each marked value as absent at that station, not as the last good number. On a process where operators act on those readings, that belongs in the shift instructions.
The Windows event tied to SCSAppPool/SCSWebBridge at the failure time is correlation evidence, nothing more; its text could not even be displayed in the reported case. Record its timestamp, line it up with the first client that went marked, and let the tests below decide whether it is cause or passenger.
Isolate the fault with three checks #
Work these in order while the failure is present. Each one cuts the remaining search space in half.
-
Prove Runtime. Open the same screens in WinCC Runtime on the server while the web clients show marks. Valid values there make this a web-only failure and end any argument about tags, archives or the process data path. It is the same layer split that decides why an HMI shows a black screen while the PLC keeps running: prove the healthy layer from its own display, then work only the failing one.
-
Run a client on the server itself. Open a WebNavigator client in a browser on the WebNavigator server machine and call one of the affected screens. If the local client marks too, the fault is server-side: the application pool, the web bridge or the logged-in session. If the local client updates while the remote ones mark, the fault is in the network path or the remote clients, and the server is cleared.
-
Check the server account's Windows session. Find the account the WebNavigator server runs under and look at whether it is logged in and whether its desktop sits locked at the welcome screen. A matching case puts the entire failure on this state: the marks appear when that account is not logged in or is locked, and recovery followed logging in rather than publishing. Treat it as the leading suspect and make the next occurrence confirm it.
Test one recovery action at a time #
The reported fix, starting Web Publisher, recovers the screens before the publishing run finishes. Regenerated pictures cannot be the mechanism when the screens already show values again before those pictures exist. What starting a publishing run does involve is a person at the server console, logged in, the same state the matching case names as the real repair. At the next occurrence, run the actions separately:
- Log in or unlock the server session without starting any publishing.
- Reopen several affected screens and check that the tag-connected objects show values again.
- Only if the marks persist, start the publisher and watch whether recovery still lands before the run finishes.
- Write down which action restored values and at what time, and line that time up with the SCSAppPool/SCSWebBridge event.
If recovery follows the login alone, the publisher was never the fix and you can stop scheduling it. If the screens stay marked until publishing starts, content regeneration genuinely matters and the investigation moves to the published pictures. On the reported evidence, expect the first branch.
What the overnight evidence rules out #
Disabling network-adapter energy saving held for exactly one night before the marks returned. A change that survives a single overnight idle has not been tested; idle nights come around every night, so give any change several consecutive ones before you credit it or drop it.
The continuous ping test reported no major overnight packet loss, and the failure still occurred. Worked example: an idle window from 22:00 to 06:00 is 8 x 3600 = 28,800 seconds, and at one probe every 2 seconds that is 28,800 / 2 = 14,400 probes. Every one of those probes can succeed while the web path is broken, because a ping exercises IP reachability only. It never opens a web session, requests a picture or transfers a tag value, so a clean ping log on a failure night is the expected result here, not a clearance.
The decision for each test result #
| Test result | Decision |
|---|---|
| Runtime shows marks too | Fix at the Runtime and tag layer first; the web path is downstream of a real data loss. |
| The local client on the server marks as well | Server-side failure. Check the server account's session first, then line up the SCSAppPool/SCSWebBridge event time; the client-connection troubleshooting list in the WinCC Information System covers the documented connection errors. |
| The local client updates, remote clients mark | Network path or remote clients. Re-test with a second remote client, check adapter power saving on both ends, and demand several clean idle nights before crediting any single change. |
| Values return on login or unlock alone | Session dependency confirmed. Stop scheduling the publisher and agree a permanent session arrangement with whoever owns server security. |
| Values return only once publishing runs | Content regeneration matters after all; move the investigation to the published pictures. |
On the reported evidence, Runtime healthy, pictures cached fine and recovery preceding the publishing run, expect this to land on the session row, confirmed by the next morning's failure.
Questions asked
Does a WebNavigator client reconnect by itself after the server comes back?
Only if the documented reconnect setting allows it. The WebNavigator documentation states that when the reconnect value is 0, the client makes no automatic reconnection attempts and outputs a message instead; a nonzero value enables automatic attempts. If your clients sit marked all morning until someone reopens the screen, check that reconnect setting before blaming anything else.
How long does a client take to notice the WebNavigator server went down?
Plan for more than 20 seconds. The release documentation notes that a WebNavigator client may take significantly longer than 20 seconds to recognize that the server is down or that communication is faulty. After you log in or unlock the server session, wait at least that long before judging the screens, and reopen more than one affected screen before you call the recovery confirmed.
Should the WebNavigator server account just be left logged in overnight?
One matching case runs exactly that and reports no recurrence, so it is a working fix rather than a guess. The tradeoff is an unlocked console session on a server. If site security rules that out, confirm the dependency first, meaning recovery on login alone with no publishing involved, then take that finding to whoever owns server security and agree a controlled way to keep the session available.


