Connecting a KTP600 to LOGO 8 with WinCC V13

HMI and touchscreens Published 7 min read By IMDTouch engineering team

Short answer

A KTP600 Basic connects to a LOGO! 8 with an S7 connection in TIA Portal V13: choose the S7-200 driver, enable Allow S7 access in the LOGO! project, place both devices in one IP subnet, and bind tags to the V addresses the LOGO! mapping table assigns. Prove it with one forced value read back on the panel before building screens; the Siemens V11 example shows the arrangement, your 0BA8 supplies the addresses.

On this page
  1. Which driver does a KTP600 Basic use to reach a LOGO! 8?
  2. How do you allow S7 access in the LOGO! 8 project?
  3. What IP settings must the KTP600 and the LOGO! share?
  4. How do you bind KTP600 tags to LOGO! VM addresses?
  5. Does the LOGO! 0BA7 WinCC V11 example transfer to V13?
  6. How do you prove the connection before building screens?
  7. Why does the panel show a fault or a wrong value?
  8. Questions asked

Use an S7 connection with the S7-200 driver: a LOGO! 8 (0BA8) serves its variable memory as a V area over S7 protocol, and that driver's addresses are exactly what the LOGO! mapping table produces. Then allow S7 access in the LOGO! project, put the panel and the controller in one IP subnet, and bind every KTP600 tag to the address the mapping assigns. Siemens publishes this arrangement as an HMI communication example for LOGO! 0BA7 with WinCC V11; the steps carry over to WinCC V13 and 0BA8, but every address comes from the installed LOGO! 8, never from the example. The checks below run in the order that saves you the most rework.

Which driver does a KTP600 Basic use to reach a LOGO! 8? #

Choose the S7-200 driver in the connection's properties: the LOGO! 8 presents its variable memory as an S7-200-style V area, so that driver's address column matches the LOGO! mapping, while the S7-1200 or S7-300/400 drivers address memory the LOGO! does not serve. A KTP 600 Basic PN is a 6-inch touch panel engineered in TIA Portal, so the driver list comes from the device entry you configure, not from the name printed on the bezel.

  1. Read the complete order number and device version from the panel's rating plate or its device information screen.
  2. In TIA Portal V13, insert the KTP600 with exactly that device version; if the version is missing from the hardware catalog, update the catalog first, because a substituted device changes the available drivers.
  3. Open Connections in the panel's device configuration, add a connection and set its driver to the S7-200 entry. If your catalog labels it differently, pick the connection whose address format is the V area — that property, not the label, is what the LOGO! requires.
  4. Leave the partner address for the subnet step below; a compiled project at this point proves the configuration processes, not that the panel communicates.

The same driver decision is behind why a LOGO 0BA8 clock transfer needs VW991 and the right HMI driver: with the wrong driver, no address ever works, however carefully the values are arranged.

How do you allow S7 access in the LOGO! 8 project? #

Open Ethernet Connections in the LOGO! engineering software and enable Allow S7 access: without that option the LOGO! refuses the panel's S7 session even with a perfect IP path, and the panel reports a connection fault.

  1. In the LOGO! project, right-click Ethernet Connections and choose Add connections if the project needs a connection entry for the panel's address.
  2. In the Ethernet Connections editor, check Allow S7 access.
  3. Download the project to the LOGO!; the option only takes effect on the device after the download.
  4. Work on this side first whenever a reachable LOGO! still refuses the panel, because the setting is project data and a project saved without it closes the door again on the next download.

What IP settings must the KTP600 and the LOGO! share? #

Give the panel and the LOGO! unique addresses in the same subnet, because the S7 session needs a direct or routed path and runs over TCP port 102. Any managed switch or firewall between the two addresses must pass that port, since it is the only one the session uses.

Worked example with illustrative addresses: place the LOGO! at 192.168.0.10 with mask 255.255.255.0 and the KTP600 at 192.168.0.20 with the same mask. The subnet test is a bitwise AND of address and mask, octet by octet: 192.168.0.10 AND 255.255.255.0 = 192.168.0.0, and 192.168.0.20 AND 255.255.255.0 = 192.168.0.0. The networks match, so a direct cable or an unmanaged switch carries the session and no router enters the path. Move the LOGO! to 192.168.1.10 instead and its network becomes 192.168.1.0 against the panel's 192.168.0.0: with no router between them the LOGO! is unreachable, and the fix is to readdress one device into the other's subnet rather than to add a router.

  1. Read the LOGO!'s active address from its network settings in the LOGO! software, and the panel's from its own network settings page.
  2. Type the LOGO!'s live address into the connection's partner address field — never the address an example project used.
  3. Scan from the engineering PC with TIA Portal's accessible-devices view; the LOGO! must appear at its address.
  4. Only then trust any cable or switch you did not verify yourself.

How do you bind KTP600 tags to LOGO! VM addresses? #

Copy each tag's address from the LOGO! mapping table and enter it unchanged in the KTP600 tag table with the matching data type, because that table is the only authority on where a value lives. The addresses follow V-area rules, shown here with example values: a bit is written V301.2, a word such as VW300 spans the two bytes VB300 and VB301, and a double word such as VD300 spans VB300 to VB303. A BOOL tag must therefore point at a bit mapping and a Word or UnsignedInt tag at a word mapping; a type one size off reads a neighbouring value.

For a walk-through of finding a parameter's mapped address, setting a LOGO 0BA8 timer from a KP400 HMI via VM mapping covers the LOGO! side. For the tag-table mechanics on this panel family, binding WinCC Basic V11 tags to PLC addresses on a KTP600 shows the WinCC side.

Does the LOGO! 0BA7 WinCC V11 example transfer to V13? #

Carry the arrangement over and nothing else: the driver choice, the Allow S7 access step and the V-area addressing are the same for 0BA8 under V13, while every device entry and address must come from your installed hardware.

Item The 0BA7 example in WinCC V11 Your KTP600 with LOGO! 8 in V13
Controller LOGO! 0BA7 LOGO! 0BA8 with its own mapping table
Panel device entry the example's target your panel's exact device version
Connection address the example's address the LOGO!'s live address in your subnet
Tag addresses the example's mapped parameters the V addresses your project maps

A converted project that compiles proves the engineering data processes, not that the panel communicates; the proof is the read-back in the next section. When the screens you inherit were drawn for a KTP700, converting KTP700 HMI screens to a KTP600 Basic panel is a separate adaptation with its own steps.

How do you prove the connection before building screens? #

Download both projects and watch one known value cross the link: force a parameter in the LOGO! online view and read it back on the panel, because one correct round trip proves driver, session and address together.

  1. Create one test screen with an I/O field on a parameter you can watch in the LOGO! online view, for example a timer value, and set the tag's acquisition cycle to 1 s for the test.
  2. Download the LOGO! project, then the panel project, and let the panel start runtime.
  3. Force or toggle the parameter from the LOGO! software and watch the panel field follow within the acquisition cycle.
  4. Write from the panel to a writable parameter and confirm the change in the LOGO! online view; a read-only test misses the write direction.
  5. Build the real screens only after both directions pass.

Why does the panel show a fault or a wrong value? #

Separate the two failure patterns first: a connection fault with a reachable address points at the session — driver, TSAPs or missing S7 access — while a live but wrong value points at the tag's address or data type.

  • Connection fault although the LOGO! appears in the scan: the driver is wrong for the LOGO!, Allow S7 access is missing, or the TSAPs sit on the wrong end; why a LOGO 0BA7 HMI connection fails despite matching TSAPs shows how that failure looks with correct-looking values.
  • Connection fine, value frozen: the address points at unmapped VM or at a parameter that is not changing; compare with the LOGO! online view before touching the network.
  • Value moves in jumps of 256: the tag sits one byte off the mapped word, usually a byte type where the mapping is a word; correct the address or the type.

Questions asked

Can the LOGO! 8 be read over Modbus TCP instead?

LOGO! 8 also runs a Modbus TCP server on port 502, and panels that lack an S7 driver are usually pointed there. A KTP600 engineered in TIA Portal stays on the S7 connection, because its tag addresses and the LOGO! mapping are built around the V area. Both servers coexist in the LOGO!, so a second client can read Modbus while the panel reads S7.

Why does the connection drop when a new LOGO! project is downloaded?

A LOGO! download restarts the CPU, so every active S7 session drops and the panel shows a brief connection fault until it reconnects on its own. If the fault never clears afterwards, the project you loaded was built without Allow S7 access; open that project, enable the option and download again.

Where do the TSAP values for the S7-200 driver come from?

When the S7-200 driver's connection dialog asks for a local and a remote TSAP, the remote one is the LOGO!'s listening endpoint and the local one belongs to the panel. Take the LOGO! value from the 0BA8 S7-access documentation, not from an 0BA7 example: a TSAP entered on the wrong end produces a connection that never establishes although the address answers ping.

Will screens made for a KTP700 fit the KTP600?

Not unchanged: the KTP600 Basic has a 6-inch display, so screens laid out for the 7-inch KTP700 need every element re-spaced after the device change in TIA Portal. The tag table and the connection carry over with the project; only the visualization objects need the adaptation, and alarm texts usually survive untouched.

Keep reading

  • How-to

    Connecting a LOGO! 0BA8 to an MT8050iE HMI over Ethernet

    Yes, a LOGO! 0BA8 connects to a Weintek MT8050iE over Ethernet using the Siemens LOGO! (Ethernet) driver in EasyBuilder Pro, with both devices on the same subnet and a server-side Ethernet connection defined in the LOGO! project; prove the link with one read tag, then add writes only after that read follows a value you change in the controller.

    HMI and touchscreens

  • Explainer

    Why one HMI cannot watch twelve LOGO controllers at once

    Twelve LOGO! 8 controllers exceed a KTP400 Basic's documented four controller connections, so one Basic panel cannot watch them all: 12 ÷ 4 = 3 panels. One shared screen needs a panel rated for sixteen controller connections used directly, or one collector LOGO! holding the twelve inbound links behind a single connection to the display; the eight-analog-input figure is per-controller wired I/O and never limits alarms crossing Ethernet.

    HMI and touchscreens

  • How-to

    Connecting WinCC to PLCSIM Through the S7Online Access Point

    WinCC exchanges external tags with an S7-300 program in PLCSIM through the MPI channel of SIMATIC S7 Protocol Suite with logical device name S7Online, station address 2 and slot number 2. The deciding point is the complete access-point route to the simulated CPU; setting PG/PC to None is installation-dependent, not a required step.

    HMI and touchscreens

Running a LOGO! Web Editor project beside a TP700 panel