Troubleshooting
Why a KTP400 Comfort OEM order number is missing from the catalog
Short answer
The order number 6AV2124-5DC00-0AC0 is a customer-specific KTP400 Comfort built for one OEM, so it never appears in the public TIA Portal catalog. Configure the standard KTP400 Comfort with the configured firmware equal to or older than the panel's installed version, and make the first transfer through ProSave with the panel in Service Mode at 192.168.1.1.

On this page
- Why is 6AV2124-5DC00-0AC0 not in the TIA Portal catalog?
- Which device do you configure in TIA Portal instead?
- Which firmware version do you set on the configured device?
- Why does TIA Portal report "Cannot connect to HMI"?
- How do you connect to the panel with ProSave in Service Mode?
- Does the standard catalog device change the panel's ratings?
- Is it OK to load a standard project onto the OEM panel?
- Questions asked
The order number 6AV2124-5DC00-0AC0 on the type plate is a customer-specific KTP400 Comfort built for one OEM, and customer-specific order numbers never appear in the public TIA Portal catalog or in the hardware support packages the manufacturer publishes. The panel is a standard KTP400 Comfort in hardware and firmware generation, so the fix is to configure the standard catalog device, keep its configured firmware equal to or older than the panel's installed version, and make the first transfer through ProSave with the panel in Service Mode. The same route clears the "Cannot connect to HMI" error that appears when TIA Portal cannot reach the panel at its configured address.
Why is 6AV2124-5DC00-0AC0 not in the TIA Portal catalog? #
Because the number is customer-specific: Siemens builds the panel to a fixed specification for one OEM, and such order numbers are delivered outside the public catalog, so no published hardware support package contains it. The number still decodes cleanly. The 6AV2124 block is the Comfort Panel family that also holds the standard 4-inch device, and the suffix marks the customer-specific build, which differs in front design, labeling and a wider ambient rating rather than in electronics or firmware generation. What the missing entry changes, and what it does not:
- You cannot select the panel in the hardware catalog by its own order number or by name.
- You can still engineer, compile and load for it, because the hardware, the loadable runtime image and the transfer channels are those of the standard KTP400 Comfort.
- The exact order number can appear in a project only when the OEM supplies its own hardware support package for it.
Which device do you configure in TIA Portal instead? #
The standard KTP400 Comfort with order number 6AV2124-1DC01-0AX0: open the device catalog, take the Comfort Panel family at the 4-inch size, and use that node, because the OEM panel loads exactly the image compiled for this device. The steps:
- Add the device in the device view and confirm in device configuration that the order number line shows the standard number, not the OEM one.
- Check the display definition: a 4.3-inch screen at 480 x 272 pixels, the same TFT the OEM unit carries.
- Compile the HMI station; when the compiler reports no device-related errors, the project is loadable onto the OEM panel.
Which firmware version do you set on the configured device? #
One equal to or lower than the firmware already installed on the panel: a configured version above the installed one is refused at transfer, because the loader will not place a newer runtime onto older device firmware. TIA Portal stores a firmware version with each configured HMI device, and the installed version is what ProSave reads back over the service connection described below. Loading a project configured for an older version onto newer panel firmware is allowed; the reverse is blocked until the panel's operating system is updated with an image matching the configured version, a matching explained in Matching an HMI panel image to its TIA Portal project version. So read the installed version first, pick that version or any older one in the device's firmware selection, and update the panel only when a project genuinely needs a newer version.
Why does TIA Portal report "Cannot connect to HMI"? #
Because the engineering PC cannot reach the panel at the address the transfer expects: the panel's PROFINET address is unknown or sits in a different subnet, so every attempt — download, operating-system update, USB alike — is refused at the connection step. This error has nothing to do with the missing catalog entry; the two problems only seem related because they arrive together. Typical causes on a panel in this state:
- The panel is still at its delivery network state while the PC sits on the office network, so no route to the panel exists.
- The panel is not accepting transfer connections at all, which is why USB fails the same way as PROFINET.
- Repeated downloads change nothing, because the address, not the project, is the blocker.
Stop retrying and move to the service connection in the next section; it works without knowing the panel's configured address.
How do you connect to the panel with ProSave in Service Mode? #
Enable Service Mode on the panel itself and it answers at the fixed service address 192.168.1.1; give the engineering PC a static address in that subnet, for example 192.168.1.10 with the mask 255.255.255.0, and cable the two together. The procedure:
- On the panel, open its on-device control panel and enable Service Mode; the panel then answers at the fixed service address instead of its configured one.
- On the PC, set the Ethernet adapter to 192.168.1.10 with the mask 255.255.255.0 and no gateway; if another adapter such as the office LAN or Wi-Fi uses the same range, disconnect it so the test cannot leave through the wrong interface.
- Connect the patch cable to either RJ45 socket of the panel's PROFINET interface.
- Verify the path with
ping 192.168.1.1 -t; replies must arrive before ProSave is opened. - Open ProSave, select KTP400 Comfort as the panel type and an Ethernet connection, and enter the service address on the General tab. If the OEM variant is missing from ProSave's device list, the standard entry is the correct substitute, the same situation covered in When a panel model is missing from the ProSave device list.
- Connect: ProSave reads back the installed firmware and image, which is the version the firmware rule above needs. From here you can back up the panel, update the operating system with the matching image, or reset it to factory settings.
- Assign the panel the address your project expects from its on-device network settings, disable Service Mode so it returns to normal operation, and download from TIA Portal.
Worked example, why this pair of addresses needs no router: the mask 255.255.255.0 has 24 network bits and 8 host bits, and 8 host bits give 2^8 = 256 combinations; removing the network and broadcast addresses leaves 254 usable ones. The service address fixes the network at 192.168.1.0, so the usable range runs 192.168.1.1 to 192.168.1.254 with 192.168.1.255 as broadcast, and both the PC address and the panel's service address fall inside it — one cable hop, no gateway.
One caution before the operating-system update or the reset: both erase the project and data on the panel, so take a ProSave backup first and do the work with the machine in a safe state, because the HMI is dark while the image is written.
Does the standard catalog device change the panel's ratings? #
No: the catalog device defines only the compiled runtime image and the transfer format, while the thermal and electrical ratings belong to the physical unit — this OEM variant's 55 °C ambient specification stays valid, and spare parts keep the OEM order number. The standard device's data, for comparison and for documentation:
| Parameter | Standard KTP400 Comfort |
|---|---|
| Display | 4.3-inch TFT, 480 x 272 pixels |
| Touch | analog resistive |
| Supply | 24 V DC, permissible 19.2 to 28.8 V, about 8 W |
| Interfaces | PROFINET with a 2-port switch, USB host, USB device |
| Protection | IP65 front, IP20 rear |
| Ambient, standard unit | 0 to 50 °C operating |
| Ambient, this OEM variant | 55 °C as designated by the OEM |
The two variants share the same electronics generation, so for cabinet design around the panel in front of you the OEM unit's own rating governs; the standard row applies to a standard unit.
Is it OK to load a standard project onto the OEM panel? #
Yes: the OEM unit is a KTP400 Comfort in hardware and firmware generation, so a project compiled for the standard device runs on it unchanged — make the standard device the permanent engineering choice unless your documentation must name the exact OEM order number. The decision for each case:
- The machine must run: standard KTP400 Comfort device, configured firmware not newer than the installed one, first transfer over the ProSave service connection. This path needs nothing from the OEM.
- The documentation must show the exact order number, as in spare-part lists or an OEM handover: request the OEM's hardware support package, confirm it targets your TIA Portal version — these packages do not install across versions — import it with the support-package installer, and create the device from the OEM node it adds.
- The first download ends in "Cannot connect to HMI": do not recompile and do not hunt the catalog; use Service Mode with ProSave, set the panel's project address, and download again.
Two problems, two fixes: the missing catalog entry is answered by the standard device, the refused connection by the service address, and neither needs anything from the OEM except, optionally, its support package.
Questions asked
How is this OEM panel different from a SIPLUS unit?
SIPLUS parts carry 6AG1 order numbers and are public catalog products: they appear in TIA Portal once the matching SIPLUS support package is installed. The 6AV2124-5DC00-0AC0 stays in the 6AV2 HMI family with a customer-specific suffix, so no public package adds it and only the OEM's own support package can.
Where do you get SIMATIC ProSave?
ProSave is installed along with TIA Portal and is also published on Siemens Industry Online Support under entry ID 10347815. Take it only from the manufacturer's support portal: ProSave writes the panel's operating system, so a copy from anywhere else is not a source you can trust.
If the OEM panel fails, can a standard KTP400 Comfort replace it?
Only where the ambient at the mounting point stays within the standard unit's 0 to 50 °C rating and the machine documentation accepts the standard part. The OEM variant's 55 °C capability is not carried by a standard unit, so at that design point the replacement must come from the OEM or carry the same extended rating.

