WinCC Runtime Advanced shows hash marks and a recipe license warning

HMI and touchscreens Published 6 min read

Short answer

The recipe message and the hash-mark values are two independent faults. A correctly matched WinCC Recipes + Logging for Runtime Advanced key transferred to the IPC clears the license warning; the hash marks remain until the output field width and format fit the tag value or the acquisition fault is repaired. Fix them in that order.

On this page
  1. What the recipe message checks
  2. What the hash marks mean
  3. Fix order
  4. Acceptance checks
  5. Decision, case by case
  6. Questions asked

Two separate faults hide behind those startup symptoms. The message "License key not available - WinCC Recipes for Runtime Advanced" is a missing option key: the 512 PowerTags license covers process tags, not recipe functions, and the key that answers that message is SIMATIC WinCC Recipes + Logging for Runtime Advanced, article number 6AV2107-0HA00-0BH0. Transferred to the IPC with Automation License Manager and matched to the installed Runtime release, it clears the warning. The #### values are a second fault no license can touch: a numeric field prints hash marks when the value does not fit its configured output width and format, or when no valid value reaches the field. With the network already proven and 0000 showing for about one second before the switch to ####, the output field's width is the first suspect.

What the recipe message checks #

Runtime validates its licenses at startup against the Automation License Manager inventory of the machine it runs on: the IPC, not the engineering station. A project transfer that succeeded and a license that validated are separate results; one proves nothing about the other. The PowerTags base license counts the tags Runtime may exchange with the controllers, while recipes, logging and similar functions sit behind their own option keys. The message names the recipes option because the loaded project uses recipe objects, and a screen or function configured for recipes makes Runtime demand that key at every start.

Work three checks before any purchase:

  • Inventory. Read the local inventory of the IPC, not just the engineering PC. The base entry and the recipes option entry both have to be there.
  • Release match. The option key has to cover the installed Runtime release; the manufacturer's product listing for the article number states which releases each key covers.
  • Intent. If the recipe screens arrived with an inherited project and nobody uses them, deleting those objects removes the demand for the key entirely.

The logging option produces the same class of message, and Why WinCC Logging for Runtime Advanced asks for a license walks through that variant. Recipe handling also differs across platforms: configuring save and restore keys for Vijeo Designer recipes shows a panel platform that drives recipes through configured keys instead of a runtime option license.

Decision: if recipes are used, transfer the correctly matched option key to the IPC and the warning disappears; if they are not used, delete the unused recipe objects and the demand disappears with them.

What the hash marks mean #

#### is not an error code; it is the field giving up. A numeric I/O field renders the acquired tag value into the character width configured for it, and it prints #### when the rendered value does not fit that width or when the value available at that moment is not valid. Both causes produce the same placeholder, so the placeholder alone does not say which one you have.

The startup pattern narrows it. 0000 for about a second is the field's initial output, held before Runtime completes its first acquisition; when the first real value is evaluated, the field switches to ####. Four zeros need four characters and fit, and the process value evidently does not. On this IPC277G with the network verified, output width is the prime suspect and acquisition comes second.

Observation What it points to Next check
Recipe message at every RT Loader start Option key missing on the IPC or not covering the installed release Inventory and release match
Initial 0000, then #### Real value arrives but cannot render Count the characters the value needs
#### in some fields, others fine Field- or tag-specific fault Compare a failing and a working field on the same connection
#### even in a wide-format test field Acquisition or tag configuration fault Runtime system messages and an online PLC comparison

A placeholder standing in for a live value is a class of fault, not a WinCC peculiarity: PanelView Plus logic modules show question marks on live values when the path between panel and controller fails.

Worked example: counting the characters a value needs #

Take an illustrative tag that reads -1234.5 at one decimal place. The rendered value needs 1 character for the sign, 4 for the integer digits, 1 for the decimal point and 1 for the decimal digit: 1 + 4 + 1 + 1 = 7 characters. A field configured for 5 characters cannot render 7, so it prints ####. Set the output width to at least 7 characters and the decimal places to 1, and the same value renders completely. The sign and the decimal point each consume a character position, which is why a field that once displayed small positive values is the one that fails on larger or negative ones.

Fix order #

  1. Read the installed Runtime release from the IPC's software information and confirm the recipe functions in the project are intentional.
  2. Select the option key for that release: SIMATIC WinCC Recipes + Logging for Runtime Advanced, article number 6AV2107-0HA00-0BH0. The option is delivered as a download without software media, so installation is the key transfer itself.
  3. Transfer the key into the IPC's Automation License Manager inventory. If the key sits on a USB stick or another station, Transfer a WinCC license from USB key to hard disk covers the move step by step.
  4. Restart the RT Loader in a maintenance window with the machine stopped: the operators lose the visualization for the seconds the runtime needs to reload.
  5. Confirm the license message is gone at startup. Then count the characters the worst-case value needs, sign, digits, decimal point and decimals together, and set the output width and decimal places of the failing fields accordingly.
  6. If hash marks remain at a sufficient width, treat it as acquisition: read Runtime system messages for read faults on that connection, because a reachable network is not a read. Compare the tag against the PLC value online, and bind a temporary wide-format test field to the same tag. If the test field renders and the original does not, repair the original field's configuration; if both fail, work through Diagnosing HMI values across driver, tag and screen.

Acceptance checks #

  • Startup: the RT Loader comes up with no recipe license message, and the IPC inventory lists the base entry and the option entry. A visible entry alone is not the test; the absent message is.
  • Display: the failing fields hold real values past the first second, with no switch from 0000 to ####.
  • Agreement: compare displayed values against PLC online values at several points, including one negative value and one with decimals; agreement at those points is the display test.
  • Records: write the Runtime release and the option key version into the project documentation so the next migration does not rediscover this.

Decision, case by case #

  • Recipe warning: the WinCC Recipes + Logging for Runtime Advanced key resolves it when its release covers the installed Runtime and the key sits on the IPC. Confirm the message is absent after restart.
  • Hash marks: no license fixes them. If the widest value the tag can hold needs more characters than the field has, widen the field and correct the decimal places, and the fault is closed. If the width already suffices, the fault is in tag acquisition or configuration; a wider field does not repair an inaccessible address, and an option license does not repair a numeric format.

Questions asked

Does the 512 PowerTags license include recipes?

No. A PowerTags license counts the process tags Runtime may exchange with the controllers, and 512 is that ceiling for this key. Recipes, logging and similar functions are unlocked by separate option keys, so both entries have to appear in the Automation License Manager inventory of the IPC. A full tag entitlement with a missing option still stops at the recipe message at every start.

Where must the recipe option key be stored?

On the IPC that runs the project, not on the engineering station. Automation License Manager keeps one inventory per machine, so a key held on the programming PC does nothing for a panel on the network. Check the local inventory of the IPC before ordering, and move the key to that machine if it currently sits elsewhere.

Does the recipes option require a software installation?

No. WinCC Recipes + Logging for Runtime Advanced is delivered as a download without software media or printed documentation, so installation is the key transfer into Automation License Manager plus a Runtime restart. The recipe functions are part of the Runtime already installed on the IPC; the key only unlocks them.

Can a field show hash marks while the network is healthy?

Yes, and that is the common case behind the startup pattern in this article. The placeholder appears when the acquired value does not fit the field's character width or format, or when the value available at that instant is not valid. A working network only proves that a value can arrive; the field still has to be able to render it.

What happens if the option key does not match the installed Runtime release?

The inventory shows the key while Runtime still refuses it for the loaded project. Read the installed Runtime version from the IPC's software information and select the key issued for that release before ordering; the manufacturer's product listing for the article number states which releases each key covers.

Keep reading

  • How-to

    Run a TIA Portal V14 HMI on WinCC Runtime Advanced

    Compile the HMI for its configured WinCC RT Advanced target, transfer the compiled application, and select it in RT Loader. Match the configured device version to the runtime installed on the workstation. Verify Windows support and use a valid runtime license sized for the application.

    HMI and touchscreens

  • How-to

    Fixing a WinCC PC station download comms error from TIA Portal V13

    When TIA Portal V13 compiles but the download to a WinCC PC station fails, the transfer channel to the runtime loader is broken while the HMI itself is healthy. Compile to file, copy the .hmi PData file to the path shown in the WinCC Runtime Loader settings, restart runtime from the loader, then align the firewall, channel settings and PC station IP to restore normal downloads.

    HMI and touchscreens

  • Troubleshooting

    Why a WinCC Advanced SQL Read Script Returns Nothing

    The read script fails for faults the working INSERT never meets: a missing space turns SELECT * FROM into FROMKayitlar, a dangling ORDER BY has no column, and MoveFirst after MoveNext pins the cursor on row one. Clear them in order: DSN visible to the runtime, SQL text valid, recordset non-empty, value inside the DInt range. Each fault masks the next.

    HMI and touchscreens