IMDTouchKnowledge BaseShop main store

Comparison

Showing S7-1200 Data Live on PC, Tablet and Phone

HMI and touchscreens Published 8 min read

Short answer

Yes: one HMI/SCADA runtime with a documented S7-1200 driver, or an OPC UA client against the CPU's built-in server, acquires the data; every device then views it through the runtime's read-only web client delivered over a managed gateway. Verify CPU identity, firmware and license separately, budget display age as poll interval plus network delay plus client refresh, and keep the monthly archive in the runtime.

On this page
  1. Separate acquisition from viewing
  2. Three routes from the S7-1200 to the screen
  3. Verify CPU, firmware and license before buying
  4. Worked example: display-age budget for a wind-turbine monitor
  5. Build and prove the first screen
  6. Deliver the view to PC, tablet and phone
  7. Keep the monthly record, too
  8. The decision, case by case
  9. Questions asked

You can put live S7-1200 values on a PC, a tablet and a phone without exposing the PLC to the internet. One HMI/SCADA runtime reads the CPU — as an OPC UA client, or through a documented S7 driver — and every device opens that runtime's read-only web client. WinCC is one qualifying package, not the only one: what qualifies a package is its documented driver and firmware support, not the name on it. Treat the screen and the data path as separate deliverables. The CPU serves data, the runtime acquires and archives it, and the browser clients render only what the runtime has already collected. The comparison below covers the three ways to read the CPU, a worked display-age budget you can defend to the customer, and the decision for each case.

Separate acquisition from viewing #

A browser cannot poll a PLC by itself, and a screen that renders quickly can still show a value the runtime never acquired. Split the job into three layers:

  • The CPU serves data: the OPC UA server or the native communication interface, enabled and secured in the CPU configuration.
  • The runtime acquires: it polls the CPU on a set interval, checks quality, raises alarms and writes the archive that replaces the end-of-month register.
  • The clients render: PC browser, tablet and phone open the runtime's web client and can only show what the runtime has already collected.

Define real time as display age: the time between the CPU producing a value and the farthest device showing it. That is a number you can measure at commissioning, and the worked example below budgets it. A phone that is "always updated" is a phone whose display age stays under an agreed target, not a phone with a special line to the PLC.

Three routes from the S7-1200 to the screen #

Route How the CPU is read What you must verify Where it fits
OPC UA server in the CPU The runtime connects as an OPC UA client to the server inside the controller. Recent S7-1200 G2 CPUs provide this server for data access, and it ships deactivated by default, so enabling it is part of CPU configuration. That your CPU and firmware provide the server; that the client's security policy and certificates match the server settings; the CPU's connection-resource budget. Vendor-neutral monitoring with one acquisition path. The default for a new build.
Native S7 driver in the runtime The runtime speaks the CPU's own protocol through a documented driver. The driver's supported-device list against your exact CPU and firmware. AVEVA Plant SCADA's S7TCP driver, for example, added S7-1200 support in driver version 2.00.01 — the list decides, not the brand. Also the CPU protection setting that permits access from remote partners, if the driver reads through it. When the SCADA package you prefer documents your CPU and firmware. As valid as OPC UA when the list matches.
CPU web server with user-defined pages No runtime: the CPU's built-in web server serves HTML pages that read variables with AWP commands, and the browser talks straight to the controller. That your firmware supports user-defined pages; web-server authentication; connection resources, because every browser session draws on them. A small status page on the local network. No SCADA-grade alarms, trends or archives, and remote delivery is harder because the controller becomes the server.

Routes one and two feed a runtime that can serve browser clients, hold alarms and write history, so they carry the PC-tablet-phone requirement. Route three carries only a status page. WinCC fits route two when the edition you buy includes the runtime — a separate check from the engineering seat, as in does a WinCC Professional entry mean SCADA runtime is installed.

Verify CPU, firmware and license before buying #

  1. CPU identity and firmware. Read both from the project's hardware configuration or from online diagnostics; the family name S7-1200 is not enough. Firmware V4.5 and newer on the S7-1200 (V2.9 on related families) changed what older engineering tools and panels can negotiate, so check the published compatibility table for your pair — STEP 7 V15.1, for example, supports downloads to S7-1200 firmware V4.5.
  2. Driver or interface. Check the runtime's driver list, or its OPC UA client, against that CPU and firmware. Verify the engineering tool, the target model and the firmware separately from the PLC driver and the runtime license: a package can pass one check and fail the next.
  3. License and runtime build. The seat that draws screens is licensed separately from the runtime that serves them. Confirm the runtime license covers browser clients on the devices you plan to hand out, and that the runtime build on the visualization PC matches the project.
  4. Connection resources. The CPU serves each driver session, HMI panel and browser session from a finite pool. Count the sessions you are adding before a second client connects.

Worked example: display-age budget for a wind-turbine monitor #

Case: a small wind turbine controlled by an S7-1200. The customer wants current values on a phone and a PC, replacing a register read once at month end.

Inputs, each labeled as an example commissioning value:

  • Acceptance target: worst-case display age no more than 3 s — the example limit set with the customer for this class of process values, making "always updated" measurable.
  • Acquisition interval: 1 s — the example poll period for the value group, set in the driver's tag database.
  • Network round trip, runtime to CPU: 0.05 s — the example plant-LAN figure; measure your own before commissioning.
  • Web client update cadence: 1 s — the example subscription period of the runtime's browser client.

Rule, in words: worst-case display age equals the longest a changed value waits for the next poll (one full acquisition interval) plus the transfer into the runtime (the network round trip) plus the longest the runtime holds it before the next client update (one full client cadence).

Arithmetic: 1 s + 0.05 s + 1 s = 2.05 s worst-case display age.

For scale, the register it replaces can be up to 30 days old by the time it is read: 30 d × 24 h/d × 3,600 s/h = 2,592,000 s, and 2,592,000 s ÷ 2.05 s ≈ 1,264,000, so the live view is about 1.3 million times fresher than the end-of-month register it replaces.

Decision: with these inputs the design meets the 3 s target with roughly 0.95 s of margin, so this example configuration passes. Put a stale-data alarm at the 3 s limit so a frozen connection announces itself instead of quietly showing old numbers. If the customer demands less than 2.05 s, cut the acquisition interval first: polling at 0.5 s lowers the worst case to 1.55 s. Whatever you configure, verify by observation: watch a value change at a known moment in the CPU and timestamp when each device shows it. The measured difference, not the configuration screen, is the display age.

Build and prove the first screen #

  1. Back up the CPU project and record the current communication and protection settings before changing any of them.
  2. List the tags the customer actually needs: value, unit, range, how fast each can change, and whether it must stay read-only.
  3. Enable the acquisition path in the CPU configuration — OPC UA server or driver access — with its security settings, and note which connection resources the new session takes.
  4. Validate five to ten tags in the runtime's tag diagnostics: values, quality and update behavior, before drawing a single screen object.
  5. Bind screen objects only to validated tags, and show connection status and a stale-data flag on the screen itself.
  6. Configure the archive separately from the live view, and prove the end-of-month export still produces the old report before retiring the manual register.

Deliver the view to PC, tablet and phone #

The runtime publishes its web client, and each device opens it with a named, read-only user account. Keep that account read-only: a monitoring screen watches the machine and never commands it, and a browser dashboard is not a control station. The screen-mirroring pattern is worked through in making a read-only web client mirror of an HMI screen.

Remote devices must reach the runtime, never the controller. Put the runtime behind the plant's managed gateway or VPN and leave the CPU off the public internet. A site with no wired link — a turbine on a hill, for instance — gets online through a cellular router, as set out in connecting an HMI to the internet with a cellular router.

The PC that runs the runtime and shows the screens is itself plant hardware: an industrial panel PC at the machine rather than an office desktop in the basement.

Keep the monthly record, too #

The register the customer is used to becomes an export from the runtime's archive, not a manual reading. Configure archiving in the runtime or in a separate collector; when the history has to land in a plant database, put the collection in a gateway or historian instead of loading the operator screen — the reasoning is laid out in logging PLC data to SQL: use a gateway, not the HMI. Prove the archive's timestamps and totals on the bench before the changeover, so the first report after go-live looks like the ones before it.

The decision, case by case #

  • One machine, alarms and history wanted, PC plus tablet plus phone: route one or two into a runtime with a supported web client, delivered read-only through a managed gateway. That is the default answer.
  • A bare status page on the local network, no alarms or archives: the CPU web server with user-defined pages can carry it, accepting that the browser talks directly to the controller.
  • Several machines, one viewer: one runtime can collect from several CPUs when its documented drivers, ports and connection limits support the combination; the pattern of many collection points feeding one server is covered in monitoring many collection points from one monitoring server.
  • Which package: decide on the documented driver list, the firmware pair, the license and the web-client support. WinCC qualifies when those check out, and so does any other SCADA whose lists match. The name answers nothing.

Questions asked

Does the SCADA package have to be WinCC to read an S7-1200?

No. WinCC is one qualifying option. Any HMI or SCADA runtime qualifies when its documented driver supports your exact CPU and firmware, or when it can act as an OPC UA client against the server inside the CPU.

How fresh is real time on a browser screen?

Treat it as display age: the time between the CPU producing a value and the phone displaying it. It is the acquisition interval plus the network round trip plus the client update cadence, and it is measured, not assumed. A page that renders instantly can still display a value the runtime collected long before.

Can the phone connect directly to the PLC over the internet?

Keep the CPU off the public internet. Publish the runtime's read-only web client instead, and let remote devices reach it through a managed gateway or VPN that terminates away from the controller. Direct exposure invites connection attempts, port scans and write access to the machine, and a monitoring view never needs write access at all.

Is the S7-1200's built-in web server enough on its own?

For a small status page, yes: the built-in web server can serve user-defined pages that read variables with AWP commands, so the browser talks straight to the CPU. It provides no SCADA-grade alarms, trends or archives, each browser session draws on the CPU's connection resources, and secure remote delivery is harder because the controller itself becomes the server.

Which firmware works with which engineering tool?

Read the firmware from online diagnostics, then check the published compatibility table for your engineering tool version. S7-1200 firmware V4.5 and newer changed what older tools and panels negotiate, and older versions have documented limits. Verify the engineering tool, the CPU firmware and the runtime driver as three separate checks; passing one does not pass the others.

Keep reading

  • Troubleshooting

    Why a WinCC server IP change freezes all HMI clients

    Treat the synchronized freeze as a server-side fault with two leads: pin the process server to its fixed address instead of dynamic addressing, and find any add-on such as OPC software running on a demonstration license whose documented runtime limit matches the interval between freezes. Rebooting only resets the running session. Run the server without its SCADA software to rule the machine itself in or out.

    HMI and touchscreens

  • Explainer

    Why an S7-1200 runs out of HMI connection resources

    The V3.0 CPU 1214 in this case reserves six HMI connection resources and cannot be upgraded to V4.x firmware, which belongs to a different hardware generation. Six panels plus the two connections WinCC 7.2 runtime opens need eight resources, two more than the CPU has: audit the WinCC project for a duplicate connection, then either move a panel off the CPU or fit a V4.x-generation CPU with twelve reserved HMI connections.

    HMI and touchscreens

  • How-to

    Keeping WinCC on S7-1500 furnaces when a supplier pushes its own SCADA

    Keep WinCC as a written requirement in the purchase specification, with the edition, the license owner and the source-project deliverables named. Give the S7-1500 a symbolic interface over OPC UA so the SCADA stays replaceable without PUT/GET access. Accept a supplier-built platform only when it passes written documentation, reference and license checks.

    HMI and touchscreens