Upgrading WinCC Professional server client licenses to V16
Short answer
In a WinCC Professional V15.1 server/client system, the SIMATIC WinCC Server for Runtime Professional option is versionless and needs no upgrade. The RT Professional, 4096 Power-Tags V15.1 license and the Client for Runtime Professional V15.1 license are version-dependent, so each needs its own V16 upgrade entitlement covering V11..V15. The same split holds when moving on to V17.

On this page
- Which licenses does a WinCC Professional server/client system carry?
- Which of those licenses actually need a V16 upgrade?
- Which upgrade products convert V15.1 licenses to V16?
- How do you apply the upgrades without touching the Server option?
- How many upgrade licenses does a multi-client system need?
- Does the same split apply to WinCC Professional V17?
- What does a license upgrade not change?
- Questions asked
Upgrading a WinCC Professional V15.1 server/client system to V16 takes two new entitlements, not three. The SIMATIC WinCC Server for Runtime Professional option on the server is versionless: it carries no version suffix and keeps working unchanged. The two version-dependent licenses each need their own upgrade. On the server, SIMATIC WinCC RT Professional, 4096 Power-Tags V15.1 converts with SIMATIC WinCC RT Professional, 4096 Power-Tags V16, upgrade V11..V15 -> V16. On the client, SIMATIC WinCC Client for Runtime Professional V15.1 converts with SIMATIC WinCC Client for Runtime Prof V16 upgrade V11..V15 -> V16. V15.1 falls inside the V11..V15 range both upgrade products name, so both base licenses qualify. The same versionless-versus-version-dependent split decides a later move to V17.
Which licenses does a WinCC Professional server/client system carry? #
A V15.1 server/client system carries three separate entitlements: the versionless SIMATIC WinCC Server for Runtime Professional option on the server, the version-dependent SIMATIC WinCC RT Professional V15.1 runtime license on the server, and one SIMATIC WinCC Client for Runtime Professional V15.1 license on each client PC.
Each entitlement covers one job. The Server option licenses the server function. The RT Professional license licenses the runtime at a fixed Power-Tags capacity. The Client license licenses one client installation. The vendor's TIA Portal licensing documentation lists the client as its own product line for every version — WinCC Client for RT Professional V11.x, V15.x and V16.x appear as separate rows — which is why one client license cannot stretch across versions or across PCs. Installing V16 software changes none of these entries; an entitlement moves only when a license action moves it.
Which of those licenses actually need a V16 upgrade? #
Two of the three need upgrading: the RT Professional runtime license and the Client license are version-dependent, each valid for V15.1 and earlier TIA Portal versions, while the Server option carries no version suffix and keeps working through the conversion untouched.
Version dependence is read from the license name itself. The runtime and client entries name a version; the Server option names none. Version independence belongs to the Server option alone — it does not extend to every license installed on the same server.
| License as installed | PC | Version dependency | Action for V16 |
|---|---|---|---|
| SIMATIC WinCC Server for Runtime Professional | Server | versionless | keep it |
| SIMATIC WinCC RT Professional, 4096 Power-Tags V15.1 | Server | version-dependent | upgrade, same capacity |
| SIMATIC WinCC Client for Runtime Professional V15.1 | Client | version-dependent | upgrade |
Which upgrade products convert V15.1 licenses to V16? #
You order exactly two upgrade entitlements for a one-server, one-client system: SIMATIC WinCC RT Professional, 4096 Power-Tags V16, upgrade V11..V15 -> V16 and SIMATIC WinCC Client for Runtime Prof V16 upgrade V11..V15 -> V16.
The range notation V11..V15 and the installed designation V15.1 are different strings, but V15.1 is a V15 release and the vendor's published procedure applies precisely these two upgrades to V15.1 licenses, so V15.1 qualifies. Match each upgrade to its base license by product role, target version and capacity: the runtime upgrade must name 4096 Power-Tags, because an upgrade at a different capacity is a different product. An upgrade entitlement converts an eligible existing license; where no qualifying base license exists, the fix is a full license, not an upgrade. The WinCC V16 delivery release, support entry 109771219, gathers the order data for all of these items in one table.
How do you apply the upgrades without touching the Server option? #
Apply each upgrade through the Automation License Manager on the PC that holds the license, leave the Server option entry untouched, and verify afterwards that the runtime and client entries read V16 while the Server option entry is still present.
Do the conversion with the runtime stopped, so no operator station sits on a lapsed entitlement during production.
- Record the baseline inventory from the Automation License Manager on both PCs — the walkthrough on exporting SIMATIC ALM licenses via the command line shows how to pull that list in one step. Expect the versionless Server option and the V15.1 runtime entry on the server, and the V15.1 client entry on the client.
- Order the two V16 upgrade entitlements named above, one for each PC that holds a version-dependent license.
- Apply the runtime upgrade on the server. Expected result: the RT Professional entry reads V16 and keeps its Power-Tags capacity.
- Apply the client upgrade on the client PC. Expected result: the Client entry reads V16.
- Leave the Server option entry alone and compare the finished inventory against step 1: three entries present, two of them now V16.
Moving an existing key to different hardware is a transfer, not an upgrade; WinCC RT vs RC licenses and moving a runtime key covers how RT and RC entitlements differ and how a key moves between PCs.
How many upgrade licenses does a multi-client system need? #
Count one runtime upgrade per server and one client upgrade per client PC: a V15.1 system with one server and three client stations needs one RT Professional 4096 Power-Tags upgrade plus three Client upgrades, four entitlements in total.
The arithmetic is 1 + (3 × 1) = 4. Each client PC runs its own Client for Runtime Professional installation under its own license, so no single client upgrade covers the room. The tag-count capacity lives on the server's runtime license alone — the client product names no Power-Tags figure — so adding clients changes the number of client upgrades but not the runtime upgrade or its capacity. A fourth client added later is one more client upgrade, ordered at whatever source range covers that PC's installed client version.
Does the same split apply to WinCC Professional V17? #
Yes — the vendor confirmed in May 2022 that the procedure is unchanged for V17: the Server option stays versionless, and the version-dependent runtime and client licenses each take an upgrade entitlement whose range ends at V17.
Order the V17 items from the WinCC V17 delivery release, support entry 109795525, whose ordering table lists every license including the upgrades, and a trial license for evaluation — for example the WinCC Basic/Comfort/Advanced/Unified trial under order number 6AV2102-0AA07-0AA7 — sits alongside the permanent items; read the source range printed on each item against the version actually installed. The names follow the same pattern as the V16 upgrades — an entitlement that covers the installed version and targets V17. The original V15.1-to-V16 guidance dates from March 2021, and the licensing split behind it — versionless option, version-dependent runtime and client — held unchanged into V17.
What does a license upgrade not change? #
A license upgrade changes only the entitlement: it does not install the V16 software, migrate the project, or raise the licensed Power-Tags capacity, and the software move itself is a separate documented procedure.
The upgrade keeps the capacity it names — the tag count going in is the tag count coming out. A bigger tag count is a separate capacity purchase; runtime tag license tiers for an HMI panel PC explains how those tiers are sized. Updating the software before the entitlements can leave the runtime in demo mode; why an HMI runtime shows a demo mode message walks through that symptom. The software move itself follows the vendor's upgrade note for WinCC Professional and SQL Server, support entry 109745000, which shows an installed system upgrade starting with the uninstall of the existing TIA Portal components before the target version goes on. If the license manager rejects an upgrade, compare the base license's product, version and capacity with the range the upgrade names — that mismatch, not a communications fault, is the usual cause.
The decision, case by case: keep the Server option on every conversion; buy one runtime upgrade per server at the installed capacity; buy one client upgrade per client PC; when the finished inventory reads Server option plus V16 runtime plus V16 client, the system is fully licensed for V16 and the software and project migration can follow.
Questions asked
Where do I find the order data for WinCC Professional server and client licenses?
In the delivery release for your target version. The WinCC V17 delivery release is support entry 109795525 and contains an Excel file listing the order data for every WinCC license; the V16 equivalent is entry 109771219. In the vendor's online catalog the items sit under SIMATIC WinCC (TIA Portal) Options, then WinCC Server and WinCC Client, and under Runtime, then WinCC Runtime Professional.
Does converting the licenses also upgrade the WinCC Professional software?
No, and the two jobs must not be confused. The license upgrade changes entitlements only. The vendor's upgrade note for WinCC Professional and SQL Server, support entry 109745000, covers the software move and shows that upgrading an installed system — its example runs V18 to V19 — starts by uninstalling the existing TIA Portal components before the target version goes on.
Can I evaluate V16 while the upgrade entitlements are still on order?
The delivery releases list trial licenses for evaluation. The WinCC V17 ordering data includes a WinCC Basic/Comfort/Advanced/Unified trial license under order number 6AV2102-0AA07-0AA7, and a WinCC Professional V17 trial license appears alongside it. A trial covers evaluation only; production operation still needs the permanent entitlements converted to the target version.
How do I prove what was licensed before I started the upgrade?
The Automation License Manager on each PC. It lists every installed entitlement with product name and version: the Server option appears without a version suffix, while the RT Professional and Client entries carry V15.1. Export that list before ordering, then compare it after the conversion so the finished inventory shows the same three entries with two of them at V16.