Explainer
Which base adapter mounts a TP1500 Comfort PRO on a pedestal
Short answer
Mount the TP1500 Comfort PRO pedestal variant (expandable, flange bottom, order number 6AV2124-0QC24-1AX0) with the silver base adapter. That adapter is already in the delivery scope for PRO pedestal and support-arm variants, so the job is to verify the adapter-to-pedestal fit against the dimension drawings, not to order a second bracket.
On this page
You mount the TP1500 Comfort PRO pedestal variant — the expandable version with the flange at the bottom, order number 6AV2124-0QC24-1AX0 — on a silver base adapter, and that adapter is already in the box with the panel. The manufacturer includes it in the delivery scope for exactly two PRO configurations: support-arm mounting (not expandable, flange at the top) and pedestal mounting (expandable, flange at the bottom). Yours is the second. The ordering question is therefore closed before you open the accessories bag: no second bracket for the panel side. What remains is the check that decides whether the job succeeds — whether the adapter's pedestal interface matches the foot you are bolting it to — and you settle that against the dimension drawings before the first fastener goes in.
What the base adapter does #
The base adapter is the documented mechanical interface between a SIMATIC HMI PRO enclosure and its mounting: the adapter documentation states it is used to mount a PRO device on a support arm system or on a pedestal. The PRO devices are IP65-protected units built for that style of mounting rather than for a cabinet cut-out, so the adapter is not an optional convenience. It is the intended connection.
Two characteristics of the variant decide which mounting story applies. The flange position, top or bottom, tells you where the mounting connection meets the enclosure, and it differs between the support-arm and pedestal versions. Expandability tells you whether the foot accepts extension components. Both are written into the order number's variant description; for this panel it reads for supporting foot (expandable, flange at bottom).
Confirm the variant before touching the accessories #
The complete order number is the only reliable identifier. Display size and the words Comfort PRO appear on several variants with different flanges and different expandability, so they select nothing.
| Variant | Expandable | Flange position | Base adapter in delivery scope |
|---|---|---|---|
| Support arm | No | Top | Included |
| Pedestal (supporting foot) | Yes | Bottom | Included |
The inclusion applies to those two configurations only. Any other PRO variant follows its own delivery list, not the family name.
Run the identification as a check, not a glance. Say the crate on your bench shows 6AV2124-0QC24-1AX0 on the rating plate. The data sheet for that number describes a 15-inch widescreen TFT with 16 million colors and a housing width of 344.2 mm. Cross-check the two figures before measuring anything: a 15-inch diagonal at 16:9 has an active display width of 15 × 16 ÷ √(16² + 9²) = 240 ÷ 18.36 = 13.07 in, and 13.07 × 25.4 = 332 mm. The housing figure is about 12 mm wider, which is exactly the room a bezel and side walls take, so the numbers are consistent. Then put a tape on the housing: a reading near 344 mm says label and hardware agree, and the silver adapter in the accessories belongs to this panel. A reading tens of millimeters off means a different variant is in the crate — stop and re-identify before any adapter work.
What comes with the panel and what can be ordered separately #
For the pedestal variant, the silver base adapter is part of the delivery scope. It can also be ordered separately: the adapter documentation lists a silver base adapter under an article number beginning 6AV7674-1KA00. If you ever need the separate part, order by the complete number printed in that documentation — color alone is not a compatibility specification, and a silver adapter from a different system proves nothing.
The same manual documents the installation variants. The base adapter fits with or without a VESA adapter, so it can meet whatever interface your arm or pedestal hardware presents, and a flange mount adapter variant exists for other mounting styles; for a pedestal it is the base adapter. Four documents carry everything this decision needs: the mounting instructions for PRO devices, the PRO device dimension drawings, the SIMATIC HMI Quick Install Guide Comfort Panels PRO, and the adapter documentation with its variants, compatibilities, delivery scope and dimensions.
The pedestal side is the real compatibility check #
An included adapter settles the panel-to-adapter connection; it does not certify your pedestal. Compare the adapter's mounting geometry and fastening provisions with the pedestal drawing before assembly. If the hole pattern, spacing or fastener sizes do not agree, the answer is the manufacturer's documented pedestal and extension components for this expandable foot — not drilled holes, not spacers, not a bracket guessed from memory. Fastener sizes and tightening values come from the installation instructions; nothing in this job is estimated.
Decision rule: drawings agree, bolt the documented arrangement together. Drawings disagree, source the documented extension components for the expandable foot. There is no third case worth improvising.
Fitting sequence #
If the panel has been running and has to come off its foot for this work, protect the project first: the steps for a TP 1500 Comfort panel backup to a PC move the configuration off the device before anything is unbolted. Then:
- Read the rating plate and confirm the variant description matches the pedestal job: expandable, flange at the bottom.
- Inventory the accessories against the parts list in the Quick Install Guide and identify the silver base adapter.
- Offer the adapter to the enclosure's bottom flange, align it per the drawing, and install the documented fasteners at the documented tightening values, in the with-VESA or without-VESA arrangement your hardware needs.
- Support the enclosure through every step. A panel that powers up after assembly has proven its electrics, not its attachment.
- Bolt the adapter assembly to the pedestal foot per the foot's own drawing.
- Route the cable loom without tension on connectors or pinch points, and restore any sealing the work disturbed.
Missing adapter or mismatched parts #
An accessories bag without the silver adapter is a delivery-scope question, not a reason to buy a substitute bracket. Check the packaging and the delivery note first, then take it up with your supplier quoting the complete order number from the rating plate; the documentation identifies the part for this variant precisely.
If identification or measurement shows the panel itself has to be replaced rather than remounted, apply the same order-number discipline used to verify an obsolete HMI replacement before ordering. Reading the full identifier before money moves is the same habit in both jobs.
Questions asked
Do I have to buy a base adapter for the TP1500 Comfort PRO pedestal variant?
No. The silver base adapter is included in the delivery scope of this variant, so the panel-side mounting part is already with the panel. If it turns up missing, resolve that with your supplier against the complete order number on the rating plate. The adapter is also available separately; the adapter documentation lists it under an article number beginning 6AV7674-1KA00, and you order by that complete documented number, never by color.
Which PRO variants include the base adapter out of the box?
Two configurations only: the support-arm version, which is not expandable and has the flange at the top, and the pedestal version, which is expandable and has the flange at the bottom. Every other PRO configuration follows its own delivery list, so do not extend the rule by family name when you unpack a different variant.
How do I confirm a crate holds the pedestal variant before full unpacking?
Read the complete order number on the rating plate and cross-check it against the data sheet. The pedestal version is described as expandable with the flange at the bottom, its display is a 15-inch widescreen TFT, and the housing width is 344.2 mm. A quick tape check of the housing width confirms that label and hardware agree before any adapter work starts.
Does the included adapter guarantee a fit on my existing pedestal?
No. The adapter is the documented panel-side interface; the adapter-to-pedestal connection is a separate mechanical check. Compare the adapter's mounting geometry and fastening provisions with your pedestal drawing. If hole pattern, spacing or fastener sizes disagree, use the manufacturer's documented pedestal and extension components for this expandable foot instead of drilled holes, added spacers or improvised brackets.
Can the base adapter be mounted without a VESA adapter?
Yes. The adapter documentation covers installing the base adapter both with and without a VESA adapter, so it meets whatever interface your arm or pedestal hardware presents. The same manual covers a flange mount adapter variant for other mounting styles and gives the dimension drawings for both connections. Follow those drawings rather than mixing parts between the two adapter types.