Removing the Green Focus Box Around a FactoryTalk View Numeric Input

HMI and touchscreens Published 6 min read

Short answer

The green box around a FactoryTalk View numeric enable input is the display's focus highlight, not an object fault. Open Display Settings for the containing display, select the Behavior tab, and check Disable Highlight When Object has Focus, then rebuild the runtime. Confirmed in FactoryTalk View Studio 6.1.

On this page
  1. What is the green box around my numeric input?
  2. Why does the box appear only after I select the input?
  3. Why doesn't editing the numeric input remove the box?
  4. Where is the setting that turns the green box off?
  5. How do I disable the highlight step by step?
  6. Should I disable the highlight on a touch-only panel?
  7. Does one change fix every screen in the application?
  8. How do I verify the fix at runtime?
  9. Questions asked

The green box that appears around a FactoryTalk View numeric enable input on a PanelView is the display's focus highlight: the runtime outlines whichever object currently holds input focus. Numeric entry is not broken, and nothing inside the object draws that outline. The fix is one checkbox in the settings of the display that contains the object — Display Settings..., Behavior tab, Disable Highlight When Object has Focus — a path confirmed working in FactoryTalk View Studio 6.1. Below: how to prove the box is the focus cue, why object-level fixes miss it, when to keep the highlight, and how to verify the result on the terminal.

What is the green box around my numeric input? #

The green box is the display's focus highlight: FactoryTalk View draws it around whichever object currently has input focus, so a numeric enable input that works correctly is not faulty, and the fix lives in the display, not the object.

Interactive objects on a FactoryTalk View display can receive input focus. The runtime marks the focused object so an operator working from a keyboard can see where the next keystroke will go. On a touch terminal the same indication reads as an unwanted graphic, but it is a display behavior, not an object fault.

The deciding observation takes one selection: touch the numeric enable input and watch the box appear, then move focus to another focusable object on the same display. If the outline follows the focus, you are looking at the focus highlight; if the value still enters correctly, the input object itself is healthy.

Why does the box appear only after I select the input? #

The box appears on selection because focus follows selection: touching the input gives it keyboard focus, the runtime marks where the next keystroke will land, and the mark moves away when another object takes focus.

The highlight exists for keyboard workflows. Pressing TAB moves focus between interactive objects, and the outline shows which one receives typed input. Touch selection gives the touched object focus directly, so on a touch panel the outline adds no information an operator uses — it only occupies space around the field. That is why the symptom reads as a fault on small screens: the cue was designed for a navigation method the panel does not use.

Why doesn't editing the numeric input remove the box? #

No object-level setting controls it: the numeric input's border, fill, font and numeric-entry configuration all work normally, which is why rebuilding, resizing or restyling the object leaves the same green outline in place.

Four common dead ends all fail for the same reason — they target the object while the highlight belongs to the display:

  • Rebuilding the numeric input. The replacement receives focus too, and the same display behavior outlines it.
  • Changing the object's border, fill or font. The highlight is drawn outside the object's normal appearance properties.
  • Resizing the object to push the outline off-screen. This shrinks the touch target and still leaves the behavior enabled.
  • Tracing tags, scaling or entry limits. Those govern data handling; if the displayed value and the entry work, they are not the fault.

One case does not fit this pattern: a green rectangle visible the moment the display opens, before anything is selected, is not the focus highlight. Look for a drawn rectangle, an object border or an alarm-state animation in the display's graphics instead.

Where is the setting that turns the green box off? #

The checkbox is in the containing display's settings: right-click the display background, choose Display Settings..., open the Behavior tab, and check Disable Highlight When Object has Focus, a path confirmed in FactoryTalk View Studio 6.1.

Right-click the empty area of the screen, not the numeric input object — staying inside the object's properties is the most common reason the option is never found. The setting belongs to the display that contains the object, and it suppresses the highlight without removing the object, changing its value, altering its linked data, or preventing it from receiving focus. For the same fix walked through on PanelView Plus numeric inputs, see disabling the PanelView Plus numeric input green focus border.

How do I disable the highlight step by step? #

Edit the display, not the object: open the application in FactoryTalk View Studio, change one checkbox on the Behavior tab of the display that shows the box, save, and rebuild the runtime for the terminal.

  1. Open the application in FactoryTalk View Studio, working on a controlled copy of the project.
  2. Open the display that shows the green box.
  3. Right-click the display background and choose Display Settings...
  4. Open the Behavior tab.
  5. Check Disable Highlight When Object has Focus.
  6. Accept the settings and save the display.
  7. Build the runtime and download it to the terminal through your normal transfer workflow.

Record which displays you edited: the checkbox belongs to each display individually, so the edit list doubles as the verification list.

Should I disable the highlight on a touch-only panel? #

On a touch-only panel, disable it: the highlight earns its space only when a keyboard and the TAB key are part of the operator's routine, and a small touch screen pays twice for a cue nobody uses.

Decide by how the station is actually operated:

  • Touch-only station: disable the highlight. Nothing on the panel uses the cue, and the outline only consumes screen space around the input.
  • Station with a physical keyboard: keep the highlight if operators move between fields with TAB. It is the only indication of which field receives the next keystroke, and a keystroke landing in an unmarked field is the one hazard this setting can create.

On terminals where value entry runs through the touch keyboard rather than a physical one, the highlight tells the operator nothing; when that keyboard fails to open from scripted input dialogs, treat it as its own fault and start with fixing a missing on-screen keyboard from scripted input dialogs.

Does one change fix every screen in the application? #

No, the setting belongs to each display, so the number of edits equals the number of displays that show the box, and no single project-wide switch exists for the highlight.

Worked example: take an application with 24 displays in which the box appears on 6 of them. The job is 6 edits, because 24 displays − 18 unaffected displays = 6 displays to change. Each edit is the same checkbox on that display's Behavior tab, and after the edits only those 6 displays need runtime verification. Plan that list before you start, because there is no action that clears the highlight everywhere at once.

How do I verify the fix at runtime? #

Test on the runtime terminal: select the input the same way the operator does, confirm the green outline no longer appears, then enter a permitted value and confirm it reaches the application.

  • Open the edited display on the terminal, not only in the editor, and select the numeric enable input exactly as the operator does; the green outline should no longer appear.
  • Enter a permitted value and complete the normal acceptance action; confirm the displayed value updates and the application receives the number.
  • Select the other interactive objects on the display and confirm the operating sequence still reads clearly without the cue.
  • If a keyboard is installed, traverse the display with TAB and confirm operators can still identify the active field.

If the box survives the edit, first confirm the terminal is running the runtime you rebuilt: checking which runtime file an HMI terminal actually loads rules out a stale download before you reopen the project.

Questions asked

Does turning off the focus highlight stop the numeric input from writing values?

No. The checkbox hides only the visual cue. The numeric input still receives focus, still opens value entry, and still writes the same value to the same tag as before, so acceptance tests on writes and limits do not need to change after the edit.

Will the same checkbox remove a green rectangle that is visible before anything is selected?

No. The focus highlight only exists while an object holds focus. A rectangle that is visible the moment the display opens is a drawn graphic, an object border, or an alarm-state animation, and it needs the display's graphics and animations inspected instead of the Behavior tab.

Is Disable Highlight When Object has Focus set per display or per project?

Per display. Each display in the project carries its own Behavior tab, so a display that never shows the box keeps its current behavior and each affected display needs its own edit. Edit and verify them one at a time rather than assuming a project-wide setting exists.

Which FactoryTalk View Studio version has this checkbox?

The path was confirmed working in FactoryTalk View Studio 6.1, on the Behavior tab of the display's Display Settings. Availability in other versions is not documented here, so if the checkbox is absent, update the engineering tool to a revision that matches your terminal's runtime before looking elsewhere.

Keep reading

  • How-to

    Setting a Company Logo Screensaver on a PanelView Plus

    Use the terminal's built-in Windows CE screen saver when the firmware is between 3.20.08 and 5.10.xx: put a BMP logo on the terminal and point Terminal Settings → Display → Screen Saver at it. On any firmware, build the screensaver as a FactoryTalk View ME display driven by a controller idle timer, with a full-screen transparent pushbutton to dismiss it and a 0-100 backlight tag to dim it.

    HMI and touchscreens

  • Troubleshooting

    Why PanelView 600 Plus Alarms Stay Blank and Configure Mode Crawls

    Blank alarms mean the alarm Trigger Type, whole-word trigger address and message value do not match the PLC bits — with Trigger Type on bit and the trigger on the whole word, the message value is the bit number plus 1. The close-to-five-minute Configure Mode exit is tag errors elsewhere in the application; deleting loaded runtime applications was tried and changed nothing. Re-map the alarms, clear every reported tag error, and both symptoms clear.

    HMI and touchscreens

  • How-to

    Adding Flowmeter and Sensor Graphics to an EasyBuilder Pro Screen

    EasyBuilder Pro has no dedicated flowmeter or temperature-sensor object, and it does not need one. Put a picture from the Shape or Picture Library (or your own imported image) on the screen to identify the instrument, then add a separate numeric object bound to the device address for the live measurement — the picture never carries the data connection.

    HMI and touchscreens

Why a USB Joystick Cannot Drive PanelView Tags