Why WinCC Unified Autologin Works Only on the Runtime Server

HMI and touchscreens Published 5 min read By IMDTouch engineering team

Short answer

The automatic login you enable in SIMATIC Runtime Manager authenticates only a browser session opened on the WinCC Unified Runtime server itself. A browser on another computer is an external web client and always requires its own login, even when the server-side autologin user and password are configured correctly.

On this page
  1. What the Runtime Manager autologin setting does
  2. Why a remote web client still shows the login screen
  3. Confirm which case you have
  4. Options for an unattended remote station
  5. The decision
  6. Questions asked

The automatic login you enable in SIMATIC Runtime Manager authenticates only a browser session opened on the WinCC Unified Runtime server itself. A browser running on any other computer is an external web client, and it will always show the login screen, no matter how carefully you configure the autologin user on the server. When autologin seems broken, the configuration is usually fine; the browser is simply on the wrong side of the documented boundary. This article explains what the setting does, why a remote client cannot use it, how to confirm which case you have, and what to do when the remote station must start without user interaction.

What the Runtime Manager autologin setting does #

Automatic login is disabled by default. To enable it on a PC runtime, open the SIMATIC Runtime Manager as administrator, select the "General" tab, and under "Automatic login" activate the enable setting and store the user credentials. Its documented purpose is to simplify login and spare the operator from entering a user name and password every time the runtime starts.

The setting stores one user context that the runtime applies to a connection made from the server itself. That is a convenience feature for a local session, not an authentication service for other machines. Nothing in the setting hands credentials to a browser that connects over the network.

Why a remote web client still shows the login screen #

The runtime documentation draws the line explicitly: automatic login works only for the connection from the server itself, and all external clients need a login. A Chrome session on a separate Windows 10 IoT LTSC station, or on any other PC, tablet or panel in the plant, is an external client in that sense.

A headless runtime changes nothing. If the runtime runs in a VM under ESXi with no user interface on the server, the boundary still sits where the browser runs. Moving the runtime to another machine, or giving the server more resources, cannot extend the setting to a remote browser. The scope of where WinCC Unified runtime can run and which remote options exist is covered in Where WinCC Unified Runtime Can Run and Remote HMI Options.

Repeatedly re-entering the Runtime Manager credentials for a remote-client problem is a dead end when the credentials are valid. Classify the browser session by location first; the fix depends on the classification, not on another attempt at the same configuration.

Confirm which case you have #

Worked example. A project runs on WinCC Unified V18 Update 3 on Windows Server 2022 Standard in an ESXi VM. Chrome runs on a separate Windows 10 IoT LTSC client. Run the two tests below and compare:

  1. Restart the runtime, then open a browser on the Runtime server and connect to the local runtime address. With the "Automatic login" setting enabled and valid credentials stored, this session authenticates without a login prompt.
  2. Restart the browser on the remote station, open the same runtime address, and observe the login screen appear.

The expected outcome is a split result: the server-local browser logs in automatically, the remote Chrome session asks for credentials. That split is not a fault. It matches the documented scope exactly, and it proves the Runtime Manager configuration works. If the local connection also prompts for a login, then you have a real configuration problem: check that the setting is enabled under the "General" tab, that the stored user exists in the project, and that the firewall allows the connection. Distinguish the two cases before changing anything.

Options for an unattended remote station #

If the remote station must show the screen without user interaction, the server-side setting cannot deliver it. You have two practical paths.

The first is a client-side automatic login. Community browser extensions exist for Chrome that supply the user name and password from the client, logging into the Unified website locally or remotely; one documented approach requires the project's start screen to contain a button with a LogOff system function so the extension can manage the logout flow. Treat these as projects built against a specific runtime version, not as a documented runtime feature: verify compatibility with your exact runtime version, and review credential handling before production use, because a login passed in a URL can appear in browser history and logs.

The second is to accept a login on the remote client and make it cheap and safe. Set up a dedicated runtime user with only the function rights that station needs; the setup of users and rights is described in Configuring WinCC Unified user administration and function rights, and the routine handling of accounts and password changes is covered in How to Manage WinCC Runtime User Accounts and Password Changes.

One security note: whichever path you pick, do not widen the server-side autologin user's rights to compensate. That user authenticates every local session on the server, so keep its rights minimal and give remote stations their own scoped accounts.

The decision #

Two cases, two decisions. If the operator station is the Runtime server itself, enable automatic login in SIMATIC Runtime Manager, verify with a local browser, and stop there: the feature works as documented. If the station is any other computer, the login screen is the correct behavior, not a bug: either deploy a validated client-side automatic login after checking version compatibility and credential handling, or give that station its own minimal runtime user and accept the login. Reconfiguring the server-side autologin will never close the gap for a remote client, because the documented scope puts remote clients outside it.

Questions asked

Can Runtime Manager autologin authenticate a WinCC Unified web client on another computer?

No. The automatic login documented for SIMATIC Runtime Manager applies to a browser connection made from the Runtime server itself. A browser on another computer is an external web client, and the documentation states that all external clients need a login. Re-entering valid credentials in Runtime Manager will not change that boundary.

Does running the WinCC Unified runtime in a headless VM change the autologin scope?

No. The boundary is where the browser runs, not where the runtime runs. A runtime on a VM without a user interface does not extend autologin to other machines. A browser on any other computer still presents the login screen, because the setting covers only the connection made from the server hosting the runtime.

How can an unattended remote station open a WinCC Unified screen without user interaction?

The server-side setting cannot do it. Community browser extensions exist that pass a user name and password from the client side, but they were built against specific runtime versions. Validate compatibility with your runtime version and review how the extension handles credentials before deploying one, since a login passed in a URL can end up in browser history.

Keep reading

  • How-to

    WinCC Professional V15 multiuser client runtime setup

    In TIA Portal V15, a WinCC Professional multiuser application is a client/server runtime split: one PC runs WinCC Runtime Professional as the server that owns the PLC connections, and each operator station runs a runtime client pointed at that server. The WinCC Explorer workflow from V7 does not apply, and installing the engineering package alone gives no PC a runtime role.

    HMI and touchscreens

  • Troubleshooting

    Why a WinCC server IP change freezes all HMI clients

    Treat the synchronized freeze as a server-side fault with two leads: pin the process server to its fixed address instead of dynamic addressing, and find any add-on such as OPC software running on a demonstration license whose documented runtime limit matches the interval between freezes. Rebooting only resets the running session. Run the server without its SCADA software to rule the machine itself in or out.

    HMI and touchscreens

  • Explainer

    Unified Comfort panel OPC UA client and server roles in V17

    From V17, a Unified Comfort Panel offers both an OPC UA server and an OPC UA Data Access client, so it exchanges process data with a third-party controller in either direction. Each connection pairs one server endpoint with one client; two clients cannot talk to each other. Unified PC Runtime adds the connection to OPC UA servers in V17; pick the panel's role from what the controller's specification says it provides.