Why WinCC Runtime Advanced V12 has no standalone installer

HMI and touchscreens Published 6 min read

Short answer

The WinCC Professional V12 setup offers no runtime-only installation. Either install the full package, about 4 GB, and uninstall everything except WinCC Runtime Advanced V12 and the License Manager, which leaves roughly 50 MB, or install from the separate runtime DVD delivered with a purchased runtime license; either way the HMI PC needs its own valid license key.

On this page
  1. Can you install WinCC Runtime Advanced V12 standalone?
  2. Why does the engineering installer offer no runtime-only option?
  3. How much disk space does the full installation need?
  4. How do you strip a full installation down to the runtime?
  5. What stays on the disk after the strip-down?
  6. What does the separate runtime DVD contain?
  7. Does the HMI PC still need the License Manager and a license key?
  8. Which installation path should you choose?
  9. Questions asked

WinCC Runtime Advanced V12 has no standalone installer on the engineering media: the WinCC Professional V12 setup offers no runtime-only selection, so when you search its product list for the runtime alone, you find nothing. A small PC that will serve only as the HMI still gets its runtime, by one of two routes. Either install the complete package and then uninstall everything except the runtime and the License Manager, which leaves a runtime-only footprint on the disk, or install from the separate runtime DVD that is delivered with a purchased runtime license. Both routes end with the same two components and one requirement: a valid license key on the runtime PC itself.

Can you install WinCC Runtime Advanced V12 standalone? #

Yes, but not from the engineering setup: the WinCC Professional V12 installer offers no runtime-only option, so a standalone runtime PC is built either by installing the full package and removing the engineering components, or by installing from the separate runtime DVD.

The product itself is meant for exactly this deployment: the vendor positions WinCC Runtime Advanced as visualization software for single-user, machine-oriented tasks, one PC at the machine with no engineering needed there. The obstacle is only how the installer is delivered, not what the runtime can do.

Why does the engineering installer offer no runtime-only option? #

Because the runtime is not a product of its own on that media: the WinCC Professional V12 setup installs the engineering system and the runtime as one package, and its product selection never lists the runtime by itself.

So the missing entry is not a broken DVD or an incomplete download; the V12 engineering media is built this way. The runtime therefore reaches a PC through one of the manufacturer's two deliveries: the engineering media, with the strip-down described below, or the runtime DVD that belongs to the runtime license. Installer files offered outside those deliveries are not a source you put on a production HMI PC.

How much disk space does the full installation need? #

About 4 GB: a full WinCC Professional V12 installation, including the whole TIA Portal engineering system, needs roughly that much hard-disk space before anything is removed.

That figure is field-reported from real installations rather than a documented minimum, and it shifts a little with the components the setup adds. Its size is the whole complaint: on a compact HMI PC with a small solid-state disk, the engineering framework is the bulk of the consumption and does nothing at the machine. It is also temporary, because the strip-down removes almost all of it.

How do you strip a full installation down to the runtime? #

Install WinCC Professional V12 completely first, then uninstall every component in the Windows program list except two, WinCC Runtime Advanced V12 and the License Manager, and confirm the runtime still starts.

  1. Run the WinCC Professional V12 setup to the end, engineering system included, and complete any restart it asks for.
  2. Open the Windows program list and uninstall each component except WinCC Runtime Advanced V12 and the License Manager; TIA Portal, the engineering system and the accompanying tools all go.
  3. Transfer the runtime license key to the PC, then start the runtime and load the compiled project file generated on the engineering PC, to prove the stripped installation runs.

The order matters: the full setup is what places the runtime on the disk, so the uninstall pass comes after it, never instead of it.

What stays on the disk after the strip-down? #

Roughly 50 MB: with everything removed except WinCC Runtime Advanced V12 and the License Manager, the HMI PC carries a runtime-only footprint instead of the engineering installation.

Worked example on the reported figures, so you can see the ratio. Take the installed package as about 4 GB, which is 4,000 MB at 1,000 MB per GB, and the stripped result as about 50 MB. Removed: 4,000 MB − 50 MB = 3,950 MB. Remaining: 50 MB ÷ 4,000 MB = 0.0125, so 1.25% of what the setup installed stays on the disk and 98.75% is gone. Both inputs are approximate field values, so use the result as a planning ratio for a small flash disk, not as a guaranteed figure for every PC.

What does the separate runtime DVD contain? #

Only the runtime installation: a runtime license bought with media comes as its own DVD that sets up just the runtime on the HMI PC, with no engineering components to remove afterwards.

The delivery split has history: for V11 the Advanced Engineering System came on a single DVD and runtime media was a separate disc, tied to the runtime license purchase. The same split answers the V12 question — whoever holds only the engineering DVD will never find a runtime-only setup on it, because runtime-only media belongs to the runtime license. For a dedicated HMI PC this is the cleanest route: nothing to uninstall, and the engineering framework never touches the disk.

Does the HMI PC still need the License Manager and a license key? #

Yes: the runtime is licensed software, so the License Manager stays on the runtime PC and a valid runtime license key must be transferred to that same PC before the HMI application is put into service.

The key has to reside on the machine that runs the runtime, not only on the engineering station. Moving it is the procedure covered under transfer a WinCC license from USB key to hard disk, and whether a key is an RT or an RC key is the difference explained in WinCC RT vs RC licenses and moving a runtime key. This is the one point not to improvise: the runtime runs only with its valid license in place.

Which installation path should you choose? #

Take the runtime DVD whenever it is available, because it installs exactly what the HMI PC needs; fall back to the full install and strip-down only when the engineering media is all you have.

Path Prerequisite What stays on the disk Work after installation
Runtime DVD A runtime license delivered with its DVD The runtime only, no engineering parts Transfer the license key, then start the runtime
Full install, then strip down The WinCC Professional V12 engineering media The runtime and the License Manager Uninstall every other component, then transfer the key

Both rows end at the same place: a runtime PC with its license in place. Close the job by loading the compiled project and watching it run through a restart, then set the machine to launch the application the way described for a desktop shortcut for WinCC Runtime Advanced, so the operator never sees the desktop.

Questions asked

Does removing TIA Portal from the HMI PC break later project updates?

No. Project changes are made on the engineering PC, where the edited project is compiled into a new runtime file, and that file is copied to the HMI PC and loaded there. The runtime machine never needs the engineering system for updates, only the runtime and the License Manager.

Does the strip-down method apply to newer WinCC versions?

Treat it as the V12 answer. By V16 the runtime is delivered as its own package, with the software and documentation on DVD and the license key on a USB flash drive, so a purchased runtime license brings its own media and nothing has to be uninstalled. Check the delivery contents stated for the exact version being licensed.

How many runtime licenses does a site with several HMI PCs need?

One per runtime PC. Every installation checks for a valid license key on its own machine, so a site with three runtime PCs needs three runtime licenses, and each delivered key is transferred to the PC that will run it.

Keep reading

  • Troubleshooting

    Why WinCC Runtime Advanced Has No Screens Folder

    The Screens folder is missing because the installed engineering edition cannot configure a WinCC Runtime Advanced PC station: WinCC Basic covers panels only. Install WinCC Advanced or Professional, license it, add the PC station in a new clean project, and the tool generates the folder. The proxy-device message is a later check, and reinstalling TIA Portal does not fix it.

    HMI and touchscreens

  • Troubleshooting

    Why WinCC Logging for Runtime Advanced asks for a license

    The message means the runtime computer holds no valid option key for historical logging; the base WinCC Runtime Advanced license never covers it. Order WinCC Logging for Runtime Advanced (6AV2107-0GA00-0BB0), one per operator station, and install or transfer the key with Automation License Manager; keys from generators or copied folders do not clear it.

    HMI and touchscreens

  • Troubleshooting

    Why WinCC Flexible Smart V3.2 Has No English Interface

    WinCC flexible Smart V3.2, the engineering tool for the Smart 700 IE V3, is China-market software with a Chinese-only interface: no English edition, language pack or language setting exists, and the Windows system locale only gates the installer. Correct operator texts through the Chinese interface, or migrate to an HMI family engineered by a tool with several interface languages.

    HMI and touchscreens