Troubleshooting
Why a WinCC V11 project will not start under Runtime V12
Short answer
A V11 project left in compatibility mode cannot start under Runtime V12, and recompiling does not change that. Run Project > Update so the project leaves V11, then right-click the HMI RT device in the device view and use Change device/version to set V12 before the final compile.

On this page
- Why will a WinCC V11 project not start under Runtime V12?
- How do I confirm the project is still in compatibility mode?
- Does recompiling hardware and software fix the mismatch?
- How do I update the project itself from V11 to V12?
- Why is Change device/version greyed out?
- How do I change the HMI RT device to Runtime V12?
- What happens to project data when the device version changes?
- Which steps run in what order to get the runtime started?
- Questions asked
A WinCC project created in TIA Portal V11 fails to start under WinCC Runtime V12 when the project is still stored at V11 and its HMI RT device still targets V11. Recompiling everything does not change the stored version, so the runtime keeps refusing the start. The fix is a version change in two places: run Project > Update so the project leaves compatibility mode, then in the device view right-click the HMI RT device, use Change device/version to set V12, and compile once more. This page walks through confirming the V11 tag in the project tree, the order of the two commands, what changing the device version does to data on the target system, and the decision between moving to V12 now or staying on V11 for the moment.
Why will a WinCC V11 project not start under Runtime V12? #
The project you built in TIA Portal V11 is still stored as a V11 project, and the WinCC Runtime V12 you installed only starts projects whose configured HMI RT device targets V12, so the launch fails no matter how often you recompile.
The runtime checks the version the project and its HMI station are configured for before it loads anything. A project opened in TIA Portal V12 without being upgraded stays at V11 in what the tool calls compatibility mode, and every compile you run inside that mode produces V11 output. Nothing in the project is broken; the two versions simply never match. The version pairing is the same rule that keeps an FWX compiled in WinCC flexible 2008 on 2008 runtime: a compiled project carries the version it was built for.
How do I confirm the project is still in compatibility mode? #
Open the project in TIA Portal and read the project tree: a project still at V11 shows the version tag V11 directly after the project name, which is the visible sign that it opened in compatibility mode instead of being upgraded.
The start failure itself does not hand you an error code naming the conflict, so confirm the version state in the tree and in the device configuration rather than by the error text. The HMI RT device inside a compatibility-mode project still carries its V11 configuration even though the tool on screen is V12. Worked example: take a project named Line1_HMI, created in TIA Portal V11 and opened in V12 without upgrading. The tree reads Line1_HMI V11, the HMI RT device reads V11, and Runtime V12 refuses the start. After Project > Update and Change device/version to V12, the tree reads Line1_HMI, the device reads V12, and the same compile-and-start sequence comes up.
| Check | V11 compatibility mode | After the update |
|---|---|---|
| Project tree, right of the project name | the tag V11 | no version tag |
| HMI RT device configuration | configured version V11 | configured version V12 |
| Start under Runtime V12 | fails | starts after one compile |
Does recompiling hardware and software fix the mismatch? #
Recompiling does not fix it: a full compile of hardware and software rebuilds the project exactly as it is stored, so a V11 project produces V11 output again and the V12 runtime rejects the same launch a second time.
Compile is not upgrade. The compiler reads the version stored in the project and rebuilds to that version; it never writes a new one, which is why a complete software and hardware rebuild leaves the start behavior unchanged. The stored version moves only through two commands, the project update and the device version change, and recompiling belongs at the end of that sequence, not in place of it.
How do I update the project itself from V11 to V12? #
Use the menu command Project > Update while the project is open in TIA Portal V12; it converts the stored project from V11 to V12, removes compatibility mode, and clears the V11 tag after the project name.
The command sits under the Project menu. It converts the stored project as a whole, the HMI station and any PLC stations included, and the documentation is explicit that projects from previous TIA Portal versions are upgraded to the version in use. Copy the project folder before you run the conversion: TIA Portal offers no downgrade of a converted project, so the untouched copy is your way back. When the conversion finishes, look at the tree again; the V11 tag must be gone before the device version step will do anything.
Why is Change device/version greyed out? #
The command stays greyed out because the project is still at V11: the HMI device's version can only be moved after the project update has converted the project, so run Project > Update, confirm the V11 tag is gone, and the command becomes available.
The device version cannot move ahead of the project version. While the tree still flags V11, the tool holds the HMI device at its V11 configuration and the right-click command on the device does nothing, which reads like a broken installation but is an unfinished update. Run the conversion, watch the tag disappear, reopen the device view, and the same right-click now opens the version list with the V12 entry in it.
How do I change the HMI RT device to Runtime V12? #
Double-click Devices & Networks in the project tree, select the HMI RT device in the device view, right-click it and choose Change device/version, then set the target to the V12 entry and recompile the project.
That is the documented path: Devices & Networks in the project tree, the HMI device selected in the device view, Change device/version. The same step serves panel targets as well as PC runtime; only the device you select differs. If the version list offers nothing valid for your target, a runtime device type that is not valid for the version is the neighboring fault to rule out. Once the device reads V12 and the compile finishes clean, start the runtime; the launch that failed on the V11 build now comes up.
What happens to project data when the device version changes? #
Changing between device versions deletes data on the HMI device: the TIA Portal documentation states that data on the target system is deleted when you change the device version, so back up before the change and plan to retransfer the compiled V12 project afterward.
For the PC runtime case this touches the runtime project data held on that workstation, not the editable source on the engineering side. Expect the retargeted runtime station to come up without that data and to be filled by the transfer of the freshly compiled project. Treat this as the one destructive step in the sequence; every other command only rewrites the engineering project.
Which steps run in what order to get the runtime started? #
The working order is copy the project, run Project > Update, change the HMI RT device to V12 with Change device/version, recompile all, then start Runtime V12; the runtime that refused the V11 project starts the retargeted one on the first attempt.
- Copy the project folder so the V11 source stays untouched.
- Open the copy in TIA Portal V12 and confirm the V11 tag in the project tree.
- Run Project > Update and check that the tag is gone.
- Open Devices & Networks, select the HMI RT device, right-click it, choose Change device/version and set V12.
- Compile the project.
- Start WinCC Runtime V12 and confirm the start screen loads.
The decision splits into two cases. If the machine has to run on the V12 workstation now, the six steps above are the whole job. If the schedule allows waiting, leave the project at V11 and run it under the V11 runtime it was compiled for; check what WinCC V11 needs to run a PC as an HMI before you touch that workstation. What never works is the mixed pair, a V11 project started by a V12 runtime. Match the versions on both sides, whichever side you choose.
Questions asked
Why does TIA Portal ask to upgrade the project when I open it?
The tool offers to upgrade a project from a previous TIA Portal version as you open it, and the documentation requires that upgrade before the project is worked on. Declining leaves the project at its old version: a V11 project then sits open in V12 in compatibility mode with the V11 tag after its name. Accepting the prompt performs the same conversion as Project > Update, so take the prompt when it appears and the version question is settled before any editing starts.
Does compatibility mode also affect PLC stations in the same project?
Yes, in a different way. A PLC station configured with STEP 7 V11 is reached for program upload in V12 through Compatibility Mode V11, the documented upload mode for devices configured in an older release. Updating the whole project to V12 removes that mode, so if a program upload from a V11-configured station is still pending, open Compatibility Mode V11 and do the upload first, then run the project update.
Does the same fix apply to a panel instead of a PC runtime?
The procedure is documented for the same family of targets: Basic Panels, Panels, Comfort Panels and the PC runtimes RT Advanced and RT Professional all take the Change device/version step from the device view. A panel still projected at V11 inside a V11 project needs the project update and the device version change just like the HMI RT station, and the same warning about data deletion on the target applies to it.