IMDTouchKnowledge BaseShop main store

Troubleshooting

Why Comfort Panel simulation fails with the pdata.fwc error

HMI and touchscreens Published 8 min read

Short answer

When Start Simulation on a Comfort Panel ends with the pdata.fwc configuration file could not be loaded and HmiRTm.exe stops, a TIA Portal V17 installed beside an older version has broken the shared simulation component: repair V17 from its DVD or ISO without uninstalling first, then apply all pending V17 updates. If only one project fails, delete the Diagnostic Viewer control from the screens and rebuild all software; as a last resort, recreate the HMI device.

On this page
  1. What does the pdata.fwc error mean at simulation start?
  2. Is the fault in my project or in the TIA Portal installation?
  3. Why does a parallel V17 installation break simulation in V14 to V16?
  4. How do you run the V17 repair installation correctly?
  5. Why do pending V17 updates still block the simulation?
  6. Why does the Diagnostic Viewer control stop only the simulator?
  7. How do you force a clean rebuild of pdata.fwc?
  8. What if the error survives the repair, updates and rebuild?
  9. Which fix applies to which case?
  10. Questions asked

When Start Simulation on a Comfort Panel such as a TP1200 ends with "pdata.fwc configuration file could not be loaded. The application will be terminated", the PC simulator has rejected the compiled panel configuration, and HmiRTm.exe, the runtime module behind the simulation, stops working. On a workstation where TIA Portal V17 sits beside an older version, the fix is a repair installation of V17 followed by its pending updates; where a single project fails, a Diagnostic Viewer control on a screen is the usual cause, and deleting it plus a full rebuild clears the message. Basic Panel projects keep simulating on the same PC throughout, which is the signature separating this fault from a dead runtime installation.

What does the pdata.fwc error mean at simulation start? #

The message means the PC simulation runtime could not read pdata.fwc, the compiled panel configuration that the compiler wrote under the project folder, so the simulator terminates instead of opening your screens. The dialog quotes the file with its full path — in one report ...\IM\HMI\{11866113-23184}\Generates\pdata.fwc — and Windows follows with "WinCC Runtime Advanced Module: HmiRTm has stopped working". That file is the compiled form of the screens, tags, alarms and schedules; when the simulator cannot load it, no picture opens at all. The panel hardware is not implicated: the same project loads and runs on the TP1200 Comfort (6AV2 124-0MC01-0AX0) while its simulation aborts.

Two neighbouring faults get mixed up with this one. A WinCC Runtime Advanced on a PC that fails at workstation start-up with the pdata.fwx message is a different fault with its own fix, covered in why the pdata.fwx configuration file could not be loaded. A crash of HmiRTm.exe on the panel itself during operation, rather than on the PC during simulation, is covered in fixing HMIRTM.EXE runtime crashes on a Comfort Panel.

Is the fault in my project or in the TIA Portal installation? #

Run two quick tests before touching anything: simulate a second Comfort project and a Basic Panel project on the same PC, because both failing points at the installation and only your project failing points at its compiled content. Work through the signs:

  • A second project with the same TP1200 simulating while yours aborts — the split seen in the earliest reported case — means the fault travels with the project content.
  • A Save As copy fails identically, so renaming the project launders nothing.
  • A Basic Panel simulating while every Comfort Panel aborts is the classic signature of the damaged shared simulation component, not of your screens.
  • Double-clicking the generated file in Windows Explorer starts the simulator standalone; the same message there confirms the file and runtime do not match, however the start is launched.
  • The installed-software details under the Help menu should list the WinCC simulator for your version; confirm it is present before deeper surgery.

The failure is reported on native Windows 7 Pro SP1 and Windows 8 Pro workstations with no virtual machine involved, so the PC environment is not the discriminator. A Unified Comfort Panel whose simulation will not start inside a VM is a separate fault with its own cause, covered in Unified Comfort Panel simulation fails in VMware.

Why does a parallel V17 installation break simulation in V14 to V16? #

The V17 setup changes a runtime and simulation component that the parallel installations share, so after V17 is installed beside V14 SP1, V15.1 or V16, Comfort simulation in the older versions aborts at load. Running several TIA Portal versions side by side is a supported arrangement, each version keeping its own projects, and the failure shows up only in some installation environments after the V17 setup. Support guidance for this message appearing at simulation start after a V17 setup is a repair installation of TIA Portal V17 — not of the version that fails — because the changed piece arrives with the V17 media. In one reported case, a PC with V14, V15.1 and V16, all fully updated, lost HMI simulation in the older two immediately after the V17 installation with its latest updates, and the V17 repair brought both back.

How do you run the V17 repair installation correctly? #

Mount the V17 DVD or ISO, start the installer with administrator rights, choose the repair option, let it finish and reboot; you do not uninstall anything first, because the repair restores the shared files in place. The sequence:

  1. Close every TIA Portal instance.
  2. Insert the TIA Portal V17 DVD or mount the V17 ISO and start the setup with administrator rights.
  3. Select the repair installation option — not uninstall, not modify.
  4. Let the repair run to completion, then reboot the PC.
  5. Open the version that failed, for example V16, and start the Comfort simulation again.

One engineer had already uninstalled and reinstalled the simulation runtime from the DVDs with no change, which fits the picture: the breaking piece comes with the V17 setup, so the V17 repair is the step that counts. If V17 is the only version on the PC and the message survives the repair, go straight to the updates before anything else.

Why do pending V17 updates still block the simulation? #

A V17 installation with unapplied updates can keep producing the message even after a repair, so open the TIA Update Service, install everything it lists as pending for V17, reboot, and simulate again. Two reported cases ended exactly this way: one confirms the link to V17 and names the pending updates as the cause, another ended when the V17 updates were completed. The check is quick — the updater shows the pending list per installed version, and V17 has to come up empty. Repair and updates are complementary: the repair puts the files back, the updates bring them to the level the simulation component expects.

Why does the Diagnostic Viewer control stop only the simulator? #

The Diagnostic Viewer compiles into pdata.fwc like any screen object and runs on the real panel, but the simulator on the PC rejects it, so a single placed control is enough to terminate simulation at load. You find it in the Controls tab of the toolbox, and its icon looks like a stethoscope; some screens call it a diagnostic overview. It simulated fine in earlier TIA versions, which is why a project that used to simulate can start failing after an upgrade.

In the confirmed case — TIA Portal V16 Update 4, a TP1200 with the viewer on one screen — recompiling and rebuilding from scratch changed nothing, and simulation returned the moment the object was deleted. Open every screen, delete the viewer wherever it sits, save, then rebuild the software as described next.

If the machine needs that diagnostic display, remember the control still runs on the panel; deleting it is the price of getting the simulator back for that project. Expect both causes at once: one report cleared a project this way while a second project on the same PC only came back after the V17 repair.

How do you force a clean rebuild of pdata.fwc? #

A clean regeneration comes from Compile > Software (rebuild all) on the HMI device, which rebuilds the runtime file and clears stale build data left behind by earlier compiles. The steps:

  1. Save a copy of the project first and keep it: if the rebuild alone cures the fault, the vendor's support team will want that copy to analyze the cause.
  2. Right-click the HMI device in the project tree and choose Compile > Software (rebuild all).
  3. Read the compile output and clear warnings such as tag type mismatches or missing PLC connections before judging the result.
  4. Start the simulation again.

Run the rebuild after every change above: a stale Generates folder inside the project's IM\HMI tree is one of the things it rules out, and it is mandatory after deleting the viewer so the runtime file no longer contains it.

What if the error survives the repair, updates and rebuild? #

Recreate the HMI device: insert a new device of the same type into the project, copy the tags, screens and connections across, delete the old device, compile and simulate — this cleared the original failing project after every other step had failed. A fresh device gets a new folder under IM\HMI, so whatever was poisoned in the old device's compiled data stays behind. One more check belongs here: if the project contains a SIMATIC PC Station, open its hardware configuration and set the WinCC RT module to the version matching your TIA Portal. One V13 project simulated again after that module was changed from version 11 to version 13.

Which fix applies to which case? #

Match the symptom to one of three cases: an installation-wide failure after a V17 setup takes the repair and the updates, a single failing project takes the Diagnostic Viewer removal and a rebuild, and a survivor takes the device recreation.

  • Case A — every Comfort project aborts, Basic Panels simulate, and V17 sits beside V14 SP1, V15.1 or V16: repair the V17 installation from its DVD or ISO, then clear the pending V17 updates. Reported outcome: the older versions simulate Comfort Panels again.
  • Case B — one project fails while others on the same PC simulate: delete the Diagnostic Viewer from every screen and run Compile > Software (rebuild all). Reported outcome: simulation back on V16 Update 4 with a TP1200.
  • Case C — the message survives both: recreate the HMI device and copy the content across, and where a SIMATIC PC Station is configured, align its WinCC RT module version with the TIA Portal version. Reported outcome: the original failing project simulated again after the device swap.

Work the cases in that order and stop at the first one that brings the simulation up.

Questions asked

Can I keep commissioning on the machine while the simulator is down?

Yes. Download the compiled project to the panel and keep working at the machine: the hardware runs the configuration normally, and only the PC preview is blocked. Schedule the repair and the updates on the engineering PC and the simulator returns without touching the machine.

Do I need to migrate the project to V17 to fix the error?

No. Every reported cure kept the project in its existing version: the repair installation and the pending updates restore simulation in the older version, and migrating the project does nothing to repair the component the V17 setup changed.

Could special characters in the project path be the cause?

Not as a first suspect. One test with an empty project on a path free of special characters produced the same message, so renaming folders rarely helps here; run the V17 repair and clear the pending updates before touching any paths.

Does the same message ever appear on the panel itself?

Yes, the vendor documents the message for the panel runtime at start-up as well. That occurrence is a device-side load failure with its own handling and is not fixed by the simulation steps in this article, which address the error thrown by Start Simulation on the PC.

Keep reading

  • Troubleshooting

    Unified Comfort Panel simulation fails in VMware

    In a reported TIA Portal V16 trial, Unified Comfort Panel simulation in VMware guests started after Activate secure download was cleared in WinCC Unified Configuration, with the same empty project. Run that as a controlled single-change diagnostic on an isolated engineering VM, and keep secure download active for transfers to a real panel.

    HMI and touchscreens

  • Troubleshooting

    Why the PDATA.FWX configuration file could not be loaded

    The message means the panel could not read the runtime configuration file its project generated, so it shut the application down. Save a backup, delete the generated PDATA file from the project, compile again, and prove the project starts clean on the PC runtime before redownloading. If the panel still fails, delete its stale copy from the flash storage folder the message names and download again.

    HMI and touchscreens

  • How-to

    Matching an HMI panel image to its TIA Portal project version

    The panel image must belong to the same TIA Portal release the HMI project was engineered in, so a V21 Update 2 project needs a V21 Update 2 image. The listing carries the V18 to V21 families, recommends V21 Update 2 for update, and from 4 September 2026 adds Service Releases with bug fixes only. Read the installed image from the panel, compare it with the project release, and move whichever side is behind.

    HMI and touchscreens

Why a Comfort Panel SendEmail fails with SMTP errors