Why a TP177 project hides the faceplate option in WinCC Flexible

HMI and touchscreens Published 8 min read

Short answer

WinCC flexible hides the faceplate command because the configured TP177 target cannot execute faceplates; only Multi Panels and some Mobile Panels can run them. Reinstalling WinCC flexible 2008 SP5 will not bring the option back. Confirm with a test project on a capable target, then either retarget the project or build the interface from ordinary grouped objects.

On this page
  1. Why the editor hides the command for a TP177 target
  2. Sort the symptom before you touch the installation
  3. Testing one button in a TP177 project and a Multi Panel test project
  4. Diagnostic sequence
  5. Retarget the project to a faceplate-capable panel
  6. Keep the TP177 and build without faceplates
  7. Verify the fix on the panel, not in the editor
  8. Pitfalls that cost the most time
  9. The decision, case by case
  10. Questions asked

The faceplate command is missing because the configured TP177 target cannot execute faceplates — the restriction lives in the device definition of your project, not in the installation. In WinCC flexible, faceplates run only on Multi Panels and some Mobile Panel models, so the editor hides the creation command for every target outside that set, TP177 included. Reinstalling WinCC flexible 2008 SP5, reselecting the object or rebooting the engineering station will not bring it back. Prove it with a throwaway test project configured for a Multi Panel: if the same right-click shows the command there, the software is complete and the target is the deciding difference. From there you have exactly two working fixes — retarget a copy of the project to a faceplate-capable panel, or keep the TP177 and build the repeated interface from ordinary grouped objects.

Why the editor hides the command for a TP177 target #

WinCC flexible filters its engineering functions by the HMI device configured in the project. A faceplate is not a drawing convenience; it is a runtime object — a reusable group whose internal elements are wired through a defined interface of tags and properties — and the panel's runtime has to understand and execute it. When the configured target has no faceplate representation in its runtime, the editor hides the creation command rather than build a project the panel could not run.

In WinCC flexible that capability is confined to the Multi Panel family and some Mobile Panel models. Every TP177 target — TP177A, TP177B and TP177 Micro included — sits outside that set, so the command stays hidden in a TP177 project under any selection, service pack or reinstall.

The filter follows the project, not the installation. The same WinCC flexible 2008 SP5 setup shows the command in a Multi Panel project and omits it in a TP177 project, which is what makes the test in the next section decisive. Target-driven filtering decides other fixed limits in this tool family as well, such as why WinCC flexible 2008 cannot pan an oversized HMI screen.

Sort the symptom before you touch the installation #

Match what you observe against the configured target. The table separates a device restriction from an installation fault.

What you see What it means What to do
Faceplate command absent when you right-click a selected button in the TP177 project A device restriction, not an installation fault Confirm with the test project below, then retarget or rebuild
Command appears in a test project configured for a Multi Panel The installation contains the feature Stop reinstalling; the production target is the deciding difference
Command absent even in a test project for a capable target Selection, object type or the installation itself is at fault Check the selection rules in the screen editor, then repair the installation
Built faceplate misbehaves in runtime on a capable panel A runtime behavior, not the creation filter Verify refresh and script behavior on the panel

Testing one button in a TP177 project and a Multi Panel test project #

This comparison closes the diagnosis in one pass.

Inputs:

  • Production project — the reported case: a TP177 target in WinCC flexible 2008 SP5, one button on one screen.
  • Test project — a throwaway build in the same installation: Multi Panel target, one screen, one button. The Multi Panel family is one faceplate-capable set in WinCC flexible; some Mobile Panel models are the other.
  • Test action — select the button in the screen editor and open the right-click context menu in both projects.

Rule: WinCC flexible offers the faceplate creation command for a selected screen object only when the configured target belongs to a family whose runtime can execute faceplates; for every other target the command is omitted.

The comparison, written out:

  1. TP177 project: button selected, context menu opened — no faceplate command.
  2. Multi Panel test project: same button type, same installation, same service pack, same menu — the faceplate command is present.
  3. Installation, service pack, object type and mouse click are identical across the two tests, so the configured target is the single input that changed.

Result: the SP5 installation carries the faceplate feature, and the TP177 target is what removes the command.

Decision and threshold: if the command appears in the test project but not in the production project, the diagnosis is closed — no reinstall can change a device capability, so choose between retargeting and a rebuild. Only if the command is absent in both projects is an installation or selection fault still on the table.

Diagnostic sequence #

  1. Open the device selection in the project and read the exact configured HMI target. Trust that entry, not the panel name on drawings, in file names or in project notes.
  2. In the screen editor, select one ordinary element — a button is the standard test object — and open its context menu. Note whether the faceplate command is absent entirely.
  3. Create a throwaway test project with a Multi Panel target, add one screen with one button, and open the same context menu.
  4. If the command appears in the test project, the installation is complete. Stop troubleshooting the service pack and pick a fix path below.
  5. If it is absent in both projects, check that you selected a single screen element rather than the screen itself, a group or several objects, and that you are working in the screen editor. Only after those checks fail, repair the WinCC flexible installation from its original media.
  6. Compile the production project once before any hardware decision, so other target-dependent messages surface early.

Retarget the project to a faceplate-capable panel #

Take this path when faceplates are a requirement — many identical equipment interfaces that must stay in step — rather than a convenience.

Copy the project first. Retargeting can change usable screen dimensions, fonts, object availability and communication settings, and every conversion message needs a decision instead of a click-through.

Select the replacement from the faceplate-capable set in the device selection, and check the new target — model and firmware — against the device support of the WinCC flexible edition installed on the engineering station before you commit. Then build the faceplate, connect its interface to the project tags, and compile the complete project.

Before transfer, confirm the physical hardware is the panel you configured; for a Multi Panel such as an MP377, the panel itself offers a way to identify an MP377 panel in WinCC flexible 2008 runtime. A clean compile for a new target does not make the panel bolted to the machine that target.

Keep the TP177 and build without faceplates #

Take this path when the installed TP177 stays. Two designs cover most faceplate jobs.

The direct rebuild: draw the control cluster once, copy it to every screen that needs it, standardize the element names, and document the tag mapping of every instance. The tradeoff is maintenance — each later change reaches every copy, so keep one controlled master screen and re-check all instances whenever it moves.

The pop-up variant: TP177A, TP177B, TP177 Micro, OP77B and OP73 support the native Screen Window object in WinCC flexible, driven by visibility conditions — the documented object for pop-up behavior on this family.

Both designs stay inside the TP177 target's capability set, so no conversion messages appear on this path. The cost is manual synchronization between copies, and the project documentation has to carry it.

Verify the fix on the panel, not in the editor #

Compile the complete project, not just the open screen, and clear every unsupported-object and conversion message before transfer.

On a retargeted project, place the faceplate more than once and connect each instance to different test tags. Operate one instance and confirm the other does not move; exercise every button, indicator, input field, visibility condition and navigation action in the interface. Faceplates have runtime traps of their own — a WinCC faceplate script does not auto-refresh is one documented pattern — so test refresh behavior on the panel, not only the first draw.

On the rebuild path, compare every copied instance against the master for appearance and tag assignment; a visually correct copy can still address the wrong process value. The editor preview proves nothing about target runtime behavior: transfer to the configured panel type and repeat the tests there.

Pitfalls that cost the most time #

  • Reinstalling the service pack first: SP5 cannot add a runtime capability the configured target's definition excludes, and the repair install changes nothing.
  • Reading the drawing instead of the project: the panel name in the documentation can differ from the configured HMI target that actually decides.
  • Trusting one family's behavior: WinCC flexible exposes its functions device by device; what a Multi Panel project shows proves nothing about a TP177 project.
  • Retargeting without a hardware check: a successful compile for a capable target does not make the installed TP177 run that project.
  • Clicking through conversion messages: usable screen area, fonts and object availability move with the target, and every message hides a runtime surprise.

The decision, case by case #

  • Faceplates are required and a panel change is possible: retarget a copy of the project to a Multi Panel or a Mobile Panel model documented as faceplate-capable, rebuild the affected screens, and verify on the physical panel before transfer.
  • Faceplates are required and the TP177 stays: the requirement has no solution on that hardware, so one of the two has to move — until then, the Screen Window pop-up and the direct rebuild are the working designs.
  • Faceplates are only a convenience: keep the TP177, rebuild with ordinary objects, and carry the instance documentation in the project file.
  • The command is missing even in a capable-target test project: the target is not the problem — fix the object selection or the installation first.

Questions asked

Which HMI panels can use faceplates in WinCC flexible?

In WinCC flexible the Multi Panel family and some Mobile Panel models are the faceplate-capable targets; the TP177 family is not. The successor engineering environment carried the feature further: faceplates are documented for Comfort Panels and for WinCC Runtime Advanced, and as of V13 SP1 faceplate properties can use HMI and PLC user data types. Match the tool and the target before planning a faceplate design.

How do I build a pop-up interface on a TP177 without faceplates?

Build the pop-up content as its own screen. Place a screen window on the base screen, point it at the pop-up screen, and toggle the window's visibility from a tag or an event. Keep one master pop-up layout and copy it for each variant, and verify the toggling on the physical panel, because object behavior is filtered by the configured target.

Does the TP177 Micro behave differently from the TP177B here?

No. The TP177 Micro is tailored to the S7-200 PLC family and is configured with WinCC flexible Micro, so it is in the same position as the rest of the small-panel range. Its pop-up route is the Screen Window object, and if faceplates become a hard requirement, the route is a move to a faceplate-capable target. Check the S7-200 driver in any new target before you move, because the Micro is tied to that PLC family.

What faceplate limits remain even on a target that supports them?

Faceplate support does not remove the tool's limits. The documented one to plan around: WinCC flexible cannot multiplex structure tags, so a faceplate instance cannot switch structure-connected elements to different structures at runtime. Connect each instance with plain tags, and verify every instance in runtime on the configured panel instead of trusting one tested copy.

Keep reading

  • Troubleshooting

    TP177B backtransfer and the missing PDZ file

    You cannot turn a TP177B's running program into an editable project unless the original download was made with Back transfer enabled in WinCC flexible. A backtransfer decides it: a PDZ file with real content means the source can be recovered and edited, while a 0-byte file or an error means it was never stored and you need the original project or a rebuild.

    HMI and touchscreens

  • Explainer

    Why KTP400 Basic Color PN is missing in WinCC flexible

    The KTP400 Basic Color PN (6AV6647-0AK11-3AX0) is not configurable in WinCC flexible 2008 in any service pack; the missing catalog entry is a support boundary, not a fault in your installation. Engineering starts in TIA Portal V11 SP2. A STEP 7 V5.6 controller project is either migrated into TIA Portal or kept separate behind a PLC proxy.

    HMI and touchscreens

  • Troubleshooting

    WinCC Flexible Migration Fails at 9% on Missing SQL Database

    A migration that stops at 9% with an SQL database message means TIA Portal could not open a database the WinCC flexible source project depends on. Read the Migration log, restore access to that exact database or remove the obsolete external connection in WinCC flexible 2008, then start Migrate project from the project level and rerun.

    HMI and touchscreens