Troubleshooting
Why a TP1500 Comfort freezes after weeks but still answers ping
Short answer
Ping alive with touch and SmartClient dead means the panel's operating system is running but the WinCC Runtime is hung, usually from a project run past its system limits, above all the 600 objects allowed per screen on a Comfort panel. Count every faceplate inner object and every animated tag, then match the panel firmware to the TIA Portal version that built the project.

On this page
- Why does the panel still answer ping when touch is dead?
- How many objects are allowed per screen on a Comfort panel?
- Do faceplate instances count against the screen limit?
- Do animations count as objects or as tags?
- How do you count what your screens actually use?
- Which firmware should the panel run?
- How do you fix a screen that is over the limit?
- Questions asked
A TP1500 Comfort that stops taking touch, refuses a SmartClient connection and still answers ping has a hung WinCC Runtime, not a network fault. The panel's operating system keeps its TCP/IP stack alive, so ping succeeds while the runtime process is stuck or out of working memory, and only a power cycle clears it. The two things that put a project into this state over weeks of running are screens built beyond the documented system limits and a firmware that does not match the TIA Portal version that built the project.
Why does the panel still answer ping when touch is dead? #
Because ping tests the operating system's network stack, not the HMI runtime, and only the runtime is hung. ICMP replies are handled below the application layer, so a panel with a deadlocked or memory-starved WinCC Runtime keeps answering on its configured address. Confirm it from the engineering station with a continuous ping to the panel's address, for example ping 192.168.1.50 -t: replies continuing during the freeze prove the panel is alive at OS level while the runtime is not. A refused SmartClient session completes the signature, because Sm@rtServer runs inside the runtime. If ping fails as well, you are chasing power, cabling or a lost network connection instead.
How many objects are allowed per screen on a Comfort panel? #
The documented limit is 600 objects per screen on a Comfort panel, and that is a ceiling, not a design target. Complex objects include bars, sliders, symbol library entries, the clock and all objects from the controls area, as published in the WinCC performance data for Comfort Panels (Comfort panel system limits). A project does not fail at compile time when it runs near or past these limits; it fails weeks later in the field, when memory fragmentation or heap exhaustion accumulates in a runtime that was already at the edge. That is exactly the weeks-then-freeze pattern you are seeing across panels from TIA Portal V13 through V16 projects.
Do faceplate instances count against the screen limit? #
Yes, and every object inside the faceplate counts on every instance, so faceplates are the most common way a screen silently blows the budget. A faceplate instance is not one object: it contributes the sum of all objects in its template to the per-screen count of every screen where it appears. A template with 5 symbol library I/O fields costs 5 objects per instance, so 30 instances of that one faceplate already consume 150 of the 600-object allowance before the screen's own buttons and fields are counted. Faceplates are not banned, but each one must be costed this way when the screen is designed.
Do animations count as objects or as tags? #
Animations count as tags, not as extra objects, and they inflate the screen's tag load rather than its object count. A graphic view with an animation on it is still one object, but each animated property, such as visibility, position or flashing, registers a tag connection in the screen's tag table. A view with two animations therefore carries two tag connections instead of one. This distinction matters when you audit: sorting by object count alone will miss screens that are heavy in animated tags, and animated tags drive the same runtime working memory that runs out over weeks.
How do you count what your screens actually use? #
Work through the project screen by screen, in this order:
- List every screen and count its objects, including every object inside each faceplate instance multiplied by the number of instances on that screen.
- Count the tag connections per screen, adding one for every animation on every object.
- Flag any screen near the 600-object ceiling or carrying dozens of animated tags as a redesign candidate.
- Check the panel's system information screen and record the firmware version next to the TIA Portal version in the project's properties, so the pairing check below has real values.
Which firmware should the panel run? #
The firmware that belongs to the TIA Portal version that compiled the project, with the latest update of that version applied. A project built in one TIA Portal version running on firmware from another generation adds avoidable runtime overhead, and vendor guidance for these freezes is consistent: update the firmware and correct the project design. Read the installed firmware on the panel's system information screen, compare it with the TIA Portal version that generated the project, and where they disagree, update both to a matched current pair and recompile and reload the project. If you also want the runtime's own numbers, a diagnostic tool such as Siemens Option+ shows CPU load, memory use and tag cycle times on the panel, at the cost of a little of the performance it measures.
How do you fix a screen that is over the limit? #
Reduce, split and localize, in this order:
- Slim each faceplate template: a 5-field faceplate used 30 times costs 150 objects per screen; cutting the template to 3 fields saves 60 objects on that screen at a stroke.
- Move rarely used detail into a pop-up or a second screen opened on demand, so the heavy content is not resident with the main view.
- Replace global tags used on only one screen with local tags, which release their memory when the screen closes.
- Pack PLC data: one 16-bit word of status bits instead of 16 separate booleans cuts tag connections and acquisition load together.
- Disable unused alarms and drop languages the operators never switch to; both free memory the runtime needs.
Worked example: a machine screen holds 40 instances of a 5-symbol faceplate, 110 other objects, and 30 objects carrying two animations each. Object count is 40 × 5 + 110 = 310 of the 600 allowed, so this screen passes on objects. Tag connections from animation are 30 × 2 = 60 where 30 would be expected, so the animation load is the screen's real weight; trimming those objects to one animation each removes 30 tag connections. Another screen in the same project with 100 instances of the same faceplate reaches 100 × 5 = 500 objects before its own content, and that is the one to split before anything else.
The decision: with ping alive and SmartClient refused, stop troubleshooting the network. Bring every screen under the object ceiling with faceplates costed per instance, cut animated tags, and put the panel on firmware matched to the TIA Portal version that built the project. An older TP270 freezing for PROFIBUS-era reasons is a different fault with its own fix; see why a TP270 touch screen freezes but the PLC keeps running if that is your panel. If a panel still freezes after the project is inside limits and the firmware is matched, replace the unit rather than keep power-cycling it, and size the replacement against your existing cut-out with the panel cut-out reference.
Questions asked
Should I use the standard graphic list or JPG images for screen graphics?
Prefer the vendor's standard graphic list objects over large JPG bitmaps. Symbol-library graphics are vector-style resources shared across screens, while every JPG adds its pixel data to panel memory and to the repaint cost of each screen change. Keep bitmaps small, and reuse one graphic list entry wherever the same symbol repeats.
How large can the archives be on the panel?
The published Comfort panel limits bound the number of archives and logging tags, but there is no single documented safe byte size for a long-running panel. Set each log to cyclic overwrite with a small retention window, and verify in the panel's system information how full the internal storage is after a few weeks; a nearly full flash slows the Runtime.
Does installing a diagnostics tool on the panel change the behavior?
Yes, slightly. Any runtime diagnostic tool, including Siemens Option+, uses some of the same CPU and memory you are measuring. Keep it installed only for the measurement period, capture load, memory use and tag cycle times under normal operation, then remove it before returning the panel to production.
Is this the same fault as a TP270 that freezes while the PLC keeps running?
No. That older PROFIBUS-era panel freezes for a different reason, tied to its communication and firmware generation. If your panel is a Comfort device with a refused SmartClient and a live ping, work through the Runtime and project-limit checks in this article instead.