Explainer
Projected capacitive touchscreens: why they skip calibration
Projected capacitive touchscreens need no calibration out of the box: the controller maps touches from electrode positions fixed at manufacture. A resistive overlay reads an analog ratio that depends on how the film is mounted, so it works only when the controller's management software ships a calibration routine — verify that support before you specify resistive. Connect the display through its native HDMI port rather than an HDMI-to-DVI or HDMI-to-VGA converter, whose results are configuration-dependent.
How-to
How WinCC Runtime Color Selection Reaches a VBScript
No WinCC basic or Comfort panel ships a runtime color-picker control, but the operator does not need one. Configure each palette swatch as a screen object whose press event writes an assigned identifier to an internal HMI tag, and have the VBScript read that tag and resolve it to the destination color value.
Explainer
Why WinCC Flexible 2008 Cannot Pan an Oversized HMI Screen
WinCC flexible 2008 SP5 has no runtime panning and no automatic zooming, so a screen configured larger than the display runs cut off with no way to reach the rest. The project resolution is hardcoded by the configured device in Device Settings, so the fix is to change the device to one matching the display with Fit Screens and Screen Items to new Device enabled, or to split the content across screens.
Troubleshooting
Why a WP231 weight field shows blank on the HMI
The blank field is a symptom, not a display fault: the HMI output field only mirrors the ASCII weight string in DR34 of the WP231 instance DB. Check DR_NO and DR_LEN online — the fault showed 5 and 40 where the documented defaults are 34 and 26 — and confirm the data-record exchange repopulates DR34; a PLC reset cleared the symptom for a few days and then the fault returned.
Explainer
What the XSUB1 Block in a 505 Program Actually Does
XSUB1 in a TISOFT 505 program is compiled special-function code that runs PID loops; it is not a serial driver for the MP370 panel. The RS-232 link to the panel needs no XSUB and no special program — the panel project carries its own 505 driver and the CPU port only has to match it. On TI545, TI555 and CTI 2500 CPUs the loops are integrated, so the block's job moves to native PID at the next planned change.
How-to
PLC timer value on an HMI: start, stop and show after a win
Time the run in the PLC, not on the panel. A TONR accumulator runs while Sensor 1's run-active bit is high, Sensor 2 copies the elapsed value into a result tag and sets the win bit, and the KTP600 shows that one tag on an I/O field while the PLC-driven screen change opens the winning screen.
Troubleshooting
HMI Goes Black After Download: Wrong System Settings File
A black screen right after a finished download, with the backlight and power LED still lit, means the System Settings file was created for the wrong panel series. Delete that file, create a new one and select cMT X Series, rebuild the download package, then run Download (PC → HMI) again; the same transfer path that failed before then completes normally.
Selection guide
Running five machine HMIs and a line overview on WinCC Unified
Yes: one WinCC Unified project serves five machine screens plus a line overview. Choose between dedicated Unified panels per machine or one Unified PC Runtime with browser clients; the runtime license includes two access points but only one control-mode connection, so five operating stations need four additional WinCC Unified Client Operate licenses.
Troubleshooting
Why Git Commits Fail on an HMI Project Lock File
Git fails with permission denied on TcHmiSrv.lock inside the .engineering_servers/ project directory because the open HMI solution or the running engineering server holds the lock file. Close the HMI solution, add .engineering_servers/ to .gitignore, and if Git already tracks the directory, run git rm --cached -r on it before committing.
Explainer
Why an HMI second Ethernet port does not route PC Runtime to the PLC
A WinCC flexible transfer to the HMI's second Ethernet port proves only PC-to-HMI reachability. The two interfaces are separate networks; a PC Runtime reaches the controller through an explicitly configured network route or supported S7 routing, never automatic bridging inside the HMI.
Troubleshooting
Why a Screenless HDMI HMI Shows a Triple Image on a Bar LCD
The triple image is the bar panel failing to convert the screenless HMI's fixed 1920 x 1080 HDMI raster, not a project fault. The engineering tool sizes drawing windows inside that raster and cannot change the output timing. Prove the HMI and cable on a standard monitor, prove the panel on a PC, and replace the panel with one that documents 1080p input and a 1:1 mode — then verify USB touch on its own.
Troubleshooting
Why an S7-226 MPI Port Limits You to Three HMI Clients
An S7-226 accepts at most three simultaneous HMI connections on its MPI port, and a PC runtime counts as one of them. Three TP177A panels plus the PC is four clients, so one stays out no matter how you assign station addresses. Run a PPI multi-master network or add an EM277 PROFIBUS module to carry all four.