Troubleshooting
Why a WinCC picture tree navigator does not open in runtime
Short answer
A missing picture tree navigator in WinCC V7.4 SP1 runtime is diagnosed by separating hierarchy persistence from runtime presentation: end Runtime, make one reversible edit in Picture Tree Manager, save, confirm it stayed saved, restart Runtime and compare. If the edit appears, fix the navigation display; if it disappears, fix the project save. Record the update level: Update 4 documented the hierarchy-display correction, and the reported case still failed with Update 8 installed.

On this page
A WinCC V7.4 SP1 runtime that starts without the picture tree navigator, while Picture Tree Manager shows a configured hierarchy, has one of two faults: the saved tree never reaches the project data the runtime loads, or the tree is saved correctly and the navigation display is simply not presenting it. Decide between the two with a single reversible edit in Picture Tree Manager, saved and confirmed, followed by a Runtime restart and a comparison against the captured starting state. Treat the installed update level as evidence to record, not as the opening move — in the reported case the update level that documented corrected hierarchy display was already installed, and the navigator stayed absent.
Read which failure you actually have #
Picture Tree Manager and the picture tree navigator are two different components. The manager is the engineering tool that stores the parent-child arrangement of the process pictures; the navigator is the runtime control that presents that arrangement to the operator. A configured hierarchy in the manager proves a structure exists in the project — it does not prove the running display is showing it. Pin down which presentation you have before changing anything.
| What you see in Runtime | What it points to first | What a healthy station shows |
|---|---|---|
| No navigation control anywhere in the picture | The startup picture and the display configuration that places the navigator | The configured navigation interface appears where the project puts it |
| The navigator opens but lists no areas or pictures | The saved hierarchy versus the project the runtime actually loaded | The configured areas and their pictures are listed |
| Entries are listed but selecting one opens no picture | The picture assignment on the entry and whether that picture exists | The selected entry opens its assigned process picture |
| Old areas are listed after a tree change | Whether the save persisted across a Runtime restart | The runtime shows the tree as it was last saved |
Capture the complete Runtime window for the record — the startup picture, the action you expect to open navigation, and any labels that do appear — not just the empty region. If your navigation surface is the overview-type window, check where its entries come from before you edit anything: where an HMI overview window gets its pages and alarms walks through that source. The first two rows are hierarchy or display faults, the third is a picture-assignment fault, and the fourth is the persistence fault the next section settles.
Run one recorded change-save-restart cycle #
End and restart Runtime only in an authorized maintenance window: while it is down, that station has no process displays, no alarm presentation and no operator control.
- Record the starting state. Capture the hierarchy in Picture Tree Manager and the full Runtime window, and choose one existing entry that must be visible afterwards.
- Back up the project, then end Runtime and confirm the session has stopped before you edit anything.
- Make one reversible edit. Rename one existing area or add a marker area whose name you will recognize, and write down exactly what changed so it can be restored.
- Save the Picture Tree Manager configuration, close the manager, reopen it and confirm the marker edit is still present. If it is already gone here, the save is the fault — stop before starting Runtime.
- Start Runtime for the same project and open the display that should contain the navigator.
- Compare against the captured starting state. The marker edit either appears in the navigator or it does not; that one observation classifies the fault.
- Restore the production tree. Undo the marker edit, save, restart Runtime once more and confirm the station is back to its normal hierarchy.
The sequence earned its reputation honestly: it cleared the fault once in a reproduction of this exact symptom, and the affected station's owner later ran the same loop many times with no change. One recorded cycle is enough — a cycle nobody records proves nothing about which stage failed.
Checks when the tree persists but the navigator stays absent #
A marker edit that reaches Runtime proves the save path and the project identity; the fault then lives in what Runtime is asked to display. Work down this list and change one variable at a time.
- Same project: confirm that the shortcut, script or autostart entry launching Runtime opens the project whose tree you edited, and compare the project path on screen with the path you edited. A second project copy on the same station imitates this fault exactly.
- Startup picture: compare the configured startup picture with the picture that actually appears after activation. A stripped-down startup layout can contain no navigation control at all.
- Navigation display: review the project configuration that places and shows the navigation interface, including visibility conditions and operator-access levels. A level filter can hide the navigator from the login you test with while it stays visible for another.
- Picture assignments: open an entry in the manager and confirm its assigned picture exists in the project's picture list under that name.
- Diagnostics: watch the messages produced during activation and record their exact text. Diagnose from the message, not from the blank area on screen.
That separation of saved engineering data from runtime presentation is the same one a WinCC trend that is empty after a runtime restart diagnoses from the trend side: the data exists in the project and the running display shows none of it. If every check comes back clean on the correct project, take the recorded evidence to the vendor's support entry for V7.4 SP1 instead of repeating the cycle.
Put the update level in the record, not first in the fix queue #
Two documented facts set the expectations. The Update 4 notes list one relevant correction: hierarchy changes in the Basic Process Control picture tree are displayed correctly in runtime from that level on. And the service line for V7.4 SP1 ran far beyond that — the documented line reaches Update 23 — so the current level has to be read from the vendor's support entry for V7.4 SP1, never assumed from memory.
Read the installed level from WinCC's own version information. The build string carries the update number in its fourth field: Update 17 ships as K7.4.1.17 and Update 23 as K7.4.1.23.
Worked example: version information shows K7.4.1.8. The fourth field is 8, and 8 ≥ 4, so the Update 4 hierarchy-display correction is already on the station — a missing navigator there cannot be explained by a missing update, which is exactly what the reported case showed with that build installed and the navigator still absent. If the dialog instead showed K7.4.1.3, then 3 < 4 and that specific correction is not installed; bringing the station current is then the right move, and the recorded cycle still decides between a save fault and a display fault. Keep the Windows build with that record, and confirm the WinCC and operating-system combination against the vendor's compatibility documentation before further software changes.
The decision, case by case #
- Marker edit appears in Runtime: persistence and project identity are proven. Fix the navigation presentation — startup picture, navigation display configuration, access levels — and leave the hierarchy alone. Re-saving the tree or reinstalling software does not address presentation.
- Marker edit gone when the manager reopens: the save is failing. Stop all runtime work and fix project persistence first — write access, disk state, which project copy you actually opened. Runtime cannot display a tree the project did not keep.
- Marker edit persists, correct project confirmed, navigator still absent: the change-save-restart loop is exhausted, and this is where the reported case ended with the update level current. Finish the checks above, then hand the evidence — build string, operating system, cycle outcome, manager and runtime screenshots — to the vendor's support entry for V7.4 SP1.
Questions asked
Does a newer WinCC update fix a missing Picture Tree Navigator?
Not by itself. Updates correct documented defects, and the correction for picture tree hierarchy display in runtime was included in the reported station's build level, yet the navigator still failed. Keep the build current for general correctness, then expect the persistence test and the display checks, not an update, to decide the outcome. Picture Tree Manager is a classic WinCC V7 tool; TIA-era panels use different navigation objects, so a fix written for one line does not transfer to the other.
Can a picture tree be moved into another WinCC project?
Yes. The process control option in WinCC documents export and import of the picture tree hierarchy between projects for reuse. If your project uses that option, bring in a tree from a project whose navigator works, save, restart runtime: if the imported tree appears, the manager tool and runtime are fine and the fault sits in the original project's tree data.
What evidence should a support request for this fault contain?
Record the exact WinCC build from version information, for example K7.4.1.8, the Windows build, the project path the runtime actually starts, a screenshot of the saved hierarchy in Picture Tree Manager beside the runtime display, the outcome of one reversible edit with its restart, and any message shown during activation. That set separates a persistence fault from a presentation fault before anyone changes software.
How many change-save-restart cycles are worth running?
One recorded cycle is enough to classify the fault. If the saved edit fails to persist, stop and fix saving; if it persists and the navigator is still absent, repeating the loop adds nothing, and the reported case had the sequence run many times with the fault unchanged. Move on to the project and presentation checks, and keep the before-and-after record from the single cycle as your evidence.