Knowledge Base
Earlier articles
Troubleshooting
Why a KTP 1000 screen fails at 244 configured items
The error means exactly what it says: screen Ana_Ekran carries 244 configured screen items and the KTP 1000 PN/DP target allows 200 per screen, so at least 44 counted items must come off that one screen. Hiding objects, visibility animations and editor grouping do not lower the compiler's count; deleting objects, replacing static artwork with a single graphics object, or moving content to another screen does. Recompile after each change.
How-to
Getting gateway sensor data onto an HMI with a Modbus TCP bridge
An HMI cannot poll a Node-RED application, so put the sensor values into a Modbus TCP server with a fixed register map and point the HMI's client driver at that server on TCP port 502. Run the server in the gateway's Node-RED when its runtime accepts the Modbus package; otherwise run it on a separate host. Add a heartbeat and a data-age register so the display can tell fresh values from retained ones.
Troubleshooting
Why a Dark Mark Stays Fixed on an HMI Screen
Stop the HMI runtime and look at the same spot on the operating system desktop. A mark that stays at one physical location outside the application is a display or mounting fault: ease the frame clamping as a test, and if the mark survives, book display repair or replacement. A mark that shows up only on one application screen is content, and you fix it in the project.
Troubleshooting
Why an online simulator cannot reach a simulated S7 PLC endpoint
The failure is a missing network endpoint, not a tag or driver fault. An HMI online simulator needs a host-reachable Ethernet address that serves the configured protocol; a simulated PLC that exists only inside the engineering tool's private context offers none, and no tag edit or undocumented bridge can fix that. Give the runtime a physical PLC or a simulator interface documented as externally reachable with explicit protocol support.
How-to
Simulate two HMI panels in WinCC Advanced V13 SP2
TIA Portal V13 SP2 with WinCC Advanced starts only one simulated panel at a time. To run two, copy an HmiRTm.ini into the WinCCRT Adv folder, set OnlyOneInstance to false, point LoadConfigFile at each compiled .fwc file, and start HMIRTM.exe once per panel.
Troubleshooting
Why HMI Alarm History Shows Live Embedded Variable Values
An alarm-history row stores the variable reference, not the value: the panel redraws each embedded variable with the current reading, so older rows drift as the process changes. Prove it with a noncritical test tag; take event-time values from the alarm export or a controller latch; keep any live number in history text explicitly labeled.
Explainer
Why a standalone HMI editor is missing from your IDE
A missing standalone HMI executable does not mean web HMI support is gone. Current IDE versions build the operator interface with an integrated HMI editor and keep the separate application for legacy projects. Read the version, identify the project type and use the matching editor before reinstalling or installing anything older.
Troubleshooting
When an HMI and PLC ping but will not communicate
A ping proves only IP reachability. Build a minimal test project with one online-imported tag: if it shows live values, the network, the Put/Get permission and the access level are good, and stale tag references in the production project are the fault. Re-import the tags online, correct the flagged entries, recompile and download.
Troubleshooting
Why an industrial panel PC takes 30 minutes to boot
A 30-minute boot that ends in a normally running SCADA runtime is a platform firmware fault, not a software fault: the BIOS is waiting for the chipset's management engine, whose firmware is corrupted or mismatched. Time the boot phases to confirm, request the panel vendor's documented management engine firmware package, install every service package in release order, and keep registry cleaners out of the recovery path.
How-to
Run and Stop a SIMOTION CPU from a Comfort Panel HMI
Write the device system variable modeOfOperation from the Comfort Panel connection: 0 puts the SIMOTION CPU in STOP and 3 puts it in RUN. Find it in SCOUT's Symbol Browser under the selected CPU, bind it as a tag, and drive two separate momentary buttons.
Explainer
Why an HMI touch foil is not a field-replaceable part
HMI vendors supply the touch front as a bonded, calibrated, factory-sealed assembly and handle its failure through a repair-exchange service, not a foil spare kit. Isolate calibration, permissions and display faults first, back up the project before the panel ships, and treat the returned unit as wiped.
Troubleshooting
Why a Vijeo Designer runtime freezes after a few days
The freeze sits inside the Vijeo Designer runtime process, not the PC: the displayed clock stops, other Windows applications keep running, and relaunching only the runtime recovers it. Rebuild and retransfer the project from a development environment set to English, then run it at least four days before calling it fixed.