IMDTouchKnowledge BaseShop main store

Explainer

Why WinCC Professional full screen hides a second HMI runtime

HMI and touchscreens Published 6 min read By IMDTouch engineering team

Short answer

WinCC Professional Runtime in full-screen mode claims the entire work area of the extended desktop by design, so a co-resident Advanced Runtime is hidden behind it, not stopped. Run both runtimes in window mode with one window per monitor, because Advanced Runtime is not released for multi-monitor use and only one Professional Runtime runs in parallel on one operating system.

On this page
  1. Why does Professional Runtime stretch across both monitors?
  2. Is Advanced Runtime gone, or only hidden?
  3. Can Advanced and Professional Runtime share one PC at all?
  4. How do you switch Professional Runtime to window mode?
  5. Where do you place each runtime window?
  6. What size should each runtime window be?
  7. When is a virtual machine the better isolation?
  8. How do you test the arrangement before commissioning?
  9. Questions asked

When WinCC Professional Runtime runs in full-screen mode on a dual-monitor PC, it claims the entire Windows work area of the extended desktop, so the Advanced Runtime behind it is hidden, not dead. The fix is window mode in both runtimes with one window per monitor: Advanced Runtime is not released for multiple-monitor operation, and only one Professional Runtime may run in parallel on one operating system. This article gives the reason, the setting, the window arithmetic and the test sequence.

Why does Professional Runtime stretch across both monitors? #

In full-screen mode, Professional Runtime claims the complete Windows work area of the extended desktop; with two 1920 × 1080 monitors side by side that is a single 3840 px wide surface, so the whole second monitor belongs to Professional. This is documented system behavior, not a fault: full-screen is the default display mode of the runtime software, and the mode does not stop at a physical monitor boundary.

The extended desktop means Windows merges both monitors into one coordinate space while each display keeps its own resolution. A full-screen application is entitled to that combined space. Your installation is therefore behaving exactly as configured, and the missing Advanced pictures are simply underneath the claimed surface.

Is Advanced Runtime gone, or only hidden? #

Advanced Runtime is only hidden: its process, PLC connections and alarm handling keep running behind the full-screen Professional surface, so data collection continues even though no operator can see or touch the Advanced pictures. Do not fix the symptom by forcing Advanced to the foreground. Focus order is temporary; the full-screen surface still owns the same desktop area and takes it back at the next focus change.

Window mode removes the overlap instead of fighting it. Once Professional runs as a bounded window, the second monitor's work area stays visible and available, and Advanced can occupy it permanently.

Can Advanced and Professional Runtime share one PC at all? #

Yes: one Advanced Runtime and one Professional Runtime can run side by side on one PC because they are built on different runtime bases, but the hard limit is one Professional Runtime in parallel per operating system. A second Professional instance on the same machine is not an option; if you ever need one, it has to live in a virtual machine.

Before counting runtimes, confirm what is actually installed on the machine, as the article on whether a WinCC Professional entry means SCADA runtime is installed explains. An engineering entry alone does not prove a runtime is present, and a missing runtime looks exactly like a hidden one on a busy desktop.

How do you switch Professional Runtime to window mode? #

Clear the full-screen option in the engineering project: open the Settings editor, click General, deactivate the Full-screen mode check box in the Screen field, then compile and load the project. This is the documented display configuration that decides how the runtime presents its screen at startup, and because full-screen is the default, an untouched project always masks everything behind it.

Apply it in this order:

  1. Stop Professional Runtime through its normal shutdown path.
  2. Open the project's Settings editor and clear the full-screen option as above.
  3. Compile and load the changed project.
  4. Start the runtime and confirm it appears as a bordered, movable window.
  5. Move the window onto the monitor assigned to Professional.

Changing only the picture layout inside the project would leave the claim on the whole work area untouched; the check box is what constrains the runtime.

Where do you place each runtime window? #

Place each runtime window completely inside one monitor: Professional on the display you choose as primary, Advanced on the other, following the Windows display diagram that defines where the boundary between the two lies. A monitor placed to the right of the primary display begins beyond the primary display's horizontal edge; a monitor placed to the left uses negative horizontal coordinates. Runtime placement follows that map, so changing the primary monitor or rearranging the displays later can push a window onto the wrong screen.

Keep the desktop in extended mode, not duplicated: a duplicated desktop shows the same coordinate space on both monitors and makes the one-window-per-monitor arrangement impossible. Match the top and bottom edges in the display diagram to the physical installation so the pointer crosses at the intended boundary.

Positioning one runtime's pictures across two monitors is a different task, covered in how one HMI runtime places windows on two monitors; here you are keeping two runtimes apart instead of spreading one across both displays.

What size should each runtime window be? #

Size each window to the picture with uniform scaling: on a 1080 px high monitor with a 48 px taskbar (an example value), only 1032 px of height remain, so a 16:9 picture fits at about 1835 px wide. Worked example with the common dual-monitor station:

Example input Value
Monitor resolution, both displays 1920 × 1080
Project resolution, both runtime projects 1920 × 1080
Taskbar height (example) 48 px

The arithmetic for one window:

  • Available height: 1080 px − 48 px = 1032 px.
  • Uniform 16:9 width at that height: 1032 px × 16 ÷ 9 = 1834.7 px, so about 1835 px.
  • Resulting window: about 1835 × 1032 px, with the picture scaled uniformly inside it.

If you want the picture at 1:1 instead, hide the taskbar and remove the window frame so the full client area fits the monitor. Never stretch the picture non-uniformly to fill a window: distorted controls and text make operator interaction unreliable. After sizing, exercise the navigation and alarm controls nearest all four picture edges and confirm none is clipped.

When is a virtual machine the better isolation? #

Use a virtual machine only when window mode cannot hold the separation in production: run Professional inside the virtual machine, dedicate one monitor to the virtual-machine display, and leave Advanced on the host on the other monitor. This gives a hard display boundary that no focus change can undo, but it also adds a guest operating system, processor and memory allocation, device access, startup coordination and licensing checks, each of which you validate against the documentation of the installed software.

Window mode needs none of that, so it is the first choice. Reach for the virtual machine only after the window arrangement has failed the startup test below for a reason you cannot remove.

How do you test the arrangement before commissioning? #

Test in the production startup order: start Professional first and confirm its window stays on its monitor, then start Advanced and confirm its position, then repeat both checks under the automatic startup sequence the machine really uses. Simultaneous starts can produce focus effects that never appear when you start each runtime by hand.

Run this sequence and record the result at each step:

  1. Start Professional Runtime. Expect a bordered, movable window, with the second monitor's work area fully visible.
  2. Start Advanced Runtime and move its window completely onto the second monitor. Expect every edge control to remain visible and selectable.
  3. Switch focus between the two runtimes in both directions. Expect each window to stay on its assigned monitor.
  4. Trigger the production auto-start and repeat steps 1 to 3, because that is the sequence the operators will actually see.

The decision: sign off when both windows survive step 4 with Advanced reachable and Professional confined to one display. If they do not, the cause is a remaining full-screen setting or a startup script, not the hardware — and the window-mode configuration above is where you correct it.

Questions asked

Can a script switch Professional Runtime back to full screen later?

Yes. The system function SetDisplayMode changes the screen settings while runtime is running, and full-screen is the default display mode, so a call from a startup script or a scheduled trigger can undo the window configuration made in the engineering project. Search the project for that function before blaming the settings editor when the runtime goes full screen again after a restart.

Does matching the project resolution to the monitor resolution prevent the overlap?

No. The full-screen work-area claim is independent of the configured picture resolution; resizing pictures only changes what is drawn inside the claimed area. Clearing the full-screen option is what confines Professional to a window, so do not spend commissioning time on resolution experiments to fix a hidden Advanced Runtime.

Why not run Advanced in full screen on one monitor instead?

Advanced Runtime is not released for multiple-monitor operation, and its full-screen behavior on an extended desktop is not a documented single-monitor guarantee. The released arrangement on a two-monitor station is a movable window sized to one display, which keeps both runtimes visible and inside their documented operating boundaries at the same time.

Keep reading

  • Troubleshooting

    What WinCC V11 needs to run a PC as an HMI

    WinCC V11 Professional in TIA Portal configures and downloads HMI projects; it does not make the PC a runtime station by itself. To run the PC as an HMI you install WinCC Runtime Advanced for panel-class projects or WinCC RT Professional for SCADA, each on its own runtime license. When the Advanced setup stops at the Sebu_winccv11 check, the image carries classic SIMATIC packages the V11 SP2 compatibility list does not clear, so clean the machine and reinstall.

    HMI and touchscreens

  • Selection guide

    Runtime tag license tiers for an HMI panel PC

    Buy the engineering license for your own PC; the panel PC needs a WinCC flexible runtime license sized to controller-connected tags in tiers of 128, 512, 1024, 2048 and 4096, plus a separate recipe license for native recipes. An array counts as one tag and an indexed variable as several, but array elements cannot carry the per-element limits recipe setpoints need.

    HMI and touchscreens

  • Explainer

    Why runtime passwords do not restrict offline HMI screen edits

    No. Runtime user administration authorizes actions inside the running HMI and does nothing to the editable project on the engineering workstation. To restrict offline HMI screen modification you control the project folder, the engineering tool login and the transfer path as three separate boundaries; only a safety program's own protection gives F-PLC-style defense.

    HMI and touchscreens

HMI boots to black screen instead of browser favorite