IMDTouchKnowledge BaseShop main store

Troubleshooting

Why WinCC Flexible Shows an Empty Screen After Migration

HMI and touchscreens Published 7 min read

Short answer

WinCC flexible 2008 shows an empty screen at startup when its stored last-project location is a network station that is offline. Clear the recent-project entry under the WinCC flexible 2008 registry key, point it at a local folder, and migrate only from a local-drive copy. Do the ProTool migration on SP2, because SP3 removed the ProTool import, and keep the license key on either the XP virtual machine or the Windows 7 host, never both.

On this page
  1. Why does WinCC flexible open an empty screen after a migration?
  2. Why is the ProTool migration option missing in WinCC flexible 2008 SP3?
  3. How do you find the stored network path that breaks startup?
  4. How do you clear the recent project path in the registry?
  5. How do you migrate a ProTool project from a local drive?
  6. Can one WinCC flexible license cover the XP virtual machine and the Windows 7 host?
  7. What should you do when the empty screen still comes back?
  8. Questions asked

The empty screen is not a broken project: WinCC flexible 2008 stored the network station of your last session and cannot reach it, so it blocks every open and every new project until you clear that stored path. The fix is a five-minute registry edit, and the prevention is one habit — copy the ProTool archive to a local drive before you migrate. This article gives the registry fix, the SP2-only migration rule, the license answer for a virtual machine and its host, and the reinstall that remains when the edit is not enough.

Why does WinCC flexible open an empty screen after a migration? #

WinCC flexible 2008 opens to an empty screen when the last-used project path it has stored points at a network station that is offline: the tool tries to enumerate that share at startup, finds nothing, and refuses to open or create any project. The project itself is usually intact; only the remembered location is dead.

The failure pattern reported on stations like this is consistent:

  • Startup reaches the project browser normally, with no error dialog.
  • Choosing the migration command shows an empty list with no entries.
  • Creating a new project also fails or hangs, again without a message.
  • The behavior repeats on every launch until the stored path is corrected.

WinCC flexible keeps the last-used project location across sessions, so once a share goes offline the condition persists. Because there is no error code and no dialog, the symptom is easy to misread as a corrupted installation or a corrupted project; treat it first as a stored-path problem and only then reach for the heavier fixes.

Why is the ProTool migration option missing in WinCC flexible 2008 SP3? #

SP3 removed the ProTool import as a deliberate product change, so a station on SP3 cannot migrate a ProTool project at all; the conversion has to run on WinCC flexible 2008 SP2, which still carries the migration helper.

Station ProTool migration Role in the workflow
WinCC flexible 2008 SP2 Built in One-time conversion of the ProTool source
WinCC flexible 2008 SP3 Removed Engineering station for the migrated project

The workflow that follows from the table: convert on SP2, save the resulting project file to a local disk, then do all further development and commissioning on SP3. The SP3 station opens the converted project without difficulty; it simply cannot produce one from a ProTool source. This is a one-way version rule, and the same rule bites in the other direction — a 2007 station cannot open a 2008 project, as described in why WinCC flexible 2007 cannot open a 2008 project. Version-matched stations save hours of guessing.

The vendor's WinCC flexible 2008 migration manual, chapter 1.3, lists which source and target panel combinations migrate, so check the panel pair there before installing anything.

How do you find the stored network path that breaks startup? #

The stored location sits in the Windows registry under HKEY_CURRENT_USER\Software\Siemens\Automation\WinCC flexible\2008, in the values that keep the most recently opened projects; any value starting with two backslashes and a server name, for example \\proj-srv\hmi\op270\, is a path that can block startup when that server is down.

Open Registry Editor, expand that key, and read through the recent-project values. A local path such as C:\Projects\ is harmless. A UNC path naming a server, a share or a station is the suspect — especially one on a machine that has been powered off, renamed or removed from the network since the last migration. You do not need to guess which entry is the culprit; any recent entry referencing an unreachable station can trigger the behavior, so note all of them before editing.

How do you clear the recent project path in the registry? #

Close WinCC flexible, export the key as a backup, then delete or replace the value that holds the offline UNC path with a local folder such as C:\Projects\; the tool stops looking for the network station on the next launch.

  1. Close all WinCC flexible windows on the station.
  2. Open Registry Editor and navigate to HKEY_CURRENT_USER\Software\Siemens\Automation\WinCC flexible\2008.
  3. Export that key to a .reg file first, so the edit is reversible.
  4. Delete the value holding the last-used project path, or set it to a local folder such as C:\Projects\.
  5. Clear every recent-project value that references an offline share.
  6. Start WinCC flexible 2008 again and confirm that creating a new project works before you retry the migration.

What does a worked before-and-after look like? #

This example is illustrative, not a measured vendor test. On one migration station the last-used value held \\proj-srv\hmi\op270\ while the server was powered down; at startup WinCC flexible tried to list that station and showed nothing, and neither project creation nor the migration helper responded. After the edit, the same value read C:\Migrate\op270\, and on the next launch both project creation and the ProTool migration worked. Nothing else on the station had changed between the two launches, which is what pins the cause on the stored path rather than on the installation.

How do you migrate a ProTool project from a local drive? #

Copy the ProTool archive or project folder to the local disk of the SP2 station, for example to C:\Migrate\, run the migration helper from SP2's project menu, and browse to that local copy — never to the share.

The rest of the conversion is short:

  1. Copy the ProTool source, whether it is an archive or an unpacked project folder, onto the SP2 station's own drive.
  2. Run the migration helper in SP2 and select the local copy of the source.
  3. Let the wizard pick the matching target panel; if the hardware is being replaced, change the device type after the migration completes.
  4. Open the converted project in SP2 and check alarms, tag connections, screen layout and recipe data for completeness.
  5. Move the project file to the SP3 engineering station and continue there.

If the source used ProTool libraries, the import has its own pitfalls, covered in importing a ProTool .lib library into WinCC flexible. Checking libraries at the SP2 stage avoids discovering a missing screen object halfway through commissioning on the new panel.

Can one WinCC flexible license cover the XP virtual machine and the Windows 7 host? #

No: a virtual machine and its host are two stations under the license terms, so the key may be active on only one of them at a time; move it with Automation License Manager, or run the vendor's trial license on the migration station for the one-time SP2 conversion.

The documented flow is a check-out and check-in: release the key from the Windows 7 host in Automation License Manager, check it in on the XP guest for the duration of the conversion, then return it to the host before any SP3 work. The key is never valid on both machines simultaneously, and running the guest and the host at the same time calls for a second key. If the SP2 station exists only for this one conversion, the vendor's trial license covers that step and no permanent key has to move at all. There is no legitimate way to have one key serve both stations at once, and the check-out route is the supported alternative.

What should you do when the empty screen still comes back? #

When clearing the stored path does not restore project open and create, the remedy reported to work on these stations is a clean reinstall of WinCC flexible on that machine, followed by migration from a local-drive copy.

Treat the reinstall as the second step, not the first: it is slower, it re-creates your settings, and the registry edit resolves the majority of these cases on its own. After the reinstall, do not restore the old recent-project values, and keep the working rule that every ProTool source is copied to the local disk before migration. A project stored on a share afterwards is fine for backup; opening it across the network is what stores the UNC path again.

The decision for each case, then: an SP3 station cannot migrate, so install SP2 on a separate machine or virtual machine for the one-time conversion; an empty startup screen means clear the recent-project values in the registry and point them at a local folder; a license covers the XP guest or the Windows 7 host, one at a time, via Automation License Manager or a trial license; and a clean reinstall is the remaining fix when the stored-path edit does not clear it.

Questions asked

Does WinCC flexible 2008 SP3 ever regain the ProTool migration option?

No. The ProTool import was removed in SP3 and was never restored, so an SP3 station cannot convert a ProTool project. Keep one station on WinCC flexible 2008 SP2 for conversions, save the migrated project to a local disk, and continue all further engineering on SP3.

Where does WinCC flexible store the last project path?

In the Windows registry for the current user, under Software, Siemens, Automation, WinCC flexible, 2008. The values there keep the most recently opened project locations. Delete the one holding an offline server path or point it at a local folder, and export the key before editing so the change is reversible.

Can I store the migrated project on a network share afterwards?

Yes, as archive or backup storage. Open, edit and migrate from a local copy, though: if WinCC flexible remembers a server path as the last-used location and that share is offline later, the empty startup screen returns. Copy the project back to the local drive before each working session.

Is a trial license enough for the SP2 migration station?

For a one-time ProTool conversion, the vendor's trial license for WinCC flexible covers the SP2 step, so no permanent key has to live on that machine. Any station doing ongoing engineering needs its own permanent license, and a key may never be active on the virtual machine and the host at the same time.

Keep reading

  • How-to

    How to Migrate a ProTool HMI Project to a New Touch Panel

    A discontinued ProTool-era panel is replaceable without a rewrite only when the editable project file exists: migrate it under WinCC flexible 2008 with Service Pack 2, Advanced edition for ProTool Pro projects, then review every conversion message and adapt tags and screens for the chosen target. Without the .ptp file, budget the job as a rebuild.

    HMI and touchscreens

  • Troubleshooting

    MP377 frozen startup screen: recovery after an interrupted transfer

    When power drops during an MP377 project transfer, storage can end up incomplete and the panel hangs at the startup screen without loading its network or transfer services, so ping, ProSave and WinCC flexible all fail. The documented recovery is an operating system update with Reset to factory settings over the panel's recovery connection; a failed ping does not prove the loader is dead, and no project download will land until the OS is rewritten.

    HMI and touchscreens

  • Troubleshooting

    Importing a ProTool .lib library into WinCC Flexible

    WinCC flexible cannot import a ProTool .lib object library, and no utility converts .lib files to the .wlf format it expects. Plan the OP270-to-TP177 migration around reusing an existing .wlf library and rebuilding the remaining objects in the TP177 project, then verify each object on the panel.

    HMI and touchscreens

FactoryTalk Linx tag browser empty after shortcut setup