Troubleshooting
Why a V11 faceplate project fails to upgrade to V13 SP1
Short answer
Error 0080:000030 means the V11-to-V13 SP1 project upgrade stopped at an unconverted HMI application object, HMI_RT_1 in the upgrade log, not at a meter fault. The recovery is to migrate the faceplate library on its own, on a current V13 SP1 update build, then import it into a fresh project and rebind the tags.

On this page
A V11 faceplate project that fails the upgrade to V13 SP1 with error 0080:000030 has stopped at an unconverted HMI application object, and the upgrade log names it: HMI_RT_1, model type Siemens.Simatic.HwConfiguration.Hmi.Model.HmiApplicationData. That is an engineering conversion fault, not a meter fault. The recovery that works is not a patched retry of the demonstration project but a split: migrate the reusable faceplate library separately on a current V13 SP1 update build, import it into a fresh target project, and rebuild the tags, connection and screen integration by hand. This article reads the log, then walks the library branch.
What error 0080:000030 actually reports #
The dialog text, "An error occurred while upgrading the project", tells you only that the conversion stopped. The log entry tells you where. The upgrade runs against serialized engineering data before any runtime exists, so this failure happens minutes after you click upgrade, not at runtime: no screen has rendered, no tag has gone bad, no meter has been polled. Treat every later log line as a consequence of the first failed object and keep the complete log.
Three things travel in the package, and the failure branches on which one you are converting:
- The faceplate itself: a reusable HMI visualization component with an interface that connects its displayed values and controls to application data.
- The library: the container that packages that reusable component and its dependent types. It migrates on its own.
- The demonstration project: device configuration plus an HMI application wrapped around the faceplate. This is the part that fails here.
The package targets WinCC Runtime Professional. Keep that runtime target fixed when you rebuild; placing the component into a project for a different runtime product is a separate compatibility problem you would be adding to this one.
Reading the upgrade log for the V11 PAC3200 faceplate project #
Inputs. The failing upgrade produces this log line, reproduced exactly as the tool records it, including its own spelling of "uncoverted":
Uncoverted object found: name='HMI_RT_1' type='Module' (model type 'Siemens.Simatic.HwConfiguration.Hmi.Model.HmiApplicationData') parts=0xfffffffd ; bit: 0=True type 'Object' (model type 'Siemens.Automation.DomainModel.Parent4LoadableObjectsLoadInfoData'); bit: 1 =False type 'Object' (model type 'Siemens.Simatic.HwConfiguration.Model.ConfigBaseData')
The engineering installation is TIA Portal V13 SP1; the reported clean migration ran on V13 SP1 Update 7.
Rule. A project upgrade aborts at the first object it cannot map into the new version's data model, and the log names that object. The name and model type identify which part of the package did not convert, and that decides which recovery branch applies.
Reading the line, field by field:
| Log field | Value in this failure | What it tells you |
|---|---|---|
| Upgrade error | 0080:000030 | Conversion stopped before a usable upgraded project existed. |
| Object name | HMI_RT_1 | The HMI application of the demonstration project, not a screen, tag or meter. |
| Object type | Module | An engineering model object, not live process data. |
| Model type | Siemens.Simatic.HwConfiguration.Hmi.Model.HmiApplicationData | The HMI application data inside the hardware configuration is what did not convert. |
| parts value | 0xfffffffd | Serialized bookkeeping. Record it in your notes; it is not a setting and must not be edited. |
Result. The unconverted object is the enclosing HMI application. The library is a separate package object with its own migration path, so a failed project upgrade does not tell you the faceplate itself is unusable — and on this package it is not: a library-only migration on a V13 SP1 Update 7 installation completed without errors.
Decision. If your log names HMI_RT_1 with that model type, stop retrying the project upgrade and take the library branch below. If your log names a different object, diagnose that object instead; this diagnosis does not transfer automatically.
Migrate the library separately #
- Re-download the original package from the manufacturer's support portal so the library you migrate has a traceable history; the faceplates for SENTRON PAC power meters are support document 67318600. A converted file of unknown origin is not a substitute for a repeatable test.
- On a TIA Portal V13 SP1 installation at the newest update you have installed, open the library alone and run its migration. Update 7 is the build on which this library is reported to migrate cleanly; earlier updates repair fewer conversion defects, so a current build is the whole point of this step.
- Save the library migration's own log. If it fails here, you have a different diagnosis, and the failed project log is not its evidence.
- Open the migrated library and confirm the faceplate and every referenced reusable type resolve. Missing types must be fixed before any import, or the destination compile will inherit them.
Rebuild the faceplate into a fresh V13 SP1 project #
The migration documentation is explicit that each migration creates a new project for the migrated data, so plan for a fresh project rather than an in-place repair of the old one.
- Create a new project with the device you actually run, targeting WinCC Runtime Professional.
- Import the migrated library into it.
- Place the faceplate on the screen and assign every required interface member to a tag of a compatible data type.
- Point those tags at your project's own HMI connection, not at any demonstration entries the import may have carried in.
- Compile. Clear every unresolved component reference and interface error before you go near runtime.
Migration moves engineering objects; it does not carry your application wiring. Connections, tags, screen integration and any referenced logic are yours to rebuild, and the compile is what proves them.
Verify the faceplate before trusting it #
A faceplate can render correctly while showing wrong or stale values, so work through this list in order:
- Every interface member is assigned, and each data type matches the tag it feeds.
- The tags resolve through the destination project's configured communication path to the real meter.
- Displayed units and scaling agree with the underlying values the connection delivers.
- Read-only values are verified first; anything that writes to the meter or the process is exercised only afterward, on an isolated bench with verified tags.
A compiled change reaches the panel only through a fresh transfer, which is why an HMI edit needs a new runtime download rather than a save. Only when the display reads correctly through your own connection, and the write controls have passed a bench test, is the conversion done. If the original terminal itself is aging and this rebuild tips the balance, the same faceplate approach can run on a PC-based operator station instead of a dedicated panel.
Questions asked
Does error 0080:000030 mean the PAC3200 meter communication is faulty?
No. The error is raised during the engineering conversion, before any runtime is compiled or started, so no meter communication has been attempted yet. Communication faults such as bad tag quality appear only after a compiled project runs. Check meter communication after you have rebuilt the project, compiled it and downloaded the result.
Can I edit the parts value 0xfffffffd or the model type to force the upgrade through?
No. Those entries describe serialized engineering data inside the project file; they are not user settings and there is no supported way to adjust them to make the conversion pass. Editing project internals by hand risks a project that loads but behaves unpredictably. Use the library migration and rebuild path instead.
Which update level of V13 SP1 should the migration run on?
Run it on the most current V13 SP1 update installed and maintained. Update 7 is the build on which the library migration is reported to have completed without errors, and each update repairs known conversion defects, so an earlier build gives a less predictable result. Check your installed update level before retrying anything.
Does migrating the library carry over the tags and screen connections?
No. The library carries only reusable engineering objects, including the faceplate and its interface. Tags, HMI connections, screen integration and any application logic live in the project and must be rebuilt in the destination. Expect to assign every faceplate interface member to your own tags before the first compile.
Which runtime is the PAC3200 faceplate package written for?
The package targets WinCC Runtime Professional, per the support entry for the faceplates for visualization of SENTRON PAC power meters. Confirm the runtime target before importing, because a faceplate placed in a project whose runtime does not match the component can compile with unresolved references or fail to render its data correctly.

