Troubleshooting
Why a Comfort panel domain field rejects a long DNS name
Short answer
The domain entry in a Comfort panel's Network ID settings takes the domain's short NetBIOS authentication name, limited to 15 characters, not the full DNS name. Get the configured short name from the domain administrator, enter it in Control Panel → Network ID, and test share access separately. No domain rename and no server-side change are needed.

On this page
The domain entry in a Comfort panel's Network ID settings does not take the network's full DNS name. It takes the domain's short authentication name, the NetBIOS domain name that Windows-style logons use, and Microsoft limits that name to 15 characters. Your customer's DNS domain name is longer than that, so it can never fit, and no workaround on the server is required: get the configured short name from the domain administrator, enter that, and leave the customer's domain untouched.
The field takes the short authentication name #
The setup from Siemens Industry Online Support Entry ID 13336639 puts three entries in Control Panel → Network ID on the panel: username, password and domain name. That domain entry belongs to the credential the panel presents when it connects to the network share. It is not the destination: the server's name in the network path is configured elsewhere and stays as it is.
Two different identifiers describe one Active Directory domain. The DNS domain name identifies the namespace in DNS; Microsoft's naming conventions for Active Directory allow a fully qualified domain name of up to 64 characters. The NetBIOS domain name is the short logon identifier, capped at 15 characters by the same conventions. A credential dialog that expects the short name therefore has no room for a typical DNS name, and that is exactly the situation in front of you.
Do not abbreviate the DNS name yourself. Cutting characters or taking the first label produces a different, invalid identifier. The short name is configured in the directory and must be read from there. The controller-side half of this arrangement, why a domain controller's default-domain feature matters when a short name is presented at logon, is covered in why AD short-name logon needs the default domain feature.
Separate an entry limit from an access fault #
Before changing anything, establish which stage is failing. An input-length rejection happens on the panel before any network traffic; everything else happens after the panel has tried to authenticate. Work through these cases:
- The full domain name cannot be entered. The block is local to the credential configuration. Compare the DNS name against the domain's configured short authentication name and use the short one.
- The entries are accepted, but access is denied. The problem has moved to authentication or authorization on the server. Check the server's security event log and the effective file permissions for that account.
- The server or share cannot be reached. This is a connectivity or name-resolution fault, not a credential problem. If the panel also reports that its logon server is unreachable, the same isolation applies as in troubleshooting error 260028 when the Simatic Logon server is unreachable.
- The share opens, but the file cannot be read. Authentication succeeded; the exact file path, read permissions or the runtime's file operation are at fault.
Record exactly how the field behaves: does it stop accepting characters, truncate the value, or reject it when you save? Reopen the Network ID dialog after saving. A field that displays a shortened value but stores the full one is a display limitation; a field that stores the shortened value has changed your credential.
Worked example: compare the two names #
Take as an example a customer DNS domain name of production-line3.factorygroup.example. Count the characters: the first label has 16, the second has 12, the third has 7, and the two separating dots add 2, so 16 + 1 + 12 + 1 + 7 = 37 characters. That is more than double the NetBIOS limit of 15 characters, so this DNS name cannot be entered no matter how the dialog is approached.
The domain administrator confirms the domain's configured short name is PRODL3, 6 characters. Six is within the 15-character allowance, so the entry fits the field. The decision for this case: enter PRODL3 in the domain field of Network ID, keep the server's DNS name and the share path exactly as configured, and change nothing in the customer's directory. Note that the short name is not the first DNS label: production-line3 is neither the logon identifier nor a valid abbreviation of it.
Enter the short name and test in the right order #
- Record the current username, domain entry and destination path before touching anything, so the panel can be returned to its present state. Handle the password through your site's approved credential process; it does not belong in troubleshooting notes.
- Get the configured short domain name from the administrator, read from the domain's properties, not derived from the DNS name. Also confirm whether the file-reading account is a domain account or one local to the file server; a server-local account is not entered as though it belonged to the customer domain.
- Open Control Panel → Network ID and enter the username, password and the short domain name. Follow the panel's documented entry convention: prefixing the username with a domain while also filling the domain field can change how the identity is interpreted.
- Save, then reopen the dialog and compare the retained username and domain with what you intended. A masked password display proves storage only, never acceptance by the server.
- Run the same read operation against the same network path that the HMI application needs. If it fails, capture the displayed error together with the matching server-side event.
A successful test from a modern workstation proves the account and path in that workstation's environment only. The panel's own SMB protocol and authentication support is a separate compatibility check against the panel's documentation, and share permissions plus underlying file-system permissions must both allow the account to traverse to and read the file.
When the short name still will not fit #
If the administrator-confirmed short name, which by Microsoft's conventions cannot exceed 15 characters, is also refused by the field, the fault is no longer a naming mismatch. Record the panel's order number, its software version, the exact field behavior and the identity format you need, and take that package to official Siemens support. Do not loosen server-wide security settings to compensate for a local text-entry problem, and do not rename the customer's domain; neither action addresses an entry limitation on the panel.
Questions asked
Where does the domain administrator find the domain's short authentication name?
In the domain's properties in the directory administration tools, or by reading the domain shown in the Windows logon dialog on a domain-joined workstation. The short name is a separately configured identifier: it can differ from every label of the DNS name, so it must be read, not derived.
Can I use an account that is local to the file server instead of a domain account?
Yes, as a different design. A server-local account authenticates at the file server itself, so the credential dialog is filled per the panel's documented convention for that case, with no customer domain involved. Confirm first that the panel's supported SMB dialects and authentication methods match the server configuration.
The short name saved fine, but the share still refuses access. Is the name wrong?
Not necessarily. A saved entry only proves the panel stored the value. Check the file server's security event log for the logon attempt: an audit failure at logon points at the credentials, a success followed by an access-denied event points at share permissions or file-system permissions for that account.
Does entering the short name change the server address or the customer's domain?
No. The domain entry belongs only to the credential the panel presents. The server's DNS name in the network path, the share name and the customer's Active Directory configuration all stay exactly as they are, which is why this fix needs no change on the customer's side.

