IMDTouchKnowledge BaseShop main store

How-to

Configuring a TP900 Comfort panel with a CPU 412-5H project

HMI and touchscreens Published 6 min read By IMDTouch engineering team

Short answer

Configure the TP900 Comfort in WinCC Comfort under TIA Portal; WinCC flexible cannot engineer it. Keep the CPU 412-5H in its STEP 7 V5.x project and link both through the vendor's combined configuration workflow or Devices Proxy-PLC, then prove tag addresses before any writes.

On this page
  1. Which engineering tool configures a TP900 Comfort panel?
  2. Why can't WinCC flexible be made to support a TP900?
  3. Why does the TIA Portal catalog not list the CPU 412-5H?
  4. How does combined configuration link the panel and the controller projects?
  5. How do you keep panel tags matched to controller addresses?
  6. How do you compile and transfer the project to the panel?
  7. How do you prove the connection works before the machine runs?
  8. Questions asked

Configure the TP900 Comfort in WinCC Comfort inside TIA Portal and leave the CPU 412-5H where it already is, in its STEP 7 V5.x project; the two projects then meet through the vendor's documented combined configuration. There is no library, option package or device file that lets WinCC flexible engineer a Comfort panel, and there is no need to move the fault-tolerant S7-400H controller into TIA Portal to make the pair work. This article walks through the tool boundaries, the combined-configuration link, tag agreement across the two projects, and the compile, transfer and acceptance checks that prove the connection before the machine runs.

Which engineering tool configures a TP900 Comfort panel? #

A TP900 Comfort, part number 6AV2124-0JC01-0AX0, is engineered only in WinCC Comfort inside TIA Portal, so confirm the installed version's HMI device catalog lists that part number before you create the project. Every panel in the Comfort family follows the same pairing rule, which the page on which HMI software works with which HMI panel hardware lays out device by device, and the article on which software configures a KP1200 Comfort panel reaches the same conclusion for its model. If your installed TIA Portal edition does not offer the TP900 Comfort in the device selection, the engineering capability is missing from that installation, not from the panel: it comes with WinCC Comfort or a higher WinCC edition. Start the panel project only in an installation that shows the device.

Why can't WinCC flexible be made to support a TP900? #

It cannot: Comfort panels are not an engineering target of WinCC flexible, so no support package, device library or option file turns WinCC flexible into a tool that compiles a TP900 Comfort project. WinCC flexible served the panel generations before Comfort, and its device support ends there. If you hold an existing flexible project for an older panel, the supported path forward is migration into TIA Portal, as the walkthrough on migrating a WinCC flexible project to TIA Portal describes. A library entry that merely draws a TP900 shape would never produce a compilable, transferable project, so drop that route early and plan the WinCC Comfort project instead.

Why does the TIA Portal catalog not list the CPU 412-5H? #

The CPU 412-5H is engineered in STEP 7 V5.x, outside the TIA Portal project, so the panel project never needs that controller in its own hardware catalog and the missing entry is expected, not a fault. Catalog membership decides where you configure the controller, not whether the panel can exchange data with it. The S7-400 connection is set up from the panel side in its connection settings, and the controller-side endpoint comes from the existing STEP 7 V5.x hardware configuration. For the general pattern of checking which controllers and modules a given TIA Portal version catalogs, and where that boundary is documented, the page on which STEP 7 V5.5 modules TIA Portal supports and where to look walks through the check. Keep ordinary data exchange separate from redundant-system behavior: a connection that works against one CPU endpoint says nothing about what happens when the active controller switches over, so if the HMI must stay operational through a switchover, verify the documented connection arrangement for that before commissioning.

Use the combined configuration workflow of the vendor's support document ID 73502293, which pairs WinCC in TIA Portal with STEP 7 V5.x, and its separate-projects variant built on the Devices Proxy-PLC function. In the combined form, one engineering setup carries the panel project together with the link to the STEP 7 V5.x controller project, and the controller's interface data reaches the panel project through that documented workflow. In the separate-projects form, the panel project stands alone and Devices Proxy-PLC supplies the reference to the controller project, keeping the STEP 7 project's storage, versioning and ownership untouched. Choose the combined form when the engineering station can hold the shared project setup; choose the proxy form when the controller project must stay fully independent of TIA Portal work. Both forms end at the same place: a panel project whose tags reference controller variables in the STEP 7 V5.x project.

How do you keep panel tags matched to controller addresses? #

Treat each controller variable as an interface item whose address, data type and access direction must match the panel tag exactly, because a plausible number read from the wrong bytes looks correct on screen. The classic failure is a data type mismatch at a correct offset, and a short worked example shows how badly it fails.

Worked example. Suppose Batch_Temp is declared in DB50 at byte offset 12 with data type REAL, so it occupies DB50.DBD12 through DB50.DBD15, and the controller's online monitor shows 78.5 °C. The 32-bit REAL encoding of 78.5 is 0x429D0000. If the panel tag is created at the same offset with data type DInt, the panel decodes those same four bytes as a signed integer and displays 1117585408. Setting the tag's data type to Real restores the display of 78.5. The offset was never wrong; the type was.

Hold an interface list with every exchanged variable, its address, data type, access direction and meaning. Keep that list under revision control together with both projects, and treat any controller address or data-layout change as an interface change that the panel side must review before the next transfer.

How do you compile and transfer the project to the panel? #

Build the first panel application around one diagnostic screen, compile it clean, verify the panel image, and transfer it before any controller data is trusted.

  1. Select the TP900 Comfort as the device in WinCC Comfort and create a single diagnostic screen that shows one test value and the connection status.
  2. Add a read-only test tag through the combined-configuration or Devices Proxy-PLC link, taken from the controller project's own declaration.
  3. Compile the panel project and clear every connection, tag and device error before attempting a transfer.
  4. Check the image installed on the panel against the project version family; the article on matching an HMI panel image to its TIA Portal project version covers what to compare, and any image update follows the vendor's documented procedure for the exact model.
  5. Transfer the project over the configured transfer path, then start the runtime on the panel.

Screen artwork lives in the project's graphics collection and can be exported, edited and imported again if graphics need rework. Remember that the transfer path only loads the application; the process-data connection carries controller values, and a successful transfer proves only the first of the two.

How do you prove the connection works before the machine runs? #

Prove the read path first with one known read-only status value, compare the panel display against the controller's online value, and only then test an approved write on the bench. Open the diagnostic screen, confirm the connection status goes operational, and check the displayed test value against the controller's online monitoring of the same variable: address, data type and engineering value should agree. A number on the screen alone is weak evidence, because it may be stale or scaled wrongly. For the write path, command a change to a value that is safe to alter, watch it arrive in the controller's online status, and record the round trip. Make that first write on a bench setup or on a value that cannot move the machine, never against live outputs, and delay setpoints and commands until the read map is fully proven.

Questions asked

Can I keep my existing WinCC flexible project and just add the TP900 to it?

No. WinCC flexible cannot engineer any Comfort panel, so the supported route is to migrate the flexible project into TIA Portal and finish the screens in WinCC Comfort. Some screens and objects transfer automatically, but check each screen after migration, because not every legacy object type survives the move.

Do I have to migrate the CPU 412-5H project into TIA Portal?

No. The combined configuration workflow exists precisely for this case: the controller keeps its STEP 7 V5.x project with its hardware configuration and program untouched, while the panel project references it for tags. Migrating a fault-tolerant S7-400H controller into TIA Portal is a separate and much larger decision, and it is not needed to make the connection work.

What is the Devices Proxy-PLC function used for?

It is the function for the separate-projects form of combined configuration: the panel project in TIA Portal references the tags of a controller project that remains in STEP 7 V5.x, without merging the two into one file. Use it when the two engineering teams or tool versions must stay independent of each other.

Does the panel need a matching image version?

Yes. The image on the panel must match the project version family produced by the engineering tool; a mismatch shows up as a transfer or version error rather than a screen fault. Update the image with the vendor's documented procedure for the exact panel model before transferring the project.

Keep reading

  • Troubleshooting

    Why WinCC Flexible 2008 SP5 runtime closes without a message

    A runtime that opens and closes without a message 10 to 20 seconds after launch is a startup-path termination, not a license fault. Record the exact Windows 10 build with winver, install the Update (Hotfix) for WinCC flexible 2008 Service Pack 5 delivered at the end of Update 2, and correct the Project ID area pointer in the connections editor. The msjet40 archive failure is a symptom branch; rebuilt MDB files hold about a day, then the exit returns.

    HMI and touchscreens

  • How-to

    Configuring WinCC Professional Modbus TCP tags to read a device

    You never build a Modbus request in WinCC Professional. Add the WinCC RT Professional device, create a connection on the Modicon Modbus TCP/IP driver, create an external tag for the register, and bind an I/O field to it — runtime polls automatically. Modbus TCP is not Modbus RTU: TCP frames carry an MBAP header and no CRC, so an RS-485 slave needs a Modbus TCP-to-RTU gateway, not a passive adapter.

    HMI and touchscreens

  • Explainer

    Why a WinCC Flexible project on a server needs the tool on your PC

    The project files can live on the server, but the engineering tool cannot: WinCC Flexible must be installed on the PC you sit at, and Windows Server 2003 cannot host it. In the reported case, Windows 7 Professional and Windows XP Professional clients running WinCC Flexible SP3 opened the server-hosted projects without the message, while matching users and SIMATIC group memberships changed nothing.

    HMI and touchscreens

TP900 Comfort to MicroLogix 1100 EtherNet/IP connection