How-to
Updating an MP370 panel image for a WinCC flexible 2007 project
Short answer
Yes, an MP370 Touch 12-inch with image 6.0.3.2 runs a WinCC flexible 2007 project, but only after a panel image update to 7.2.0.0, the image that release offers for that target. Windows CE staying at 3.00 is normal: the panel image and the CE version are separate identifiers.
On this page
- What has to match
- Check the hardware and the project target
- Read the diagnostic the right way
- Run the image update and transfer
- Image version, boot loader and Windows CE are separate numbers
- Sizing the image update for the 6AV6 545-0DA10-0AX0 with image 6.0.3.2
- Verify the runtime on 24 MB of memory
- Questions asked
Yes. An MP370 Touch 12-inch TFT with order number 6AV6 545-0DA10-0AX0 running a ProTool project on image 6.0.3.2 will run a WinCC flexible 2007 project, but only after a panel image update to 7.2.0.0, the image that release offers for that target. Windows CE staying at 3.00 afterwards is expected: the panel image and the CE version are separate identifiers. This case was carried through to a running project, so the steps below are the ones that resolved it.
What has to match #
Three layers decide whether the project transfers and runs:
- The panel target configured in the WinCC flexible project.
- The runtime image installed on the panel.
- The Windows CE platform under that image.
The panel image is the device-specific runtime software package on the operator panel. It is not the same identifier as the CE base version, and the boot loader is a third identifier. Keep them apart or you will repeat updates that cannot fix a project-target mismatch.
The package name "Advanced" in the engineering license does not decide panel compatibility. The configured target and the installed image do.
Check the hardware and the project target #
- Read the panel designation and order number from the device label or device information. This case: MP370 Touch 12-inch TFT, 6AV6 545-0DA10-0AX0. If either differs, select the image and target definition for the hardware you actually have; a shared family name is not a sufficient match.
- Open the project's device configuration and confirm it targets that same MP370 class. If it targets another panel, correct the target or run the appropriate device change first.
- Record the baseline before touching anything: image 6.0.3.2, boot loader 1.06, Windows CE 3.00, 24 MB memory.
A ProTool project already running on the panel proves the hardware executes its current application. It does not prove the installed image executes anything generated by WinCC flexible 2007. Converting the project changes the runtime requirements even though the panel stays the same; for moving a project to different hardware instead, see the guide on how to migrate a ProTool HMI project to a new touch panel (article:how-to-migrate-a-protool-hmi-project-to-a-new-touch-panel).
Read the diagnostic the right way #
Read the image version in the panel's device information and compare it with the image options your WinCC flexible 2007 installation lists for the selected MP370 target. In this case 6.0.3.2 did not appear in that list, and that absence is the diagnostic, not the numerical gap between versions.
- Image not offered for the target: the installed image is not aligned with the image set your engineering configuration uses. Update the image.
- Image offered and accepted: alignment is fine; look at the hardware target and transfer settings instead.
- Order number or type differs from the device definition: you are comparing against the wrong device. Go back to the hardware check.
Never choose an image because its number is higher. Take the image the installed software presents for the exact panel type and order number.
Run the image update and transfer #
- Back up the ProTool project and any panel data you need for recovery. An image update is a maintenance operation that can require restoring the runtime application and retained data.
- Open or convert the application in WinCC flexible 2007 with the exact MP370 target selected.
- Obtain the MP370 image that engineering release supports, from Siemens support or its distributors; the one that resolved this case was 7.2.0.0. The vendor's OS-update procedure for WinCC flexible panels is documented in the Siemens support entry on operating system update with WinCC flexible.
- Put the panel into the transfer or update state and run the update over the configured communication path, with power and communications stable throughout.
- Restart the panel and read device information. Continue only when the image field reports the new version; CE may still read 3.00.
- Transfer the compiled project and start the runtime.
Image version, boot loader and Windows CE are separate numbers #
After the update, read all version fields instead of treating "OS" as one value. The image update replaces the device-specific runtime package; the package can sit on the same CE generation, so an unchanged CE reading does not mean the update failed. Verify success from the image field and from the application executing.
The boot loader, 1.06 on this unit, is a third identifier. Record it for maintenance, but do not read it as evidence that either the image or CE changed. The same version-designation question comes up when matching an HMI panel image to its TIA Portal project version (article:matching-an-hmi-panel-image-to-its-tia-portal-project-version); there too the project tool, the image and the platform version are checked separately.
Sizing the image update for the 6AV6 545-0DA10-0AX0 with image 6.0.3.2 #
Inputs, all from the reported case: panel MP370 Touch 12-inch TFT, order number 6AV6 545-0DA10-0AX0; installed image 6.0.3.2; boot loader 1.06; Windows CE 3.00; memory 24 MB; engineering tool WinCC flexible 2007.
The rule: the panel image must be one the engineering release offers for the selected target, and the project's target must be the panel's own type and order number. There is nothing to multiply; the check is a set membership and an equality.
Arithmetic as a comparison: image offered for the MP370 target in WinCC flexible 2007 = {7.2.0.0, ...}; installed image 6.0.3.2 is not in that set, so the panel fails the membership test. Project target order number 6AV6 545-0DA10-0AX0 equals the label reading 6AV6 545-0DA10-0AX0, so the equality test passes.
Result: one failed test, the image. Update the panel to 7.2.0.0, restart, confirm the image field reads 7.2.0.0, and transfer. CE remaining at 3.00 is not a failed test and needs no action.
Verify the runtime on 24 MB of memory #
The converted project in this case ran but operated slower than the old ProTool runtime. Compatibility and performance are separate acceptance criteria: a successful transfer proves the target and image can run the project, not equivalent response.
- Open every critical screen; each must load without a runtime termination or missing objects.
- Operate representative buttons, numeric inputs, alarms and navigation; one deliberate input gives one action.
- Watch controller values; live values update and commands reach the intended tags.
- If response is too slow, inspect screen object count, scripts, animations, alarm activity and communication demand. The 24 MB figure alone does not locate the bottleneck; measure screen-change and input-response times before and after trimming.
- Cycle power and repeat the critical path; the image stays at the new version and the runtime starts normally.
If the panel itself fails during this work and the repair is not worth it, an industrial panel PC running a PC runtime is the replacement path (https://industrialmonitordirect.com/collections/all-panel-pcs/).
One safety note: do the image update and the first transfers on a stopped machine or a bench setup, so a panel that reboots mid-update cannot leave an operator without a live interface.
Questions asked
Does an OS update change the Windows CE version on the MP370?
No. The update replaces the panel image, the device-specific runtime package, and the Windows CE base version can stay where it was. On this panel CE stayed at 3.00 while the image field moved to 7.2.0.0. Judge the update by the image field and by the application running, not by the CE reading.
Why is 6.0.3.2 not listed in the WinCC flexible 2007 device selection?
Because that release offers a different image set for the MP370 target than the one on the panel. The missing entry is the diagnostic: the installed image does not belong to the image set your engineering configuration uses. Do not pick an image because its number is higher; take the one the installed software presents for the exact panel type and order number.
The converted project runs but feels slower than the old runtime. What do I check?
Check screen object count, scripts, animations, alarm activity and communication demand on each slow screen. A successful transfer proves compatibility, not equivalent response on 24 MB hardware. Time screen changes and input response before and after trimming objects; if a screen stays too slow, split it or move cyclic scripts to event triggers.