Troubleshooting
Why the System Diagnostics View stays empty on a Comfort panel
Short answer
The System Diagnostics View is empty with four greyed-out buttons when the compiled PLC and HMI projects on the equipment do not match the edited configuration. Recompile hardware and software in both projects and download to both the PLC and the panel; the diagnostic messages then appear, including faults from third-party PROFINET devices.

On this page
A Comfort panel's System Diagnostics View that shows nothing but four greyed-out buttons is almost always running a compiled configuration that does not match the PLC's compiled configuration. The view is hardware-bound: it displays the diagnostic model of the devices configured in the PLC project, delivered through the HMI connection. When the panel runs an older compile, or the PLC was recompiled without the HMI following, there is nothing for the view to show. The fix is a coordinated compile of hardware and software in both projects and a download to both devices. This article walks the check order, explains why third-party PROFINET devices appear in the view, and separates this built-in display from the RALARM data-block approach. If you instead want diagnostics inside the PLC program, the same distinction matters for reading raw PLC tags as diagnostics in WinCC over OPC.
What the System Diagnostics View actually displays #
The view shows the operating state and diagnostic information of the connected, diagnostics-capable automation devices. It is not a generic browser of PLC data. It reads the controller's diagnostic system through the HMI connection you configure in the object's properties, and it lists the devices the controller supervises: the CPU itself, its modules and the configured PROFINET IO devices.
That has two consequences:
- Content comes from the PLC's hardware configuration. A device that is not configured in the PLC project cannot appear in the view, however healthy its wiring is.
- The panel needs its own matching compile. The HMI project carries the diagnostic object and its connection settings; downloading only the PLC leaves the panel running its previous compiled configuration.
This is why the empty view with four greyed-out buttons points at project alignment, not at a dead field device. Greyed-out buttons mean the view has no selectable content at its current level. They do not prove that third-party devices are excluded or that a station has failed. When your other screens read and write process tags normally, you know the HMI connection itself works, and the empty diagnostic view is a configuration mismatch, not a communication fault.
The fix: compile and download both projects #
Work through this list in order. The coordinated compile in steps 3 and 4 is the correction that restores the messages; the checks around it confirm you are not chasing a second problem.
- Confirm the connection the view uses. Open the System Diagnostics View on the panel screen and check, in its properties, which HMI connection it points to. A view bound to the wrong connection shows another device's diagnostics or nothing at all.
- Confirm the PLC hardware configuration matches the machine. Every PROFINET station must be configured with the correct device description (the GSDML file for third-party hardware), the correct device name and the correct module arrangement. Read the exact device identity from the hardware or the nameplate, not from a similar family member: a CPX valve terminal and a CPX-AP-I-PN-M12 diagnostic node are different configurations.
- Compile the PLC project, hardware and software. Recompile all so the controller's diagnostic model includes every configured station and module.
- Compile the HMI project and download to the panel. The HMI compile picks up the diagnostic object and connection configuration; the download replaces the panel's previous compiled revision.
- Download the PLC project to the controller. Both devices now run matching compiled configurations.
- Verify on the bench. With the machine safe, pull one PROFINET connector or remove one CPX module. The view should list the affected station and its fault within the connection's monitoring time, and recover when you restore it.
Record which compiled revision went to each device. If the fault recurs after a later edit, compare against that record before changing wiring: an obsolete compile on either side can make the view look broken while the controller reports useful faults in its own online diagnostics.
Third-party PROFINET devices in the view #
PROFINET diagnostics are not restricted to the controller manufacturer's devices. The IO controller supervises every configured IO device and reports station failures and any diagnostic information the device itself supplies. The HMI presents what the controller's diagnostic system knows.
How much detail you see depends on the device:
| Observation | What the controller can report | What the view shows |
|---|---|---|
| Station unreachable (blown fuse, cut cable) | Loss of the station on the network | Station fault; the device itself cannot explain why |
| Reachable station with a module fault | Module or channel diagnostics the device supplies | Module-level fault as interpreted by the configured device description |
| Module unplugged within a modular station | Depends on how the assembly maps its modules | The rank or slot if the device description reports it at that granularity |
For a missing CPX module, distinguish the station's position in the controller configuration from the physical module's rank inside the Festo assembly. Whether the view names the rank depends on how that assembly maps and reports a disconnection; compare the displayed location with the configured module arrangement.
Why RALARM and D_ACT_DP are a different path #
PLC instructions such as RALARM read PROFINET alarm records into a data block, and D_ACT_DP can identify a slot during network issues. That data is then displayed with ordinary HMI tags on a custom screen. It never becomes content inside the System Diagnostics View: tag bindings and the built-in diagnostic object use different information paths. So a working RALARM example project proves nothing about the view, and an empty view is not fixed by adding RALARM logic.
| Path | Information route | Best use | Engineering effort |
|---|---|---|---|
| System Diagnostics View | Controller diagnostic model through the HMI connection | Locating failed stations and hardware faults quickly | Matching compiled projects; no PLC code |
| RALARM/D_ACT_DP plus data block and HMI tags | PLC logic, stored values, tag reads | Device-specific interpreted text and detail the standard model lacks | PLC acquisition logic, data fields, tags, screen objects |
Use the view first. Add the custom path only when the view locates a failed station but maintenance needs the fault explained in their own terms. For tag-side planning across vendors, see which HMI software works with which HMI panel hardware.
Worked example: recovering the view on an S7-1214 with a TP1200 #
Inputs (from the reader's machine):
- PLC: S7-1214 CPU, firmware V4.2.
- HMI: TP1200 Comfort panel with a System Diagnostics View configured.
- Third-party PROFINET: one Festo CMMT-ST stepper motor controller and one Festo CPX valve terminal with inputs.
- Symptom: the view opens with four greyed-out buttons and no device entries, while process screens update normally.
The rule: the view displays only the diagnostic model delivered by the compiled PLC configuration, read through the HMI connection bound in the compiled HMI project. Both compiles must reflect the current configuration, and both must be downloaded.
The arithmetic of the check: there is nothing to calculate; the test is a count of matching revisions. Before the fix there are 2 compiled revisions on the devices (an older PLC compile, an older HMI compile) and 0 matching the edited projects, so the diagnostic model the panel holds lists 0 usable devices. After compiling and downloading both, the view lists every configured device: 1 CPU, 1 CMMT-ST station and 1 CPX station, so 3 entries at station level.
The decision: with process tags updating and the view empty, do not touch wiring or add PLC diagnostic code. Compile hardware and software in the PLC project, compile the HMI project, download both, and confirm the entries appear. This is exactly the correction that restored the messages on this installation; it worked with the third-party devices included, no RALARM logic required.
Safety note #
Test station-loss behavior on an isolated bench or with the machine in a safe state, never by pulling connectors on live production equipment: depending on the IO configuration, a lost station can force outputs to their substitute values.
Questions asked
Can the System Diagnostics View show faults from third-party PROFINET devices?
Yes. The IO controller supervises every configured IO device regardless of maker and reports station failures and the diagnostic information each device supplies. The view presents what the controller's diagnostic system knows, so a third-party valve terminal or drive controller appears when it is configured in the PLC hardware and the projects match.
What is the difference between the System Diagnostics View and the RALARM instruction?
RALARM is PLC logic that reads PROFINET alarm records into a data block, which you then display with ordinary HMI tags on a custom screen. The System Diagnostics View reads the controller's diagnostic model through the HMI connection and needs no PLC code. The two paths do not feed each other.
Why are the four navigation buttons greyed out?
They do not identify a failed station or exclude third-party devices. Compile and download both projects, then check the controller connection configured in the view's properties.
When should I build a custom diagnostic screen with PLC tags?
Build one when maintenance needs device-specific text, interpreted fault codes or values the controller's standard diagnostic model does not expose, such as slot-level detail read with D_ACT_DP or RALARM. Get the built-in view working first, then add the custom display beside it.


