IMDTouchKnowledge BaseShop main store

Explainer

Binding WinCC Basic V11 tags to PLC addresses on a KTP600

HMI and touchscreens Published 6 min read By IMDTouch engineering team

Short answer

A KTP600 Basic color runs screens, not your control logic. The E0.0-to-A0.0 behavior belongs in the PLC program; WinCC Basic V11 contributes Boolean HMI tags bound to those PLC addresses over one configured connection, and the compiled configuration downloads to the panel while the rung stays on the controller.

On this page
  1. The panel visualizes, the PLC decides
  2. What an HMI tag binds
  3. Create the connection first, then the tags
  4. Worked example: three Bool tags for E0.0 and A0.0
  5. Compile and download to two targets
  6. When the screen freezes or lags
  7. The decision, case by case
  8. Questions asked

The behavior you want — toggle input E0.0, watch output A0.0 follow to 1 — is a ladder rung, and a KTP600 Basic color panel does not run ladder rungs. The panel is a visualization terminal: WinCC Basic V11 builds its screens, and those screens exchange values with the PLC through HMI tags bound to PLC addresses over one configured connection. The rung that assigns the output from the input stays in the PLC program. The panel reads the two addresses through Bool tags and, where the operator should command from glass, writes a memory bit that the PLC logic evaluates. Compile the configuration, download it to the panel, and keep the control program on its own transfer to the controller.

The panel visualizes, the PLC decides #

A KTP600 Basic color executes screens: it draws objects, runs the actions bound to them and exchanges tag values with the controllers named in its connections. It has no scan cycle that assigns outputs and no home for your control logic. The ladder that makes the output follow the input belongs in the PLC program, written with the PLC programming tool; the screens belong in WinCC Basic V11. The two tools can share one engineering project, but they compile separately and download separately — one compilation into the controller, one into the panel. The software split is laid out in Which software programs an S7-300 PLC and which runs the HMI.

WinCC Basic is the tier of the WinCC family that serves Basic Panels such as the KTP600; the tool-to-panel pairing across manufacturers is set out in Which HMI Software Works With Which HMI Panel Hardware.

What an HMI tag binds #

An HMI tag is a named value with a data type. A tag pointed at the controller also carries the connection and the PLC address, and every screen object bound to that tag reads or writes the operand behind it. An internal tag, listed in the project's Internal Tags area, gets a name and a data type but no connection and no controller address.

For this binary example the data type is Bool: one bit, false or true. Keep names short — WinCC documentation sets a 128-character cap on tag names, and a short name never has to test the limit on any version.

Create the connection first, then the tags #

A tag binds to an address only through a connection, so build the connection first. In the connection settings of the HMI project, select "New Driver Connection" and fill in the parameters of the PLC: its address and the interface the panel actually has. The PN variant of the KTP600 speaks PROFINET over Ethernet; the DP variant joins a PROFIBUS line under the PLC's DP master — a KTP600 Basic DP beside a CPU 313C-2 DP, for example, takes its station parameters from that master configuration. With the PLC entry in place, right-click it and select "New tag", then give each tag its data type and address.

Then the rule that keeps a screen honest: read process data from process addresses, and command through a memory bit. A panel button bound to a physical input address writes into a process image the wiring refreshes every scan, so the write evaporates before the logic reads it — Why WinCC Start and Stop buttons do not control an S7-300 output shows that failure exactly. A button bound straight to an output address is just as wrong: it fights the rung that assigns the same output.

Worked example: three Bool tags for E0.0 and A0.0 #

In the PLC program the rung reads A0.0 := E0.0, and for panel operation it grows one term: A0.0 := E0.0 OR M0.0, where M0.0 is a memory bit reserved for the operator command. The HMI side then carries three tags:

Tag (example name) Data type Connection (example) PLC address Role
Switch_State Bool PLC_1 E0.0 panel reads the physical switch
Lamp_State Bool PLC_1 A0.0 panel reads the output
Panel_Cmd Bool PLC_1 M0.0 panel button writes the command bit

A Bool tag occupies one bit. Address E0.0 is byte 0, bit 0 of the input image, so binding it uses 1 of that byte's 8 bits and leaves the other 7 (E0.1 through E0.7) free for further input tags; the same one-bit arithmetic sizes the tags on A0.0 and M0.0. On the screen, bind the switch indicator to Switch_State and the lamp indicator to Lamp_State — never to Panel_Cmd, which proves only that the button was pressed. The button's switch action binds to Panel_Cmd.

The states then walk like this:

  • Switch open, button untouched: E0.0 = 0 and M0.0 = 0, so the rung assigns A0.0 = 0; all three tags read 0 and both indicators stay dark.
  • Switch closed: E0.0 = 1 assigns A0.0 = 1; Switch_State and Lamp_State both read 1 and the screen lights both indicators.
  • Button pressed, switch open: M0.0 = 1 and the OR term drives A0.0 = 1, so Lamp_State reads 1 while Switch_State still reads 0. That split — command at 1, input at 0, output at 1 — is the proof the tags sit on the right operands.

Commission the button with the actuator disconnected or the machine in a safe state: a Bool write from the panel takes effect immediately, with no permissive your logic does not add.

Compile and download to two targets #

Compile the HMI project before any transfer: an unknown tag, a wrong data type or a missing connection fails the compile there instead of failing live on the panel. The panel download then loads screens, tags and the connection into the KTP600 — it never loads the control program into the panel. A change to the rung is the opposite trip: the PLC program travels through the PLC programming tool while the panel keeps running. The route follows the panel's interface: the PN variant takes its configuration over Ethernet, while the DP variant loads through the transfer hardware of its service interface, as Why a KTP600 Basic DP needs a PC Adapter USB A2 for transfer explains.

When the screen freezes or lags #

A screen full of hash marks is the documented connection fault, not a tag fault: the Basic Panels operating instructions state that when communication between the HMI device and the PLC is interrupted, every displayed tag value is replaced by a hash mark (#). So # on every field sends you to the cable, the addresses and the connection settings before the tag table.

Screen refresh is asynchronous to the PLC scan: the panel exchanges values and redraws on its own cycle, so a short lag between closing the switch and the lamp changing is not evidence the rung is wrong. Compare the PLC's online value of the output with the tag on the screen at the same instant; if the controller already shows 1 and the panel still shows 0, the fault sits in the connection or the binding, and Is It the Driver, the Tag or the Screen? Diagnosing HMI Values walks that split object by object.

The decision, case by case #

  • Physical switch only: keep A0.0 := E0.0 in the PLC, bind two read Bool tags to E0.0 and A0.0, and display both. The panel carries no logic.
  • Touchscreen switch: bind the button to a writable Bool memory-bit tag such as M0.0, reserve that bit in the PLC program, and evaluate it in the rung beside the physical input. Never bind a command to an input address and never write the output from the panel.
  • Both sources: combine them in the rung as A0.0 := E0.0 OR M0.0, display all three tags, and let the PLC own the priority. One connection, Bool types, compile before download — that is the whole recipe the KTP600 needs to mirror your rung on glass.

Questions asked

What must a firewall pass for remote access to the PLC?

S7 communication to the PLC runs over TCP port 102, so a firewall or port-forwarding rule in front of the controller must pass that port for program transfers and online connections. Keep the panel's own transfer path in the same plan: the KTP600 is reached through its configured interface, and remote setups forward the ports for panel and PLC separately. The two downloads stay distinct transfers regardless of how the ports are forwarded.

When do I need an internal tag instead of a PLC tag?

Choose an internal tag when a value matters only to the screens — a page counter, a stored selection, a temporary marker between two displays. It gets a name and a data type but no connection and no PLC address, so it costs no controller traffic and cannot disturb the process image. Anything the PLC logic must see or decide belongs in a PLC-connected tag with the controller address instead.

Are E0.0 and A0.0 the same points as I0.0 and Q0.0?

Yes. E and A are the German-style operand letters for input and output, and I and Q are the English-style letters for the same physical points. The address layout is identical: byte 0, bit 0 in both notations. A tag bound to E0.0 reads the exact point an English-notation program calls I0.0, so pick the notation your project and CPU use and stay consistent.

Keep reading

  • Explainer

    Why a WinCC flexible panel tag limit comes from the panel itself

    The tag capacity of a WinCC flexible panel is a hardware specification: the Number of variables per device entry in the panel's own Technical Data, under Functionality. For order number 6AV6647-0AC11-3AX0 that entry states 500. WinCC Explorer tag tiers such as 1024, 2048 or 8192 license the software product and never transfer to the target panel.

    HMI and touchscreens

  • Explainer

    Why KTP400 Basic Color PN is missing in WinCC flexible

    The KTP400 Basic Color PN (6AV6647-0AK11-3AX0) is not configurable in WinCC flexible 2008 in any service pack; the missing catalog entry is a support boundary, not a fault in your installation. Engineering starts in TIA Portal V11 SP2. A STEP 7 V5.6 controller project is either migrated into TIA Portal or kept separate behind a PLC proxy.

    HMI and touchscreens

  • How-to

    Binding PLC tags from different DBs to a WinCC HMI UDT

    No configuration makes an HMI UDT span multiple data blocks: a structured HMI tag resolves to one addressable PLC instance. With the PLC program frozen, keep every existing address, create one external HMI tag per variable, and assign them to the faceplate interface properties at each instance; the screen-window tag prefix cannot supply per-equipment data and only reaches shared values with the documented marker.

    HMI and touchscreens

Why WinCC Runtime Advanced Has No Screens Folder