Troubleshooting
Why a WinCC flexible Runtime device type is not valid for this version
Short answer
The message means the WinCC flexible Runtime component on that PC is missing or sits at a different update level than the Engineering System, not that Windows is wrong. Compare the Installed Software lists on both stations, then re-run setup in modify mode and re-apply the updates so both entries match.
On this page
- Why does WinCC flexible say the Runtime device type is not valid?
- Is WinCC flexible Runtime the right device type for a PC?
- Is Windows XP SP3 the reason the project will not open?
- How do I compare the software versions on both computers?
- Why does one disc give two different installations?
- How do I repair the installation so the device type is accepted?
- What if the Installed Software lists already match?
- Which fix matches which symptom?
- Questions asked
When a project that opens on one PC is refused on another with the message "The kind of HMI WinCC flexible Runtime is not valid for this version of WinCC flexible", the cause is the installation, not Windows and not the project file: the WinCC flexible Runtime component on the failing PC is missing, or it sits at a different update level than the Engineering System. The same installation disc does not guarantee the same installation, because setup lets each PC take a different component set. Fix it by comparing the Installed Software lists on both stations entry for entry, then re-running setup in modify mode and re-applying the updates so the Runtime entry matches the Engineering System entry exactly. The service pack question that comes up first is a side issue: the release supports Windows XP Professional SP2, so leave both operating systems alone.
Why does WinCC flexible say the Runtime device type is not valid? #
The error means the WinCC flexible Runtime component on that PC is missing or sits at a different update level than the Engineering System, so the device list the Engineering System builds from local registrations does not carry a Runtime entry it can accept.
The Engineering System builds its device list at startup from the components registered on the station, and each device type carries the version of the component that provides it. Opening a project makes it compare the stored device type against that registration. A difference in update level, not only in the release name, is enough: the Engineering System cannot instantiate the target with the configuration libraries present, so it declares the type invalid rather than silently loading a mismatched configuration.
Two terms carry the whole diagnosis. The device type is the target entry stored in the project and offered in the device selection dialog. The Runtime component is the installed software that both executes a compiled project on a PC and supplies the Engineering System with the configuration support for that target. They install together, and a reduced setup or a one-sided update is what pulls them apart.
Is WinCC flexible Runtime the right device type for a PC? #
Yes — WinCC flexible Runtime is the target to choose when the finished application must run on a standard PC rather than on a panel, and if the runtime already loads and runs your project on that station, the runtime binaries themselves are healthy.
Panels are hardware targets in the same dialog; the Runtime entry is the target for an ordinary PC, so choosing it is correct whenever the finished application executes on a PC. The guide to running a WinCC flexible 2008 project in PC runtime shows that same target put to work.
If the runtime application on the failing station already loads and runs a downloaded project, the rejection happens on the engineering side only, which is exactly the split the version comparison in the next section exposes.
Is Windows XP SP3 the reason the project will not open? #
No — WinCC flexible 2007 is released for Windows 2000 SP4 and Windows XP Professional SP2, so the SP2 lab PC is inside the documented baseline, and the service pack level is not the discriminator for this error; the component registration is.
Adding or removing a service pack does not touch component registration, which is what this error reads. That is also why the fix is not an operating-system change: stripping a service pack off a loaded engineering PC to chase this message endangers every other package installed on it and leaves the registrations exactly as they were. If a later pack is blocked because other software on the station was never released for it, leave the operating system alone. A second machine on the same service pack that accepts the project settles the question in one test.
How do I compare the software versions on both computers? #
Open Start > SIMATIC > Information > Installed Software on the working PC and on the failing PC, write down every SIMATIC entry with its complete version string, and set the two lists side by side for an entry-for-entry comparison.
- On the working station, record every SIMATIC entry with the complete version string, including the trailing update and hotfix digits.
- Repeat on the failing station and put the two lists side by side.
- Compare them entry for entry; identical product names with different version digits are the finding, so look hardest at the Engineering System entry, the Runtime entry and every update or hotfix line.
- Flag entries present on one station only: a missing Runtime entry explains an absent device type with no further diagnosis.
- Read the device type and the version that last saved the project from the file on the working station, because a project saved by a higher update level is refused by a lower one.
Worked example, with illustrative counts. Say the home list carries 21 SIMATIC entries and the lab list carries 19. Pairing the names leaves exactly two lines unmatched, and 21 - 19 = 2: both are the Runtime entry plus the update line that carries it, so the lab station never received the component and the modify-mode install in the next section is the fix. The second shape ends the same way by counting matches instead of gaps: with 21 entries on both lists but one Runtime string carrying two more trailing hotfix digits than its twin, 20 of 21 strings agree and the one that disagrees is the fix target.
It is the same lineup check to run before trusting any station with a project, and checking HMI engineering software before a panel replacement covers it from the replacement angle.
Why does one disc give two different installations? #
Setup asks for a component selection on every PC, so a reduced install can omit the Runtime target entirely, and an update run on a station without the Runtime component lifts only the Engineering System half of the pairing.
A reduced install looks identical from the desktop; the difference only shows when the device dialog opens or a project loads. A station that once carried an older WinCC flexible release can also keep that release's registrations, and the Engineering System then sees two competing versions of one device type. This is why reinstalling from the disc changes nothing: the same selection reproduces the same gap. Compare the component sets before comparing anything else.
How do I repair the installation so the device type is accepted? #
Close the Engineering System and any running runtime, start the WinCC flexible setup from the installation medium, take the modify path instead of a fresh install, add the Runtime component beside the Engineering System, reboot, then re-apply every update and hotfix in release order with all components installed.
- Close the Engineering System, stop any running runtime, and end any simulation on the failing station.
- Start the WinCC flexible setup from the installation medium and take the modify or repair path, not a fresh install.
- In the component selection, add WinCC flexible Runtime beside the Engineering System until the component set matches the working station's list.
- Let setup finish and reboot; the Engineering System rebuilds its device list from the registrations only after the restart.
- Re-apply, in release order, every WinCC flexible update and hotfix that the working station's list shows, each run with all components installed so both sides lift together.
- Reopen
Start > SIMATIC > Information > Installed Softwareon both stations and confirm the lists agree entry for entry.
Step 5 carries an order for a reason, the same one behind installing the HMI base software before the service pack: an update run against a partial installation lifts only the components present and rebuilds the mismatch you just removed.
What if the Installed Software lists already match? #
Then look for registrations left by an older WinCC flexible release on the failing PC, because two competing versions of the same device type produce this conflict even when the newer setup reported success; uninstall the old release, reboot, and reinstall the current one with its updates.
Re-read the trailing digits as well as the product names, because a hotfix digit is easy to read past on screen. A related symptom, where the tool reports a component missing outright instead of a device type rejected as invalid, ends at the same list; its walkthrough is resolving a WinCC component-not-installed error on an engineering station.
Which fix matches which symptom? #
Each symptom maps to one fix: an absent Runtime entry gets the component added in modify mode, a stale update level gets the updates re-applied, a project saved by a newer level gets the station lifted, and a license banner is a separate licensing check.
- The new-project device dialog shows no Runtime entry at all: the component was never installed on that station, so run setup in modify mode and add it.
- An existing project with the Runtime device type is refused on open: the component sits at a different update level than the Engineering System, so re-apply the updates with every component installed.
- The project was last saved by a higher update level than the station carries: lift the failing station instead of saving the project down, because device type definitions do not travel backwards cleanly.
- A demo or time-limited banner appears when the runtime starts, while projects open normally: that is licensing, not registration; check the authorization separately, and transferring a WinCC flexible license authorization to a panel shows how one moves between stations.
The decision is one test in every case: make the Installed Software lists agree entry for entry, and stop when they do, not merely when the message disappears once. Under schedule pressure a known-good, matching station takes the project today, but that moves the work rather than repairing the installation, and the gap resurfaces at the next handover.
Questions asked
Is the project file itself corrupted when this error appears?
No. The message comes from the comparison the Engineering System makes between the device type stored in the project and the components registered on that PC. The file itself is untouched, and the same project opens unchanged on a station whose Installed Software list matches the one that saved it.
Can I copy the runtime installation folder from the working PC to the failing one?
No. Copying program folders skips the registration and license steps that setup performs, and it drops version-specific files onto a station that may sit at a different update level. Repair through the setup program's modify path instead, so the component and its registration land together at the Engineering System's level.
Can the two computers run different Windows service packs?
Yes, provided both operating systems are on the release's compatibility list. The error follows component versions, not the service pack: two PCs on different supported service packs open the same project when their SIMATIC entries match line for line, and a service pack change on either machine will not fix a registration gap.
Why does reinstalling from the same disc not clear the error?
Because a plain reinstall with the same component selection reproduces the same missing registration. Run setup again and take the modify option, tick the Runtime component explicitly next to the Engineering System, let it finish, reboot, then re-apply the updates that the working station's list shows before you test the project again.