Why WinCC Runtime Advanced runs only one instance per PC

HMI and touchscreens Published 5 min read By IMDTouch engineering team

Short answer

WinCC Runtime Advanced enforces a single production runtime instance per PC, with no documented equivalent of the WinCC flexible OnlyOneInstance=False setting. Multiple simultaneous RT Advanced simulations have been demonstrated on TIA Portal 17, but that is not a supported production arrangement. Consolidate into one project or use separate runtime hosts.

On this page
  1. What changed between WinCC flexible and TIA Portal
  2. Separate the four arrangements that get confused
  3. What a second launch actually does
  4. The simulation result and why it is not a deployment recipe
  5. Worked example: two projects of 300 and 200 tags against a 512-tag license
  6. The decision for each case
  7. Questions asked

WinCC Runtime Advanced runs exactly one production runtime instance per PC. There is no documented switch equivalent to the WinCC flexible HmiRTm.ini setting OnlyOneInstance=False, and searching the installation folders for such a file finds nothing because the single-instance limit is built into the runtime application itself. The supported deployment options are one consolidated project on the PC, or separate runtime hosts, one per project.

What changed between WinCC flexible and TIA Portal #

Under WinCC flexible, starting several runtime instances with different projects on the same PC was straightforward. The only requirement was that the sum of all tags across the running projects stayed within the license size, and single-instance enforcement could be disabled in HmiRTm.ini with the key OnlyOneInstance=False.

Runtime Advanced in TIA Portal dropped that mechanism. An engineer on TIA Portal 15.1 Update 3 searched the usual locations for .ini and .xml files carrying that setting and found none, which matches how the newer runtime is built: the application prevents a second independent copy from starting internally, rather than reading a switch from an editable file.

If you are still running projects designed in the older tool, the article on the WinCC flexible 2008 lifecycle and the Runtime Advanced license covers what that transition means for runtime licensing.

Separate the four arrangements that get confused #

Before hunting for a configuration switch, identify which arrangement the application actually needs, because they have different consequences:

Arrangement What it establishes Deployment consequence
Several screens in one runtime project One application presents several views No separate instances needed; this is the supported way to serve several views
Several engineering windows open at once The engineering station works on multiple projects A configuration-tool behavior, not a runtime behavior
Several simultaneous simulations Projects can execute concurrently in simulation Demonstrated on TIA Portal 17, but it does not prove production support or license coverage
Several independent production runtimes Separate projects run as operational HMIs Enforced to one instance; needs explicit release and licensing confirmation to change

The first row is the decision for most requests that look like a multi-instance problem: if the goal is several operator views of one machine, one project with several screens already does it.

What a second launch actually does #

Single-instance enforcement means the second launch does not open a second project. Depending on the release, the second start either hands focus back to the running application or stops before any new project becomes operational. That is different from a runtime that starts and then fails because of a communication path, a missing authorization or a resource conflict — those failures are diagnosed in the article on HMIRTM.EXE runtime crashes on a Comfort panel.

Capture the behavior before changing anything: record the exact release and update, start the first project normally, launch the second through its normal path, and note whether the first application gets focus, a message appears, or a second process briefly starts. A repeatable, classified symptom is what a support case needs.

The simulation result and why it is not a deployment recipe #

A test on TIA Portal 17 showed that simultaneous Runtime Advanced simulations are possible when an HmiRtm.ini file is created in the C:\Siemens\TIAPortal\WinCC RT Advanced directory. That observation is real, but it stays a test observation for three reasons:

  • The complete file contents and launch procedure were not documented, so it is not a reproducible configuration.
  • A result on TIA Portal 17 says nothing about behavior on 15.1 Update 3 or any other release.
  • A simulation launch path does not establish what the production runtime does, and an unsupported arrangement leaves you without vendor help when it misbehaves. The article on AVEVA System Platform on Proxmox makes the same point for a different product: it runs, but the vendor does not support it, and that gap shows up exactly when you need help.

Parallel installation of engineering and runtime software has its own documented restrictions in the TIA Portal installation notes, and those notes govern what may coexist on one PC at the installation level, independent of the runtime instance question.

Worked example: two projects of 300 and 200 tags against a 512-tag license #

This example shows how the old WinCC flexible rule was applied, using example numbers; check your own project tag counts and license size before reusing the arithmetic.

Inputs: project A is configured with 300 tags and project B with 200 tags, both example counts from the project tag lists; the PC holds a 512-tag runtime license, a size that existed in the tag-count license scheme.

The rule under WinCC flexible: the sum of tags across all simultaneously running instances must not exceed the license size.

Arithmetic: 300 tags + 200 tags = 500 tags. 500 tags is less than or equal to 512 tags, so both projects fit one license and both runtimes may start.

Result: under WinCC flexible, this PC runs both projects after OnlyOneInstance=False is set.

Decision: under Runtime Advanced, the license arithmetic is necessary but not sufficient. The single-instance limit stops the second project regardless of the tag count, so the same requirement resolves to consolidating both projects into one runtime project (counting its total tags, here 500, against the license), or to deploying a second runtime host. Confirm with vendor support how the exact Runtime Advanced release licenses concurrent instances before ordering licenses for a two-host layout.

The decision for each case #

  • You need several operator views of one machine: build one runtime project with several screens. No instance question arises.
  • You need to test two projects side by side: simulation is the legitimate path; the TIA Portal 17 result shows it is technically possible, with the caveats above.
  • You need two independent production HMIs on one PC: Runtime Advanced will not run them as two instances. Either merge the projects into one runtime, accounting for the combined tag count against the license, or run the second project on its own PC or panel. When the second operator station means new panel hardware, the page on industrial panel PCs and touchscreen computers is the place to compare a PC-based runtime host against a dedicated terminal.
  • You believe your release is different: put the exact release and update in a support request and get a written determination on instance support and licensing for that release. Do not carry the flexible-era combined-tag assumption forward on its own.

One safety note: any arrangement the vendor has not documented is unqualified for a machine that will run. Keep unsupported configurations on the bench.

Questions asked

Does the OnlyOneInstance=False setting exist anywhere in TIA Portal Runtime Advanced?

No documented equivalent has been published for Runtime Advanced. The setting lived in HmiRTm.ini under WinCC flexible, and searching TIA Portal installation folders for .ini and .xml files with that key typically finds nothing, because the single-instance behavior is enforced by the runtime application itself rather than by an editable file. Changing instance behavior therefore needs a release-specific statement from the vendor, not a hand-edited file.

If two Runtime Advanced projects run at the same time on a test PC, is that deployment supported?

A process that starts is not a supported arrangement. Concurrent simulations have been demonstrated on TIA Portal 17 after creating an initialization file in the RT Advanced folder, but a simulation launch path does not establish production behavior, and support for the arrangement and its licensing has to be confirmed in writing for the exact release before it goes on a machine that will run.

How does WinCC flexible licensing differ from Runtime Advanced licensing for several projects?

Under WinCC flexible, multiple runtime instances on one PC were accepted as long as the combined tag count stayed within the license size, and that combined-count rule was enforced by the HmiRTm.ini configuration. Runtime Advanced licensing has to be resolved separately: ask the vendor how the exact release licenses concurrent runtime instances and tag counts, rather than assuming the earlier combined-tag rule carries over.

Keep reading

  • Explainer

    Why WinCC Runtime V13 cannot run two instances on one PC

    WinCC Runtime Professional V13 SP1 runs as a single instance on a PC, so you cannot start one Runtime per monitor. Two independently operated screens need the WebNavigator option: the server component runs with Runtime, each monitor gets its own client session in a browser or the WinCCViewerRT.exe viewer, and each session occupies one WebNavigator license at the server. If both seats share control, one Runtime with windows on both monitors does the job with no extra option.

    HMI and touchscreens

  • Troubleshooting

    What WinCC V11 needs to run a PC as an HMI

    WinCC V11 Professional in TIA Portal configures and downloads HMI projects; it does not make the PC a runtime station by itself. To run the PC as an HMI you install WinCC Runtime Advanced for panel-class projects or WinCC RT Professional for SCADA, each on its own runtime license. When the Advanced setup stops at the Sebu_winccv11 check, the image carries classic SIMATIC packages the V11 SP2 compatibility list does not clear, so clean the machine and reinstall.

    HMI and touchscreens

  • How-to

    Running a WinCC 7.0 project on another PC without a new build

    No. WinCC has no compile-to-EXE option: the destination PC needs WinCC Runtime of version 7.0 or higher, installed and licensed, and you transfer the project files to it. A newer WinCC opens and converts the project; an older release will not open it.

    HMI and touchscreens

Moving a TP1500 Comfort project to WinCC Runtime Advanced