Moving a TP1500 Comfort project to WinCC Runtime Advanced

HMI and touchscreens Published 5 min read

Short answer

Yes: retarget the TP1500 project to WinCC Runtime Advanced V14 and run it on a Windows panel PC. The Professional engineering edition does not force Runtime Professional. Size the runtime license by counted PowerTags — the 2048 class for the worked example here — add licenses for recipes or logging, then fix scripts and storage paths before commissioning.

On this page
  1. Engineering edition does not choose the runtime family
  2. Retarget the TP1500 project
  3. Size the runtime license by PowerTags
  4. Recipes and logging need their own licenses
  5. Fix scripts and storage paths
  6. Choose the panel PC and its area approval
  7. Confirm the license covers the V14 runtime
  8. Commission with a test that proves it
  9. Questions asked

Yes — the TP1500 application engineered in TIA Portal V14 Professional can run on a Windows panel PC with WinCC Runtime Advanced V14. The Professional edition on the engineering station does not force WinCC Runtime Professional on the target; engineering edition and runtime family are separate licensing decisions. The runtime license is sized by the project's counted PowerTags, recipes and logging need their own licenses, and the retarget itself is done with the documented device-change command. The steps below take you from the panel project to a commissioned runtime on the panel PC.

Engineering edition does not choose the runtime family #

Engineering software creates and compiles the application; runtime software executes it on the operator station. A TIA Portal Professional installation can configure and compile a Runtime Advanced target — nothing in the engineering license pushes you onto Runtime Professional. Choose the runtime family from what the application must do: a single-station HMI application with controller connections is Runtime Advanced territory; Runtime Professional is a different runtime product for multi-station and larger architectures.

The runtime-side deployment is the same path described for engineers who run a TIA Portal V14 HMI on WinCC Runtime Advanced; this article covers retargeting the existing panel project itself.

Retarget the TP1500 project #

Changing the target is an engineering change, not a file copy. Do it on a working copy so the original panel application stays recoverable:

  1. Archive the original project and create a separate migration copy. Never retarget the only copy.
  2. In TIA Portal V14, double-click "Devices & Networks" in the project tree to open the device view.
  3. Select the TP1500 in the device view, right-click it and choose "Change Device/Version" from the shortcut menu.
  4. In the "Change Device" dialog, select the PC station with WinCC Runtime Advanced V14 as the new device.
  5. Compile the retargeted application. Zero errors is the requirement; every warning gets a disposition — fixed, or documented as acceptable with a reason.

Screens, tags and controller connections carry over in principle, but the compile report tells you what did not survive: device-specific functions, script calls and storage references written for the panel's file system. Expect to edit those before the first download.

Size the runtime license by PowerTags #

A PowerTag is an external process tag with a controller connection, and the runtime license counts exactly those — not screens, not internal variables. License classes run from 128 PowerTags up to the range documented for your release, with 8192 as the largest class in the current licensing tables. Read the counted value from the compiled project's license information after retargeting, because conversion can change tag use.

Worked example, with illustrative numbers: the compiled retargeted project reports 1540 PowerTags. You need a class at or above that count. The 2048 class covers it with 2048 − 1540 = 508 PowerTags of headroom, about a third of the license — enough for the tag additions a modernization usually brings. A smaller class would fail licensing at runtime.

Decision for this case: order the 2048 PowerTag class, and write the calculated requirement (1540, measured at compile) next to that choice in the project documentation. If a later expansion pushes the count past 2048, the next class up is the answer, not a workaround.

Recipes and logging need their own licenses #

If the application uses recipes or logs process or alarm data on Runtime Advanced, those functions require additional licenses beyond the PowerTag class. The logging case is covered in why WinCC Logging for Runtime Advanced asks for a license.

Audit the converted project before ordering: open the recipe view and each configured log in the project tree and note whether they are actually used. Every function in use becomes a line on the license order. A recipe or log that is configured but never used is better deleted in the migration copy than licensed for nothing.

Fix scripts and storage paths #

The panel's file layout and execution environment differ from a Windows PC's, and this is where migrated applications typically fault. Work through these checks:

  1. Find every script that writes or reads files, and replace panel storage-card paths with valid Windows paths on the panel PC.
  2. Recompile and confirm that no script references a panel-only system function; replace or remove the ones that do.
  3. On the panel PC, run each file-writing script once and verify the file appears where the application expects it.
  4. Test every operator input field, since entry behavior and screen navigation can shift with the new display and touch hardware.

Choose the panel PC and its area approval #

Where the TP1500 must physically leave the machine — a station relocated into a hazardous zone that no Comfort panel is approved for is the classic reason — the replacement is an industrial panel PC running the runtime. Verify separately that the panel PC's installed Windows version is on the supported list for Runtime Advanced V14; a computer that runs Windows is not automatically a supported runtime host.

One safety note: the software choice confers no hazardous-area approval. The approval comes from the panel PC's certificate for the exact supplied configuration — enclosure, cable entries, peripherals and installation conditions — and the station is only installed in the zone when that certificate covers the arrangement as built.

Confirm the license covers the V14 runtime #

License version and runtime version are distinct, and whether a newer license key activates an older runtime depends on the supplier's key-validity table for that exact product. Decision: order a license documented as valid for Runtime Advanced V14. If the supplier offers only a newer license, get written confirmation that its key activates a V14 runtime before you buy — do not build the project plan on the assumption that it will.

Commission with a test that proves it #

  1. Install the runtime package and the license on the panel PC.
  2. Download the compiled application from TIA Portal V14.
  3. Start the runtime and confirm it launches with no license warning; a warning means the class or the version coverage is wrong, so stop and fix the license.
  4. Open the runtime's license information and confirm the compiled PowerTag count sits within the licensed class.
  5. Walk every screen, exercise the controller connections, and run the recipe and logging functions once each with test data.

When the runtime starts clean, the tag count is inside the class and the write tests pass, the migration is done — and the archived TP1500 copy stays on the shelf as the rollback.

Questions asked

Do internal variables count toward the PowerTag license?

No. Internal variables have no controller address and are not counted for the license, but they have their own runtime limits: depending on the release, 2048 or 4096 internal variables, 1600 elements per array and 999 structures. The compiled project must stay within those limits even though they do not change the license class.

Can the retargeted project still be loaded back onto the TP1500?

Not from the same copy. Once a device is changed to the PC runtime, that copy no longer generates for the panel. Keep two project copies: the archived original, which still targets the TP1500 for rollback, and the retargeted working copy for the panel PC.

Does Runtime Advanced need separate engineering software?

No. The same TIA Portal V14 installation that engineered the Comfort panel configures the Runtime Advanced target and compiles the application for it. The runtime package on the panel PC only executes the compiled application; engineering, compilation and download all happen from TIA Portal.

Keep reading

  • How-to

    Replacing an MP277 Touch Panel with a Panel PC

    A Panel PC 677 can replace an MP277, but as a migration, not a swap: retarget a copy of the project with WinCC flexible Advanced (a Powerpack upgrades an existing Standard license), then buy a PC Runtime license sized to the project's PowerTag count. The engineering license on the development PC does not authorize Runtime on the Panel PC.

    HMI and touchscreens

  • How-to

    Migrating a WinCC PC Runtime project to a Comfort panel

    There is no whole-project conversion from a WinCC PC runtime station to a TP1500 Comfort panel. Copying screens inside TIA Portal is supported, but each object, faceplate and system function must be dispositioned and reconfigured for the Comfort system. Advanced sources transfer with the least rework, Professional sources need object-by-object reconciliation, and a Unified source should move to a Unified Comfort panel instead of being converted.

    HMI and touchscreens

  • Troubleshooting

    WinCC Unified project will not open with a Comfort or Advanced license

    A WinCC Comfort or Advanced engineering license can cover WinCC Unified engineering from TIA Portal V16, but installing the classic WinCC tools does not install the Unified editor. During setup you must tick WinCC Unified Engineering in the installation scope yourself. Add that component first; only then look at the license.

    HMI and touchscreens